![Ascon tecnologic TLK41 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/ascon-tecnologic/tlk41/tlk41_manual_2981548005.webp)
5
To enter into the menu
“OPEr”
select then the option “OPEr” and push key “P”.
Now, the display will show the code identifying the first group of parameters (“
]
SP
“) and with keys “UP” and “DOWN” will be
possible to select the parameters group to be modified.
Once the desired parameters group has been selected, push key “P” and it will be visualised the code Identifying the first
parameter of the selected group.
Still using keys “UP” and “DOWN” its’ possible to select the desired parameter and, pushing key “P”, the display will
alternatively show the parameter’s code and its programming value, modifiable through keys “UP” or “DOWN”.
Once the desired value has been programmed, push again key “P” : the new value will be memorised and the display will
show only the code of the selected parameter.
Working on keys “UP” or “DOWN” it’s then possible to select a new parameter (if present) and modify it as just described.
To select another group of parameters, hold key “UP” or “DOWN” pushed for approx. 2 sec., afterwards the display will come
back to visualise the code of the parameters group.
Release then the key and with keys “UP” and “DOWN” it will be possible to select a new group (if present).
To get out of the programming mode, do not work on any key for approx. 20 seconds, or hold the key “UP” or “DOWN” pushed
until the exit from the programming mode occurs.
To enter into the menu
"ConF"
it’s instead required a PASSWORD.
At this request, do program, using keys “UP” and “DOWN”, the number reported on the last page of this manual and push key
“P”.
Whether it’s programmed a wrong password, the instrument comes back onto the previous control state.
If the password is correct the display will visualise the code identifying the first parameters group (“
]
SP
“) and with keys “UP”
and “DOWN” it will be possible to select the desired parameters group.
The modality of programming and exit for the “ConF” menu is the same as described for menu “OPEr”.
2.3 – PARAMETERS PROGRAMMING LEVELS
The menu “OPEr” normally contains the parameters used to program the Set Point, however it’s possible to make appear or
disappear on this level all the desired parameters, following this procedure:
Enter into the menu “ConF” and select the parameter which is desired to have or not to have programmable in the menu
“OPEr”.
Once the parameter has been selected, if led SET is switched off this means that the parameter is programmable only in the
menu “ConF”, if instead the led is lighted on this means that the parameter is also programmable in the menu “OPEr”.
To modify the visibility of the parameter, push key “U” : led SET will change its state indicating the parameter accessibility
level (lighted on = menu ”OPEr” and “ConF”; switched off = menu “ConF” only).
The active Set Point and the alarm thresholds will be visible on the Set Point fast programming level (described on par. 2.1)
only if the relative parameters are programmed as visible (i.e. are present in the menu “OPEr”).
The possible modification of these Set, with the procedure described on par. 2.1, is instead subordinated to what
programmed on par.
“Edit”
(contained in the group “
]
PAn
“).