5 - PROGRAMMABLE PARAMETERS
Here following are described all the parameters available on the
instrument. Some of them could be not present or because they are
depending on the type of instrument or because they are
automatically disabled as unnecessary.
5.1 - PARAMETERS TABLE
Group “InP”
(parameters relative to the measure input)
Par.
Description
Range
Def.
Note
1
HCFG
Input type
tc / rtd / I /
UoLt / SEr
tc
2
SaSP
Sampling rate in case
of input with V / I or Pot
signals
8-16-32-64
8
3
SEnS
Probe type
tc :
J / CrAL / S /
Ir.J / Ir.CA
rtd :
Pt1 / Ptc / ntc
I :
0.20 / 4.20
UoLt :
0.50 / 0.60 /
12.60 / 0.5 /
1.5 / 0.10 /
2.10 / Pot
J
4
rEFL
Reflection
coefficient
for IRS sensors
0.10 ÷ 1.00
1.00
5
SSC
Low scale limit in case
of input with V/I signals
-1999 ÷ FSC
0
6
FSC
High scale limit in case
of input with V/I signals
SSC ÷ 9999
0
7
0.Pot
Zero
value
with
potentiometer input
SSC ÷ FSC
0
8
dP
Number of decimal
figures
tc/rtd :
0 / 1
UoLt / I / SEr:
0 ÷ 3
0
9
Unit
Temperature unit of
measurement
tc/rtd :
°C / °F
°C
10
FiL
Input digital filter
0FF÷ 20.0
sec.
0.2
11
OFSt
Measuring Offset
-1999 ÷ 9999
0
12
rot
Rotation
of
the
measuring straight line
0.000 ÷ 2.000 1.000
13
dIF
Digital input function
noF / Aac /
ASi / HoLd /
r.Pic / 0.Pot /
r.P0P
noF
Group “O1”
(parameters relative to output 1)
Par.
Description
Range
Def.
Note
14
O1F
Functioning of output 1
if digital type
ALno / ALnc
Ser / OFF
ALno
15
Aor1
Beginning of output 1
scale if analogical type
0 / no_0
0
16
Ao1F
Functioning of output 1
if analogue type
r.inP / r.SEr
OFF
r.inP
17
Ao1L
Minimum reference for
analogical output 1 for
signal retransmission
-1999 ÷ Ao1H
0
18
Ao1H
Maximum reference for
analogical output 1 for
signal retransmission
Ao1L ÷ 9999
0
Group “O2”
(parameters relative to output 2)
Par.
Description
Range
Def.
Note
19
O2F
Functioning of output 2
ALno / ALnc
Ser / OFF
ALno
Group “O3”
(parameters relative to output 3)
Par.
Description
Range
Def.
Note
20
O3F
Functioning of output 3
ALno / ALnc
Ser / OFF
ALno
Group “O4”
(parameters relative to output 4)
Par.
Description
Range
Def.
Note
21
O4F
Functioning of output 4
ALno / ALnc
Ser / OFF
ALno
Group “AL1”
(parameters relative to alarm AL1)
Par.
Description
Range
Def.
Note
22
OAL1
Output where alarm
AL1 is addressed
Out1 / Out2
Out3 / Out4
OFF
OFF
23
AL1t
Alarm AL1 type
LoAb / HiAb
LHAb
LoAb
24
Ab1
Alarm AL1 functioning
0 ÷ 15
0
25
AL1
Alarm AL1 threshold
AL1L÷ AL1H
0
26
AL1L
Low
threshold
band
alarm AL1 or Minimum
set alarm AL1 for high
or low alarm
-1999 ÷ AL1H -1999
27
AL1H
High threshold band
alarm AL1 or Maximum
set alarm AL1 for high
or low alarm
AL1L ÷ 9999
9999
28
HAL1
Alarm AL1 hysteresis
OFF ÷ 9999
1
29
AL1d
Activation delay of
alarm AL1
OFF ÷ 9999
sec.
OFF
30
AL1i
Alarm AL1 activation in
case of measuring error
no / yES
no
Group “AL2”
(parameters relative to alarm AL2)
Par.
Description
Range
Def.
Note
31
OAL2
Output where alarm
AL2 is addressed
Out1 / Out2
Out3 / Out4
OFF
OFF
32
AL2t
Alarm AL2 type
LoAb / HiAb
LHAb
LoAb
33
Ab2
Alarm AL2 functioning
0 ÷ 15
0
34
AL2
Alarm AL2 threshold
AL2L÷ AL2H
0
35
AL2L
Low
threshold
band
alarm AL2 or Minimum
set alarm AL2 for high
or low alarm
-1999 ÷ AL2H -1999
36
AL2H
High threshold band
alarm AL2 or Maximum
set alarm AL2 for high
or low alarm
AL2L ÷ 9999
9999
37
HAL2
Alarm AL2 hysteresis
OFF ÷ 9999
1
38
AL2d
Activation delay of
alarm AL2
OFF ÷ 9999
sec.
OFF
39
AL2i
Alarm AL2 activation in
case of measuring error
no / yES
no
Group “AL3”
(parameters relative to alarm AL3)
Par.
Description
Range
Def.
Note
40
OAL3
Output where alarm
AL3 is addressed
Out1 / Out2
Out3 / Out4
OFF
OFF
41
AL3t
Alarm AL3 type
LoAb / HiAb
LHAb
LoAb
42
Ab3
Alarm AL3 functioning
0 ÷ 15
0
43
AL3
Alarm AL3 threshold
AL3L÷ AL3H
0
44
AL3L
Low
threshold
band
alarm AL3 or Minimum
set alarm AL3 for high
or low alarm
-1999 ÷ AL3H -1999
45
AL3H
High threshold band
alarm AL3 or Maximum
set alarm AL3 for high
or low alarm
AL3L ÷ 9999
9999
46
HAL3
Alarm AL3 hysteresis
OFF ÷ 9999
1
47
AL3d
Activation delay of
alarm AL3
OFF ÷ 9999
sec.
OFF