External Control/Monitor Operation 

The  DS-7C  provides  external  control  and  monitor 
capability.    Order  the  optional  CS-3  “Control  Cable”  and 
CS-4  “Monitor  Cable”  to  access  these  points.    External 
Control  allows the user to externally activate (Manual On) 
or disable and clear the delay (Standby/Reset) for the DS-
7C relays.  Connecting the White lead to a control lead will 
activate the function listed in the Profile Table.  This can be 
achieved using a switch or dry contact.  A “Standby/Reset” 
function  will  always  override  a  companion  “Manual  On” 
function. 
 
The external monitor points provide low power dry contact 
closures that mimic the operation of the load relays.  These 
relays,  rated  at  24  VAC/VDC  @ 400 mA, 10W maximum, 
will close with their respective load relays and can be used 
to externally monitor activation of the sensor. 

Typical Load Wiring 

The main relays are dry contacts and do not supply power directly to your load

 

The Yellow load leads and Red load leads connect to main relays 1 & 2 respectively.  Both relays in the 
DS-7C activate according to the selected profile.  These relays act as normally open switches and are fully 
isolated from each other.  Each relay is intended to switch a separate circuit.  Switching capacity of the DS-
7C is 30A per circuit, 2 separate circuits.  While not as convenient as directly supplying power for the load, 
dry contacts allow you to operate the DS-7C from one voltage while controlling loads of a different voltage 
without adding an external relay or contactor.  For example, the DS-7C can be powered from 120VAC but 
can  directly  control  a  240VAC  heater  and  a  120VAC  feed  blower  or  two  separate  277VAC  heat  cables.  
The following diagrams show some possible wiring schemes for connecting the DS-7C to your load.  Your 
load may be a direct connection to heat cable, a heater, a contactor coil, or a control voltage.  

For clarity 

the green safety GROUND leads are not shown. 

NEUTRAL BUS BAR

C

B

BROWN

BLUE

LOAD CENTER

RED

YELLOW

BLOWER

C

B

POWER SUPPLY

DS−7C

HEATER

 

120VAC In, 120VAC Deice Heater/Rain Blower for VSAT or Similar 

Moisture Sensor Mounting & Termination 

Ten feet of cable is pre-terminated to the remote precipitation sensor.  This cable may be shortened on the 
controller end as required.  

Do not add additional cable to the interface.

  Erratic operation may result.  If 

the cable must be lengthened 

only use the EX-50 extension kit

.  Pass the cable through the strain relief 

on top of the unit.  Strip the outer insulation and shield from the cable and terminate each conductor to the 
Grid Jack following the color code printed on the circuit board.  The bare drain wire should be installed into 
the terminal marked “S” for Shield.  Two cable ties are also included.  Wrap these ties securely around the 
cable in the enclosure to provide additional strain relief between the flexible enclosure gland and the free 
end of the cable.

 

Power & Activation Indicator 

A green lamp shines through a lens on the cover of the DS-7C to indicate operational status.  If this lamp is 

OFF

 the DS-7C is not receiving power.  If this lamp is steady 

ON

 the DS-7C is powered but not triggered.  

If this lamp blinks once Relay 1 is closed.  If it blinks twice Relay 2 is closed. If it blinks three times both 
Relay  1  and  Relay  2  are  closed.    Note  that,  even  though  snow  or  rain  may  have  stopped,  the  DS-7C 
indicator will continue to flash during the Delay-Off drying cycle. 

Setting the Configuration Switches and Adjustments 

The following paragraphs and table outline the operating modes for the DS-7C and 
explain  the  functions  of  the  adjustments.    Trigger  temp  (

TT

)  is  adjustable  from 

34

°

F-44

°

F  (1

°

C-6

°

C)  using  the  TRIG  TEMP  control.    When  ambient  air 

temperature (

AT

) is below this setting precipitation is assumed to be snow.  When 

above this setting, precipitation is assumed to be rain. 

The DEL configuration switch activates the Delay-Off drying cycle timer on the DS-
7C.  The timer allows the DS-7C to continue to operate and dry the heated surface through evaporation 

once  precipitation  has  stopped.    The  drying  cycle  reduces  the  chance  of 
moisture  left  behind  refreezing  into  ice.    This  timer  is  restarted  by  each 
sensor trigger.  Therefore, the DS-7C will continue to operate as long as it is 
triggered, then for the Delay-Off period once the trigger clears.  The range of 
the Delay-Off adjustment is defined in the Profile Table.  The adjustment will 
have no function if Delay-Off time is shown in the profile as a fixed value. 

The DS-7C precipitation sensor is very sensitive and can detect a single snow flake or rain drop.  However, 
if the DS-7C is mounted in an area susceptible to high winds, overhanging trees, or blowing ground snow, 
nuisance triggering may occur.  While proper placement is the best remedy, 
the  SENSITIVITY  control  can  also  be used to reduce nuisance triggering.  
An internal timer checks the precipitation sensor for moisture and compares 
cleared  time  with  triggered  time.  The  highest  sensitivity  setting  (toward 
MORE)  triggers  on  first  detection.  As  the  control  is  adjusted  clockwise 
precipitation  must  be  detected  for  a  longer  period  to  be  considered  valid.  
The lowest sensitivity setting (toward LESS) requires 120 seconds of detection before the unit triggers.  If a 
trace amount of snow blows onto the grid from a drift or overhang it will likely be melted and evaporated in 
less than a minute.  Similarly, a very light snowfall may also clear quickly from the grid.  If these conditions 
should  be  ignored  by  the  sensor  the  SENSITIVITY  control  can  be  adjusted  as  required.    However,  to 
prevent non-triggering during a true event, it is recommended that 

the user start at highest sensitivity 

(MORE), then adjust while monitoring operation over time.

 

 
 

External Control 

Pin 

CS-3 

Function 

Green 

See Profile Table 

Black 

See Profile Table 

Orange 

See Profile Table 

Red 

See Profile Table 

White 

GND/Common 

External Monitor 

Pin 

CS-4 

Function 

Black 

Relay 1 Monitor 

Red 

Relay 1 Monitor 

Green 

Relay 2 Monitor 

White 

Relay 2 Monitor 

Содержание DS-7C

Страница 1: ...agreed that such repair or replacement is the exclusive remedy available from ASE and that ASE IS NOT RESPONSIBLE FOR DAMAGES OF ANY KIND INCLUDING INCIDENTAL AND CONSEQUENTIAL DAMAGE Some states do n...

Страница 2: ...PROFILE SELECT MONITOR JACK CONTROL JACK GRID JACK ALWAYS FOLLOW LOCAL AND NATIONAL ELECTRICAL CODES Toujours Suivre Les Codes lectriques Locaux Et Nationaux 2 BROWN BLUE LOAD CENTER CB RED YELLOW 24...

Страница 3: ...ation Indicator A green lamp shines through a lens on the cover of the DS 7C to indicate operational status If this lamp is OFF the DS 7C is not receiving power If this lamp is steady ON the DS 7C is...

Страница 4: ...t Low Temp Cutoff Relay Function Delay Off Black Deice Manual On Relay 1 Deice 30 93 min Green Deice Standby Reset Relay 2 Rain 2 min Red Rain Manual On Orange Rain Standby Reset Profile 6 Dual Deice...

Страница 5: ...t Low Temp Cutoff Relay Function Delay Off Black Deice Manual On Relay 1 Deice 30 93 min Green Deice Standby Reset Relay 2 Rain 2 min Red Rain Manual On Orange Rain Standby Reset Profile 6 Dual Deice...

Страница 6: ...ation Indicator A green lamp shines through a lens on the cover of the DS 7C to indicate operational status If this lamp is OFF the DS 7C is not receiving power If this lamp is steady ON the DS 7C is...

Страница 7: ...PROFILE SELECT MONITOR JACK CONTROL JACK GRID JACK ALWAYS FOLLOW LOCAL AND NATIONAL ELECTRICAL CODES Toujours Suivre Les Codes lectriques Locaux Et Nationaux 2 BROWN BLUE LOAD CENTER CB RED YELLOW 24...

Страница 8: ...agreed that such repair or replacement is the exclusive remedy available from ASE and that ASE IS NOT RESPONSIBLE FOR DAMAGES OF ANY KIND INCLUDING INCIDENTAL AND CONSEQUENTIAL DAMAGE Some states do n...

Отзывы: