10. Special Precaution For R410A
Special precautions when dealing with refrigerant R410A unit
1) What is new refrigerant R410A?
R410A is a new HFC refrigerant which does not damage the ozone layer. The working pressure of this
new refrigerant is 1.6 times higher than conventional refrigerant (R22), thus proper installation / servicing
is essential.
2) Components
Mixture weight composition R32(50%) and R125(50%)
3) Characteristic
•
R410A liquid and vapor components have different compositions when the fluid evaporates or
condenses. Hence, when leak occurs and only vapor leaks out, the composition of the refrigerant
mixture left in the system will change and subsequently affect the system performance.
DO NOT
add
new refrigerant to leaked system. It is recommended that the system should be evacuated thoroughly
before recharging with R410A.
•
When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or
liquid phase. Hence when charging R410A, ensure that only liquid is being withdrawn from the cylinder
or can. This is to make certain that only original composition of R410A is being charged into the
system.
•
POE oil is used as lubricant for R410A compressor, which is different from the mineral oil used for
R22 compressor. Extra precaution must be taken not to expose the R410A system too long to moist
air.
4) Check list before installation/servicing
•
Tubing
Refrigerant R410A is more easily affected by dust of moisture compared with R22, make sure to
temporarily cover the ends of the tubing prior to installation
•
Compressor oil
No additional charge of compressor oil is permitted.
•
Refrigerant
No other refrigerant other that R410A
•
Tools (size of service port is different from R22 system)
Tools specifically for R410A only (must not be used for R22 or other refrigerant)
i)
Manifold gauge and charging hose
ii)
Gas leak detector
iii)
Refrigerant cylinder/charging cylinder
iv)
Vacuum pump c/w adapter
v)
Flare tools
vi)
Refrigerant recovery machine
5) Handling and installation guidelines
Like R22 system, the handling and installation of R410A system are closely similar. All precautionary
measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and
thorough leak check and vacuuming are equally important requirements. However, due to its hydroscopic
POE oil, additional precautions must be taken to ensure optimum and trouble free system operation.
a) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to
moist air. Residual POE oil in the piping and components can absorb moisture from the air.
b) Ensure that the compressor is not expose to open air for more than the recommended time specified
by its manufacturer (typically less than 10 minutes). Removed the seal plugs only when the compressor
is about to be brazed.
c) The system should be thoroughly vacuumed to 1.0 Pa ( 700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
Содержание A5LCX 10 C
Страница 1: ...DC Inverter Single Split A5LCX 2007 Models A5LCX 10 C CR A5LCX 15 C CR A5LCX 20 C CR A5LCX 25 C CR...
Страница 14: ...12 MODEL A5CKX20A A5LCX20C A5CKX25A A5LCX25C A5CKX20C A5LCX25C MODEL A5CKX10C A5LCX10C A5CKX15C A5LCX15C...
Страница 15: ...13 MODEL A5CMX20E A5LCX20C A5CMX25E A5LCX25C MODEL A5CMX20ER A5LCX20CR ACMX25ER A5LCX25CR...
Страница 16: ...14 MODEL A5CCX20C A5LCX20C A5CCX25C A5LCX25C MODEL A5CCX10C A5LCX10C A5CCX15C A5LCX15C...
Страница 17: ...15 MODEL A5CCX20CR A5LCX20CR A5CCX25CR A5LCX25CR MODEL A5CCX10CR A5LCX10CR A5CCX15CR A5LCX15CR...
Страница 20: ...18 Installation Installation Diagram...
Страница 108: ...106 7 WIRING DIAGRAMS Indoor Unit MODEL A5WMX 10 15 G GR WITH IONIZER Outdoor Unit MODEL A5LCX 10 15 C CR...
Страница 109: ...107 Indoor Unit MODEL A5WMX 20 25 G GR WITH IONIZER Outdoor Unit MODEL A5LCX 20 25 C CR...
Страница 110: ...108 MODEL A5CKX 10 15C CR c w A5LCX 10 15 C CR...
Страница 111: ...109 MODEL A5CKX 20C CR c w A5LCX 20C CR...
Страница 112: ...110 MODEL A5CKX 20 25A AR c w A5LCX 20 25C CR...
Страница 113: ...111 MODEL A5CMX 20 25E ER c w A5LCX 20 25C CR...
Страница 114: ...112 MODEL A5CCX 10 15C CR c w A5LCX 10 15C CR...
Страница 115: ...113 MODEL A5CCX 20 25C CR c w A5LCX 20 25C CR...
Страница 127: ...125 MODEL A5CKX 20 25A AR...
Страница 129: ...127 MODEL A5CKX 10 15 20C CR...
Страница 131: ...129 MODEL A5CMX 15 20 25E ER...