GROUP “ 

]

rEG” (PARAMETERS RELATIVE TO THE CONTROL):

It contains the parameters relative to the control functioning.
Cont 

– CONTROL TYPE: It permits to select one of the possible control mode offered by the instrument : PID (Pid),  ON/OFF

with asymmetrical hysteresis (On.FA),  ON/OFF with symmetrical hysteresis (On.FS), Neutral Zone ON/OFF (nr).

Func –

 FUNCTIONING MODE OUTPUT 1rEG:

 

It permits to decide if the control output 1rEG has to actuate a reverse action,

as for example a Heating process ("HEAt") or a direct action, as for example a Cooling process ("CooL").

HSEt

 –ON/OFF CONTROL HYSTERESIS: Semi-band relative to the Set Point which definers the activation and deactivation

values of the control output/s in case of  ON/OFF control (On.FA, On.FS, nr).

Auto

 – AUTOTUNING FAST ENABLE : this parameter permits to decide how the Autotuning has to be executed . The possible

selections are :
 = 1  -  if it’s desired to have the autotuning automatically, each time the instrument is switched on, at the condition that the
process value is lower (with “Func” =HEAt) or higher (with “Func” =CooL) than SP/2
= 2  -  if it’s desired to have the autotuning automatically, the next time the instrument is switched on, at the condition that the
process value is lower (with “Func” =HEAt) or higher (with “Func” =CooL) than SP/2, and once the tuning is finished, the par.
“Auto” IS automatically swap into the OFF state
= 3  - - if it’s desired to activate the autotuning manually, through the selection of par. “tunE” in the main menu or though key
“U” properly programmed as “USrb” = tunE. In this case the autotuning starts without any control on the process value
condition. It’s recommended to use this option, starting the autotuning when the process value is as far as possible from the
Set Point because, in order to feature the Autotuning FAST with its best performances , it’s preferable to respect this condition
= OFF - Autotuning disabled.
When it’s occurring an Autotuning cycle, led AT blinks.

SELF

 – SELFTUNING ENABLE: Parameter used to enable (yES) or disable (no) the Selftuning function. Once the function has

been enabled, the Selftuning has to be started selecting item “tunE”, in the main menu, or through key U properly
programmed (“USrb” = tunE).When the Selftuning function is active, led AT is permanently lighted, and all the PID parameters
("Pb", "Int", "dEr", ecc.) are not visualised anymore.

Pb

 – PROPORTIONAL BAND: Width of the band around the Set Point within which the proportional control is performed.

Int

 – INTEGRAL TIME: Integral time to be programmed in the PID algorithm, expressed in sec.

dEr

 – DERIVATIVE TIME: : Derivative time to be programmed in the PID algorithm, expressed in sec.

FuOc 

- FUZZY OVERSHOOT CONTROL: Parameter that permits to eliminate the variable over-shoots at the start up of the

process or at the changing of the Set Point. A low value of this parameter reduces the overshoot while a high value increase
it.
 

tcr1

 – CYCLE TIME OF OUTPUT 1rEG : Cycle time of output 1rEG with PID control mode, expressed in sec..

Prat

  –  POWER RATIO 2rEG /  1rEG  :  Parameter where it’s possible to program the power ratio between the element

controlled by output 2rEG (ex.Cooling) and the element controlled by output 1rEG (ex. Heating) in case of PID double action
control.

tcr2

 - CYCLE TIME OF OUTPUT 2rEG : Cycle time of output 2rEG with PID double action control mode, expressed in sec..

rS

 -  MANUAL RESET: Power Offset added to the power increase of the proportional term, in order to eliminate the error when

it’s not present the integral value. This parameter is only visualised when  “Int” =0.

Parameters relative to the ramps, allowing the reaching of the Set Point in a predetermined time.
Furthermore, once the first Set (SP1) has been reached, it’s possible to have the automatic commutation on the second
Set (SP2) after a programmable time, obtaining in this way a simple thermal cycle (functions available for all the control
types)

SLor

 – GRADIENT OF RISE RAMP:  Gradient of rise ramp to actuate when the process value is lower than the active Set

Point, expressed in unit/minute.
Programming the parameter = InF the ramp is not active.

dur.t - 

DWELL TIME: Dwell time of the Set Point SP1 before the automatic commutation on SP2 (expressed in hrs. and min.)

Through this parameter,

 

once the first Set (SP1) has been reached, it’s possible to have the automatic commutation on the

second Set (SP2) after a programmable time, obtaining in this way a simple thermal cycle.
Programming the parameter = InF the function is not active.

SLoF

 - GRADIENT OF FALL RAMP:  Gradient of fall ramp to actuate when the process value is higher than the active Set

Point, expressed in unit/minute.
Programming the parameter = InF the ramp is not active.

Parameters relative to the Soft-Start function, which allows to limit the control power, at the instrument switch on, for a
predetermined time. This function is only available for PID control, furthermore when the Soft Start is active, it’s not
possible to have the Autotuning function as this could supply an excessive power.

St.P

 - SOFT START POWER:

If parameter “SSt” is programmed with a values different from OFF, this is the power given as output at the instrument switch
on, for the time “SSt”.
In the practice, the instrument works in manual condition and commutates into automatic control at the elapsing of time
“SSt”.

Содержание TLK41

Страница 1: ...5 SINGLE ACTION PID CONTROLLER 4 6 DOUBLE ACTION PID CONTROLLER 4 7 AUTOTUNING AND SELFTUNING FUNCTIONS 4 8 REACHING OF SET POINT WITH CONTROLLED SPEED AND AUTOMATIC COMMUTATION BETWEEN TWO SET POINT...

Страница 2: ...Break Alarm function Other important available functions are Loop Break Alarm function reaching of the Set Point at controlled speed ramp and dwell function Soft Start function PC configuration parame...

Страница 3: ...he process value is lower than as programmed on par AdE 12 Led Shift index It indicates that the process value is within the range SP AdE SP AdE 13 Led Shift index It indicates that the process value...

Страница 4: ...play is coming back to the normal functioning 2 2 SELECTION OF THE CONTROL STATE AND PARAMETERS PROGRAMMING Pushing key P and holding it pushed for approx 2 sec it s possible to enter into the main se...

Страница 5: ...UP and DOWN the number reported on the last page of this manual and push key P Whether it s programmed a wrong password the instrument comes back onto the previous control state If the password is co...

Страница 6: ...ing on the instrument automatically assumes the state it had at the switching off AUTOMATIC CONTROL rEG The automatic control is the normal functioning state of the controller During the automatic con...

Страница 7: ...r SPAt in the parameters group SP Through key U if par USrb CHSP Automatically between SP1 and SP2 in case a time dur t see par 4 8 has been programmed Set Point SP1 SP2 SP3 SP4 will be visible depend...

Страница 8: ...ousing by the front side is recommended to disconnect the power supply from the instrument when it s necessary to effectuate this operation 3 3 ELECTRICAL CONNECTION Carry out the electrical wiring co...

Страница 9: ...nit of measurement C F and through par dP the desired resolution 0 1 1 0 1 As regard instead the instruments with normalised analogue input signals it s necessary first of all to program the desired r...

Страница 10: ...of the display which can be the process variable dEF the control power Pou the active Set Point SP F the Set Point operating when there are active ramps SP o or alarm threshold AL1 2 or 3 AL1 AL2 or...

Страница 11: ...n or cooling Func CooL it deactivates the output when the process value reaches SP HSEt in case of symmetrical hysteresis or SP in case of asymmetrical hysteresis and it activates it again when the pr...

Страница 12: ...element causing a negative increase has to be connected to the output programmed as 2rEG 4 4 SINGLE ACTION PID CONTROLLER 1rEG All the parameters referred to the PID control are contained into the gr...

Страница 13: ...ng of the following parameters Pb Proportional Band tcr1 Cycle time of the output 1rEG tcr 2 Cycle time of the output 2rEG Int Integral Time rS Manual Reset if Int 0 only dEr Derivative Time FuOC Fuzz...

Страница 14: ...PID parameters Whether Auto 1 or Auto 2 and whenever at the Autotuning start it s not verified the condition for which the process value is lower with Func HEAt or higher with Func CooL than SP 2 the...

Страница 15: ...tioning is defined by the following parameters SLor Gradient of rise ramp Process value Set point expressed in unit minute SLoF Gradient of fall ramp Process value Set point expressed in unit minute d...

Страница 16: ...the function is interrupted and the instrument gives an output power as programmed on par OPE If the measuring is restored the Soft Start is in any case deactivated Note When the Soft Start is active...

Страница 17: ...m set on parameter ALn LHAb ABSOLUTE BAND ALARM The alarm is activated when the process value goes under the alarm set on parameter ALn or goes higher than alarm set on parameter ALnH LOdE DEVIATION L...

Страница 18: ...on has come to pass it starts the counting of the delay as programmed on par ALnd expressed in sec and only after the elapsing of that time the alarm will be activated ALARM LATCH It s possible to hav...

Страница 19: ...alarm is not active while it s deactivated when the alarm is active Enter then into group Hb and program on parameter OHb on which output the alarm signal has to be addressed The functioning mode of t...

Страница 20: ...larms the value of this parameter has to be set considering the time the plant spends to reach the Set point when the measured value is far away from it for example at the plant start up At the alarm...

Страница 21: ...connected with all the namesake terminals of the net For the wiring operation it s enough then to interlace a double cable telephonic type and to connect on ground all the GND terminals Nevertheless p...

Страница 22: ...Probe type tc J CrAL S Ir J Ir CA rtd Pt1 Ptc ntc I 0 20 4 20 UoLt 0 50 0 60 12 60 0 5 1 5 0 10 2 10 J 11 SSC Low scale limit in case of input with V I signals 1999 FSC 0 12 FSC High scale limit in c...

Страница 23: ...9999 sec OFF 41 AL2i Alarm AL2 activation in case of measuring error no yES no Group AL3 parameters relative to alarm AL3 Par Description Range Def Note 42 OAL3 Output where alarm AL3 is addressed Ou...

Страница 24: ...9 InF unit min InF 72 dur t Dwell time 0 00 99 59 InF hrs min InF 73 SLoF Gradient of fall ramp 0 00 99 99 InF unit min InF 74 St P Soft Start power OFF 100 100 OFF 75 SSt Soft Start time OFF 0 1 7 59...

Страница 25: ...5 V or 10 V dP NUMBER OF DECIMAL FIGURES It permits to decide if the measuring resolution has to be 1 0 0 1 1 0 01 2 0 001 3 In case of temperature probes the allowed resolutions are 1 0 and 0 1 1 Uni...

Страница 26: ...witch on the instrument is in alarm conditions the alarm is not activated It will be activated only when the process value is out and back again in alarm conditions ALARM DELAY 0 ALARM NOT DELAYED The...

Страница 27: ...eferred to alarm AL2 HAL2 ALARM AL2 HYSTERESIS Similar to HAL1 but referred to alarm AL2 AL2d ACTIVATION DELAY OF ALARM AL2 Similar to AL1d but referred to alarm AL2 AL2i ALARMAL2 ACTIVATION IN CASE O...

Страница 28: ...e parameters relative to the Heater Break alarm heating element breakage This function is present only when the instrument is equipped with the input TAHB to measure the current absorbed by the load T...

Страница 29: ...ATIVE TIME Derivative time to be programmed in the PID algorithm expressed in sec FuOc FUZZY OVERSHOOT CONTROL Parameter that permits to eliminate the variable over shoots at the start up of the proce...

Страница 30: ...amp The output power starts from 0 and is progressively increased basing on the calculated ramp up to the reaching of time SSt or until when the power overcomes the power calculated by the PID control...

Страница 31: ...value is within the range SP AdE SP AdE the lighting of the red led indicates that the process value is lower than the value SP AdE and the lighting of the red led indicates that the process value is...

Страница 32: ...eG control ErEP Possible anomaly of the EEPROM memory Push key P In error conditions the instrument provides an output power as programmed on par OPE and activates the desired alarms if the relative p...

Страница 33: ...s II for Front panel Insulation Reinforced insulation between the low voltage section supply and relay outputs and the front panel Reinforced insulation between the low voltage section supply and rela...

Страница 34: ...nd 93 68 EN 61010 1 7 5 MEASURING RANGE TABLE INPUT without D P with D P tc J HCFG tc SEnS J 160 1000 C 256 1832 F 160 0 999 9 C 199 9 999 9 F tc K HCFG tc SEnS CrAl 270 1370 C 454 2498 F 199 9 999 9...

Страница 35: ...TLK 41 a b c d e f g ii a POWER SUPPLY L 18 30 VAC VDC H 90 240 VAC b OUTPUT OUT1 R Relay O 20 mA 14 VDC x SSR c OUTPUT OUT2 R Relay O 20 mA 14 VDC x SSR d OUTPUT OUT3 R Relay O 20 mA 14 VDC x SSR e O...

Отзывы: