- OPERATING INSTRUCTIONS - Vr. Mondial Group - 10/10 - ISTR-MY39EENGmondial - PAG. 11
on delay
39
P.P1
Output “ot” delay at
switch on
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
40
P.P2
Output “ot” delay after
switch off
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
41
P.P3
Output
“ot”
delay
between switching-on
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
42
P.od
Delay outputs at power
on
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
A. - parameters relative to alarms
43
A.Ay
Temperature
alarms
Type:
1 = Pr1 absolute with
label (Hi - Lo)
2 = Pr1 Relative with
label (Hi - Lo)
3 = “Au” absolute with
label (Hi - Lo)
4 = “Au” Relative with
label (Hi - Lo)
1 / 2 / 3 / 4
1
44
A.HA
High
temperature
Alarm threshold
oF / -99.9 ÷
999 °C/°F
oF
45
A.LA
Low
temperature
Alarm threshold
oF / -99.9 ÷
999 °C/°F
oF
46
A.At
Temperature Alarms
delay
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
47
A.PA
Temperature
Alarms
delay at power on
oF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
(hrs.min.x10)
2.00
48
A.dA
Temperature
Alarms
delay after defrost, and
unlock display delay
after defrost
oF/ 0.01 ÷ 9.59
(hrs.min. ) ÷
99.5
(hrs.min.x10)
1.00
49
A.oA
Alarm delay with door
open
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
3.00
o. - parameters relative to configuration of outputs and
buzzer
50
o.o1
OUT1 function:
oF= No function
ot=
Temperature
control (compressor)
dF= Defrosting
Fn= fan
Au= Auxiliary
At/-t=
Silenceable
alarm
AL/-L= Not silenceable
Alarm
on=
on
when
instrument switch on
HE = Heating (Neutral
zone control)
oF/ot/dF/
Fn/Au/At/ AL/-
t/-L/on/HE
ot
51
o.o2
OUT2 function:
see “o.o1”
oF/ot/dF/
Fn/Au/At/ AL/-
t/-L/on/HE
dF
52
o.o3
OUT3 function:
see “o.o1”
oF/ot/dF/
Fn/Au/At/ AL/-
t/-L/on/HE
Fn
53
o.bu
Buzzer function mode
oF = disable
oF / 1 / 2 / 3
3
1 = active alarms only
2 = key pressed only
3 = active alarms and
key pressed
54
o.Fo
Function
mode
auxiliary output:
oF= No Function
1= control output “ot”
delayed
2= manual activation
by key or digital input.
3 = light with economy
mode (on in Normal
mode off in Eco mode)
4 = internal light (off
with door closed and
on with door opened)
oF / 1 / 2 / 3 / 4
oF
55
o.tu
Time
relative
to
auxiliary output
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
99.5
(min.sec.x10)
oF
t. - parameters relative to configuration of the keyboard (and
to communication)
56
t.UF
Function
mode key
DOWN/AUX:
oF= No function
1=
Auxiliary
output
command
2= Norm. / Eco mode
Selection
3=
Switch
on/off
(Stand-by)
oF / 1 / 2 / 3
oF
57
t.Fb
Function
mode key
Down/Aux: see “t.UF”
oF / 1 / 2 / 3
oF
58
t.Lo
Keyboard lock function
delay
oF/ 0.01 ÷ 9.59
(min.sec ) ÷
30.0
(min.sec.x10)
oF
59
t.Ed
Set Visibility with fast
procedure by key P:
oF = None
1 = SP
2 = SPE
3 = SP and SPE
4 = Active SP
oF / 1 / 2 / 3 / 4
4
60
t.SA
Active mode:
0 = Normal
1 = Economic
0 ÷ 1
0
61
t.PP
Access Password to
parameter functions
oF ÷ 999
oF
62
t.AS
Station address (for
serial communication)
0 ÷ 255
1
6 - PROBLEMS, MAINTENANCE AND GUARANTEE
6.1 - SIGNALLING
Errore
Reason
Action
E1 -E1
E2 -E2
The
probe
may
be
interrupted (E) or in
short circuit (-E), or may
measure a value outside
the range allowed
Check
the
correct
connection of the probe
with the instrument and
check the probe works
correctly
EPr
Internal
EEPROM
memory error
Press key P
Other Signalling:
Message
Reason
od
Delay at power-on in progress
Ln
Keyboard lock
Hi
Maximum temperature alarm in progress
Lo
Minimum temperature alarm in progress
oP
Door opened