Profile Selection
The DS-7C was designed to be as adaptable as possible to different operating requirements. The mode of
operation, called the “profile”, can be selected by setting the Profile Select switch. A profile is selected by
aligning the arrow on the screwdriver slot of the switch with the appropriate number or letter. The following
table lists the operating characteristics of each profile.
A CHANGE IN PROFILE WILL NOT TAKE
EFFECT UNTIL THE DS-7C HAS HAD POWER REMOVED, THEN REAPPLIED.
All profiles observe the
34
°
F to 44
°
F adjustable trigger temperature. Deice functions occur when temperatures are below or equal
to the trigger temperature and precipitation is detected. Rain functions occur when temperatures are above
the trigger temperature and precipitation is detected. Profiles noted as “Low Temp Cutoff” do not initially
trigger below 15
°
F but will retrigger if triggered above 15
°
F but temperature then drops below 15
°
F.
“Delay-Off” is the minimum time the relay will remain closed after a detection. All delays are restarted by a
detection during the Delay-Off period. Functions for the external control leads for each profile are listed.
Profile 0
Low Temp/Precipitation Sensor with Low Temp Cutoff
Profile 1
Low Temp/Precipitation Sensor without Low Temp Cutoff
Relay
Function
Delay-Off
Black
Low Temp Manual On
Relay 1
Low Temp
20 sec
Green
Low Temp Standby/Reset
Relay 2
Precip
20 sec
Red
Precip Manual On
Orange
Precip Standby/Reset
Profile 2
Deice/Rain Diversion Sensor with Low Temp Cutoff
Profile 3
Deice/Rain Diversion Sensor without Low Temp Cutoff
Relay
Function
Delay-Off
Black
Deice Manual On
Relay 1
Deice
20 sec
Green
Deice Standby/Reset
Relay 2
Rain
20 sec
Red
Rain Manual On
Orange
Rain Standby/Reset
Profile 4
Deice/Rain Diversion Controller with Low Temp Cutoff
Profile 5
Deice/Rain Diversion Controller without Low Temp Cutoff
Relay
Function
Delay-Off
Black
Deice Manual On
Relay 1
Deice
30-93 min
Green
Deice Standby/Reset
Relay 2
Rain
2 min
Red
Rain Manual On
Orange
Rain Standby/Reset
Profile 6
Dual Deice Controller with Low Temp Cutoff
Profile 7
Dual Deice Controller without Low Temp Cutoff
Relay
Function
Delay-Off
Black
Deice Manual On
Relay 1 & 2
Deice
30-93 min
Green
Deice Standby/Reset
Red
Not Used
Orange
Not Used
Profile 8
DS-9B Replacement with Delay, without Rain Diversion, and 2 Minute Cooldown
Relay
Function
Delay-Off
Black
Deice Manual On
Relay 1
Deice
30-93 min
Green
Deice Standby/Reset
Relay 2
Deice
Relay 1 + 2 min
Red
Not Used
Orange
Not Used
4
Profile 9
DS-9B Replacement with Delay On, Rain Diversion and 2 Minute Cooldown
Relay
Function
Delay-Off
Black
Deice Manual On
Relay 1
Deice
30-93 min
Green
Deice Standby/Reset
Relay 2
Deice
Relay 1 + 2 min
Red
Rain Manual On
Relay 2
Rain
2 min
Orange
Rain Standby/Reset
Profile A
Dual Deice Controller with 4
°
F Supercold Trigger
Relay
Function
Delay-Off
Black
Deice Manual On
Relay 1 & 2
Deice/Supercold
30-93 min
Green
Deice Standby/Reset
Red
Not Used
Orange
Not Used
Profile B
DS-9B/DDC-400 Sensor Replacement
Relay
Function
Delay-Off
Black
Deice Manual On
Relay 1
Deice
20 sec
Green
Deice Standby/Reset
Relay 2
Deice
Relay 1 + 2 min
Red
Rain Manual On
Relay 2
Rain
2 min
Orange
Rain Standby/Reset
Profile C
Deice/Rain Div Controller with Delay On, Rain Diversion and 30 Minute Cooldown
Relay
Function
Delay-Off
Black
Deice Manual On
Relay 1
Deice
30-93 min
Green
Deice Standby/Reset
Relay 2
Deice
Relay 1 + 30 min
Red
Rain Manual On
Relay 2
Rain
30 min
Orange
Rain Standby/Reset
Profile D
Not Assigned
Relay
Function
Delay-Off
Black
Relay 1
Green
Relay 2
Red
Orange
Profile E
Not Assigned
Relay
Function
Delay-Off
Black
Relay 1
Green
Relay 2
Red
Orange
Profile F
Not Assigned
Relay
Function
Delay-Off
Black
Relay 1
Green
Relay 2
Red
Orange
POWER MUST BE CYCLED AFTER CHANGING THE PROFILE SELECT SWITCH
L'alimentation Doit Être Redémarrée Après Avoir Changé Le Profil Select Switch
5