ASCON TECNOLOGIC - TLI 40 - OPERATING INSTRUCTIONS - 

PAG. 7

5 - PROGRAMMABLE PARAMETERS

 

Here  following  are  described  all  the  parameters  available  on  the 
instrument. Some of them could be not present or because they are 
depending  on  the  type  of  instrument  or  because  they  are 
automatically disabled as unnecessary. 

5.1 - PARAMETERS TABLE

 

Group “InP” 

(parameters relative to the measure input) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

HCFG

  Input type 

tc / rtd / I / 

UoLt / SEr 

tc 

SaSP

  Sampling  rate  in  case 

of input with V / I or Pot 
signals 

8-16-32-64

SEnS

  Probe type 

tc : 

J /  CrAL / S / 

Ir.J / Ir.CA 

rtd : 

Pt1 / Ptc / ntc 

I : 

0.20 / 4.20 

UoLt :

 

0.50 / 0.60 / 
12.60 / 0.5 / 

1.5 / 0.10 / 

2.10 / Pot 

4

rEFL

  Reflection 

coefficient 

for IRS sensors 

0.10 ÷ 1.00 

1.00 

SSC

  Low scale limit in case 

of input with V/I signals 

-1999 ÷ FSC

FSC

  High scale limit in case 

of input with V/I signals 

SSC ÷ 9999 

0.Pot

Zero 

value 

with 

potentiometer input 

SSC ÷ FSC 

dP 

Number of decimal 
figures 

tc/rtd :

 

0 / 1 

UoLt / I / SEr: 

0 ÷ 3 

Unit

  Temperature unit of 

measurement 

tc/rtd : 

°C / °F 

°C 

10 

FiL

  Input digital filter 

0FF÷ 20.0 

sec. 

0.2 

11 

OFSt

  Measuring Offset 

-1999 ÷ 9999

12 

 rot 

Rotation 

of 

the 

measuring straight line 

0.000 ÷ 2.000  1.000 

13 

dIF

  Digital input function 

noF / Aac / 

ASi / HoLd / 

r.Pic / 0.Pot /

r.P0P

noF 

Group “O1” 

(parameters relative to output 1) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

14 

O1F

  Functioning  of  output  1 

if digital type  

 ALno / ALnc 

Ser / OFF 

ALno 

15 

Aor1

  Beginning  of  output  1 

scale if analogical type 

0 / no_0 

16 

Ao1F

  Functioning  of  output  1 

if analogue type 

r.inP / r.SEr

OFF

r.inP

17 

Ao1L

  Minimum  reference  for 

analogical  output  1  for 
signal retransmission 

-1999 ÷ Ao1H

18 

Ao1H

  Maximum  reference  for 

analogical  output  1  for 
signal retransmission 

Ao1L ÷ 9999 

Group “O2” 

(parameters relative to output 2) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

19 

O2F

  Functioning of output 2 

ALno / ALnc 

Ser / OFF 

ALno 

Group “O3” 

(parameters relative to output 3) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

20 

O3F

  Functioning of output 3 

ALno / ALnc 

Ser / OFF 

ALno 

Group “O4” 

(parameters relative to output 4) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

21 

O4F

  Functioning of output 4 

ALno / ALnc 

Ser / OFF 

ALno 

Group “AL1”

 (parameters relative to alarm AL1) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

22 

OAL1

  Output where alarm 

AL1 is addressed 

Out1 / Out2 
Out3 / Out4 

OFF 

OFF 

23 

AL1t

  Alarm AL1 type 

LoAb / HiAb 

LHAb 

LoAb 

24 

Ab1

  Alarm AL1 functioning 

0 ÷ 15 

25 

AL1

  Alarm AL1 threshold 

 AL1L÷ AL1H 

26 

AL1L

  Low 

threshold 

band 

alarm  AL1  or  Minimum 
set  alarm  AL1  for  high 
or low alarm 

-1999 ÷ AL1H -1999

27 

AL1H

  High  threshold  band 

alarm  AL1  or  Maximum 
set  alarm  AL1  for  high 
or low alarm 

AL1L ÷ 9999 

9999 

28 

HAL1

  Alarm AL1 hysteresis 

OFF ÷ 9999 

29 

AL1d

  Activation delay of 

alarm AL1 

OFF ÷ 9999 

sec. 

OFF 

30 

AL1i

  Alarm  AL1  activation  in 

case of measuring error 

no / yES 

no 

Group “AL2”

 (parameters relative to alarm AL2) 

Par. 

Description 

Range 

Def. 

Note 

31

  OAL2 

Output where alarm 
AL2 is addressed

 

Out1 / Out2 
Out3 / Out4 

OFF

 

OFF

 

32

  AL2t 

Alarm AL2 type

 

LoAb / HiAb 

LHAb

 

LoAb

 

33

  Ab2 

Alarm AL2 functioning

 

0 ÷ 15

 

0

 

34

  AL2 

Alarm AL2 threshold

 

 AL2L÷ AL2H

 

0

 

35

  AL2L 

Low 

threshold 

band 

alarm  AL2  or  Minimum 
set  alarm  AL2  for  high 
or low alarm

 

-1999 ÷ AL2H -1999

36

  AL2H 

High  threshold  band 
alarm  AL2  or  Maximum 
set  alarm  AL2  for  high 
or low alarm

 

AL2L ÷ 9999

 

9999

 

37

  HAL2 

Alarm AL2 hysteresis

 

OFF ÷ 9999

 

1

 

38

  AL2d 

Activation delay of 
alarm AL2

 

OFF ÷ 9999 

sec.

 

OFF

 

39

  AL2i 

Alarm  AL2  activation  in 
case of measuring error

 

no / yES

 

no

 

Group “AL3”

 (parameters relative to alarm AL3) 

Par.

 

Description

 

Range

 

Def.

 

Note

 

40 

OAL3

  Output where alarm 

AL3 is addressed 

Out1 / Out2 
Out3 / Out4 

OFF 

OFF 

41 

AL3t

  Alarm AL3 type 

LoAb / HiAb 

LHAb 

LoAb 

42 

Ab3

  Alarm AL3 functioning 

0 ÷ 15 

43 

AL3

  Alarm AL3 threshold 

AL3L÷ AL3H 

44 

AL3L

  Low 

threshold 

band 

alarm  AL3  or  Minimum 
set  alarm  AL3  for  high 
or low alarm 

-1999 ÷ AL3H -1999

45 

AL3H

  High  threshold  band 

alarm  AL3  or  Maximum 
set  alarm  AL3  for  high 
or low alarm 

AL3L ÷ 9999 

9999 

46 

HAL3

  Alarm AL3 hysteresis 

OFF ÷ 9999 

47 

AL3d

  Activation delay of 

alarm AL3 

OFF ÷ 9999 

sec. 

OFF 

Содержание TLI40

Страница 1: ...6 PROBLEMS MAINTENANCE AND GUARANTEE 6 1 ERROR SIGNALLING 6 2 CLEANING 6 3 GUARANTEE AND REPAIRS 7 TECHNICAL DATA 7 1 ELECTRICAL DATA 7 2 MECHANICAL DATA 7 3 MECHANICAL DIMENSIONS PANEL CUT OUT AND MO...

Страница 2: ...value has been programmed push key P once more the new value will be memorised and the display will show only the code of the selected parameter By using the UP or DOWN keys it is then possible to se...

Страница 3: ...ked as instrument disconnecting device which interrupts the power supply to the equipment It is also recommended that all the electrical circuits connected to the instrument must be protect properly u...

Страница 4: ...ument is switched on by using the U key that has been suitably programmed see par U key with function USrb r Pic or through the suitably programmed digital input see par digital input with function dI...

Страница 5: ...d in sec and the alarm will be activated only after the elapsing of that time ALARM LATCH the alarm output may behave in two different ways depending on the value added to par Abn 0 ALARM NOT LATCHED...

Страница 6: ...eter input it is possible to set the zero value with this function By closing the contact connected to the digital input assuming the value measured in that instant as 0 r P0P For the instruments equi...

Страница 7: ...tput 3 Par Description Range Def Note 20 O3F Functioning of output 3 ALno ALnc Ser OFF ALno Group O4 parameters relative to output 4 Par Description Range Def Note 21 O4F Functioning of output 4 ALno...

Страница 8: ...to a high value when the material to be measured is particularly light reflective and reduce it when the surface is especially dark non reflective keeping in mind however that for most materials the r...

Страница 9: ...ARM The alarm is activated when the process value goes below the alarm threshold set on parameter AL1L or goes higher than alarm set on parameter AL1H Ab1 ALARM AL1 FUNCTION This permits definition of...

Страница 10: ...r the instruments equipped with potentiometer input with this function it is possible to set the points of measure of the potentiometer by means of an auto ranging procedure through which the paramete...

Страница 11: ...ection class against electric shock Class II for Front panel Insulation Reinforced insulation between the low voltage section supply and relay outputs and the front panel Reinforced insulation between...

Страница 12: ...99 99 99 1 999 9 999 0 50 mV HCFG UoLt SEnS 0 50 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 0 60 mV HCFG UoLt SEnS 0 60 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 12 60 mV HCFG UoLt SEnS 12 60...

Отзывы: