![Ascon tecnologic TLI40 Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/ascon-tecnologic/tli40/tli40_operating-instructions-manual_2981565012.webp)
ASCON TECNOLOGIC - TLI 40 - OPERATING INSTRUCTIONS -
PAG. 12
tc K
“HCFG” = tc
“SEnS” = CrAl
-270 ... 1370 °C
- 454 ... 2498 °F
-199.9 ... 999.9 °C
-199.9 ... 999.9 °F
tc S
“HCFG” = tc
“SEnS” = S
-50 ... 1760 °C
-58 ... 3200 °F
-50.0 ... 999.9 °C
-58.0 ... 999.9 °F
tc B
“HCFG” = tc
“SEnS” = b
72 ... 1820 °C
162 ... 3308 °F
72.0 ... 999.9 °C
162.0 ... 999.9 °F
tc E
“HCFG” = tc
“SEnS” = E
-150 ... 750 °C
-252 ... 1382 °F
-150.0 ... 999.9 °C
-199.9 ... 999.9 °F
tc L
“HCFG” = tc
“SEnS” = L
-150 ... 900 °C
-252 ... 1652 °F
-150.0 ... 900.0 °C
-199.9 ... 999.9 °F
tc N
“HCFG” = tc
“SEnS” = n
-270 ... 1300 °C
-454 ... 2372 °F
-199.9 ... 999.9 °C
-199.9 ... 999.9 °F
tc R
“HCFG” = tc
“SEnS” = r
-50 ... 1760 °C
-58 ... 3200 °F
-50.0 ... 999.9 °C
-58.0 ... 999.9 °F
tc T
“HCFG” = tc
“SEnS” = t
-270 ... 400 °C
-454 ... 752 °F
-199.9 ... 400.0 °C
-199.9 ... 752.0 °F
tc C
“HCFG” = tc
“SEnS” = C
0 ... 2320 °C
32 ... 4208 °F
0.0 ... 999.9 °C
32.0 ... 999.9 °F
TECNOLOGIC IRS
range “A”
“HCFG” = tc
“SEnS”= Ir.J - Ir.CA
-46 ... 785 °C
-50 ... 1445 °F
-46.0 ... 785.0 °C
-50.8 ... 999.9 °F
Pt100 (IEC)
“HCFG” = rtd
“SEnS” = Pt1
-200 ... 850 °C
-328 ... 1562 °F
-99.9 ... 850.0 °C
-99.9 ... 999.9 °F
PTC (KTY81-121)
“HCFG” = rtd
“SEnS” = Ptc
-55 ... 150 °C
-67 ... 302 °F
-55.0 ... 150.0 °C
-67.0 ...302.0 °F
NTC (103-AT2)
“HCFG” = rtd
“SEnS” = ntc
-50 ... 110 °C
-58 ... 230 °F
-50.0 ... 110.0 °C
-58.0 ... 230.0 °F
0..20 mA
“HCFG” = I
“SEnS” = 0.20
-1999 ... 9999
-199.9 ... 999.9
-19.99 ... 99.99
-1.999 ... 9.999
4..20 mA
“HCFG” = I
“SEnS” = 4.20
-1999 ... 9999
-199.9 ... 999.9
-19.99 ... 99.99
-1.999 ... 9.999
0 ... 50 mV
“HCFG” = UoLt
“SEnS” = 0.50
-1999 ... 9999
-199.9 ... 999.9
-19.99 ... 99.99
-1.999 ... 9.999
0 ... 60 mV
“HCFG” = UoLt
“SEnS” = 0.60
-1999 ... 9999
-199.9 ... 999.9
-19.99 ... 99.99
-1.999 ... 9.999
12 ... 60 mV
“HCFG” = UoLt
“SEnS” = 12.60
-1999 ... 9999
-199.9 ... 999.9
-19.99 ... 99.99
-1.999 ... 9.999
0 ... 5 V
“HCFG” = UoLt
“SEnS” = 0.5
-1999 ... 9999
-199.9 ... 999.9
-19.99 ... 99.99
-1.999 ... 9.999
1 ... 5 V
“HCFG” = UoLt
“SEnS” = 1.5
-1999 ... 9999
-199.9 ... 999.9
-19.99 ... 99.99
-1.999 ... 9.999
0 ... 10 V
“HCFG” = UoLt
“SEnS” = 0.10
-1999 ... 9999
-199.9 ... 999.9
-19.99 ... 99.99
-1.999 ... 9.999
2 ... 10 V
“HCFG” = UoLt
“SEnS” = 2.10
-1999 ... 9999
-199.9 ... 999.9
-19.99 ... 99.99
-1.999 ... 9.999
Potentiometer
(> 1 K
Ω
Ω
Ω
Ω
)
“HCFG” = UoLt
“SEnS” = Pot
-1999 ... 9999
-199.9 ... 999.9
-19.99 ... 99.99
-1.999 ... 9.999
7.6 - INSTRUMENT ORDERING CODE
TLI 40 a b c d e f g h ii
a : POWER SUPPLY
L
= 24 VAC/VDC
H
= 100 ... 240 VAC
b : OUTPUT OUT1
-
= None
R
= Relay
O
= Voltage VDC for SSR
C
= Analogue 0/4 ..20 mA
V
= Analogue 0/2 .. 10 V
c : OUTPUT OUT2
-
= None
R
= Relay
O
= Voltage VDC for SSR
d : OUTPUT OUT3
-
= None
R
= Relay
O
= Voltage VDC for SSR
e : OUTPUT OUT4
-
= None
R
= Relay
O
= Voltage VDC for SSR
f : COMMUNICATION INTERFACE
S
= RS 485 Serial interface
I
= RS 485 Serial Int digital input
-
= No interface
g : SENSORS OUTPUT SUPPLY
A
= 12 VDC
B
= 2,5 VDC (Potentiometer input)
h : OPTIONAL PROBES
- = None
ii = SPECIAL CODES
Note :
- The output OUT4 must be the same type as OUT3.
- The digital input can only be present as an alternative to the output
OUT4.
TLI 40 PASSWORD = 381