Selecting a Mounting Location for the DS-7C 

The  small  corded  device  with  the  interleaved  grid  is  the  remote  precipitation  or  "moisture"  sensor.  The 
brass cylinder protruding from the bottom of the DS-7C enclosure is the temperature sensor. For reliable 
rain  and  snow  detection  the  moisture  sensor  must  be  exposed  to  a  clear  view  of  the  sky.  For  proper 
temperature  detection  the  DS-7C  enclosure  must  be  mounted  outdoors,  away  from  furnace  vents,  dryer 
vents, and other sources of heat. Operating temperature range is -40

°C to +85°C. 

When powered, the 

DS-7C  moisture  grid  will  always  remain  hot.  This  is  normal.  This  allows  the  sensor  to  continuously 
melt/evaporate rain and snow from the grid. 

The  DS-7C  enclosure  can  be  mounted  by  screwing  the  base  conduit hub onto an appropriate size free-
standing conduit or by using the mounting holes in each corner of the enclosure. 

DO NOT DRILL HOLES THROUGH THE ENCLOSURE FOR MOUNTING! 

Ne Font Pas Les Trous De Foret Par La Boîte Pour Le Support! 

This  can  allow  water  into  the  enclosure  causing  a  potential  shock  hazard.  It  is  recommended  that  a 
weatherproof junction box be mounted below the DS-7C for termination of the power and load pigtails to 
the equipment/building wiring. 

Use Care When Replacing the Front Cover.  Do Not Pinch the Gasket or Overtighten the Screws.

 

0

F

E

D

C

B A

9

8

7

6

5

4

3

2

1

TEMPERATURE ADJUST

DELAY OFF ADJUST

SENSITIVITY ADJUST

LOAD1

LOAD2

INPUT POWER

PROFILE SELECT

MONITOR JACK

CONTROL JACK

GRID JACK

 

ALWAYS FOLLOW LOCAL AND NATIONAL ELECTRICAL CODES 

Toujours Suivre Les Codes 

É

lectriques Locaux Et Nationaux 

 

2

BROWN

BLUE

LOAD CENTER

CB

RED

YELLOW

240VAC LOAD

CB

240VAC LOAD

DS−7C

POWER SUPPLY

 

240VAC In, Dual 240VAC Load, Heat Panels or Similar 

DO NOT ATTEMPT TO INCREASE SWITCHING CAPACITY BY WIRING THE RELAYS IN PARALLEL 

Ne Pas Tenter D'Augmenter La Capacité De Commutation Par Le Câblage Des Relais En Parallèle 

DO NOT USE THE DS-7C ENCLOSURE AS A JUNCTION BOX 

Ne Pas Employer Une DS-7C As Une Boîte De Jonction 

Moisture Grid Maintenance & Replacement 

It is recommended that the DS-7C be powered down and the moisture grid wiped clean with clear water at 
least once every 4 months.  Heavy deposits may be removed using a non-metallic scouring pad (Scotch-
Brite

TM

 or equivalent.)   However, after a number of years, the corrosive elements left behind when water is 

evaporated out of the moisture grid will eventually damage the grid rings.  The moisture grid can be easily 
replaced  by  ordering  and  installing  a  new  MG-6  “Moisture  Grid  Assembly”.    Reference  the 

“Moisture 

Sensor Mounting & Termination”

 section for information on replacing the moisture grid. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

General Safety Instructions 

 

1. 

THIS UNIT SHOULD BE INSTALLED, OPENED, AND REPAIRED BY QUALIFIED PERSONNEL 
ONLY! 

 

CETTE UNITÉ DEVRAIT ÊTRE INSTALLÉE, OUVERTE, ET RÉPARÉE PAR LE PERSONNEL 
QUALIFIÉ SEULEMENT! 

 

2.  To avoid shock hazard do not open the front cover with power connected to the DS-7C or any 

controlled equipment. 

 

Pour éviter la décharge électrique déconnectez toute la puissance avant d'ouvrir la couverture du DS-
7C. 

Содержание DS-7C

Страница 1: ...agreed that such repair or replacement is the exclusive remedy available from ASE and that ASE IS NOT RESPONSIBLE FOR DAMAGES OF ANY KIND INCLUDING INCIDENTAL AND CONSEQUENTIAL DAMAGE Some states do n...

Страница 2: ...PROFILE SELECT MONITOR JACK CONTROL JACK GRID JACK ALWAYS FOLLOW LOCAL AND NATIONAL ELECTRICAL CODES Toujours Suivre Les Codes lectriques Locaux Et Nationaux 2 BROWN BLUE LOAD CENTER CB RED YELLOW 24...

Страница 3: ...ation Indicator A green lamp shines through a lens on the cover of the DS 7C to indicate operational status If this lamp is OFF the DS 7C is not receiving power If this lamp is steady ON the DS 7C is...

Страница 4: ...t Low Temp Cutoff Relay Function Delay Off Black Deice Manual On Relay 1 Deice 30 93 min Green Deice Standby Reset Relay 2 Rain 2 min Red Rain Manual On Orange Rain Standby Reset Profile 6 Dual Deice...

Страница 5: ...t Low Temp Cutoff Relay Function Delay Off Black Deice Manual On Relay 1 Deice 30 93 min Green Deice Standby Reset Relay 2 Rain 2 min Red Rain Manual On Orange Rain Standby Reset Profile 6 Dual Deice...

Страница 6: ...ation Indicator A green lamp shines through a lens on the cover of the DS 7C to indicate operational status If this lamp is OFF the DS 7C is not receiving power If this lamp is steady ON the DS 7C is...

Страница 7: ...PROFILE SELECT MONITOR JACK CONTROL JACK GRID JACK ALWAYS FOLLOW LOCAL AND NATIONAL ELECTRICAL CODES Toujours Suivre Les Codes lectriques Locaux Et Nationaux 2 BROWN BLUE LOAD CENTER CB RED YELLOW 24...

Страница 8: ...agreed that such repair or replacement is the exclusive remedy available from ASE and that ASE IS NOT RESPONSIBLE FOR DAMAGES OF ANY KIND INCLUDING INCIDENTAL AND CONSEQUENTIAL DAMAGE Some states do n...

Отзывы: