Ascon Tecnologic - KX5P Line - ENGINEERING MANUAL - PAG. 37
no. Param.
Description
Dec.
Point
Values
Default
89
diSP
Display management
nonE Standard display;
Pou
Output Power;
PoS
Valve position (servomotor control);
SpF
Final set point;
Spo
Operative set point;
AL1
Alarm 1 threshold;
AL2
Alarm 2 threshold;
AL3
Alarm 3 threshold;
Pr.tu
- During a soak, the instrument shows the soak elapsed time;
- During a ramp the display shows the operative set point. At the end
of the program execution, the instrument will show “P.End” messages
alternately with the measured value;
-
When no program is running, the instrument shows the standard display;
Pr.td
- During a soak, the instrument shows the soak remaining time (count
down);
- During a ramp the display shows the operative set point. At the end
of the program execution, the instrument shows “
P.End
” messages
alternately with the measured value;
-
When no program is running, the instrument shows the standard display;
P.t.tu When the programmer is running, the display shows the total elapsed
time. At the end of the program execution, the instrument shows “
p.End
”
messages alternately with the measured value;
P.t.td When the programmer is running, the display shows the total remaining
time (count down). At the end of the program execution, the instrument
shows “
P.End
” messages alternately with the measured value;
PErc Percent of the power output used during soft start (when the soft start
time is equal to infinite, the limit is ever active and it can be used also
when ON/OFF control is selected).
Pr.tu
90
di.cL
Display colour
0 The display colour is used to show the actual deviation (PV - SP);
1 Display red (fix);
2 Display green (fix);
3 Display orange (fix).
0
91
AdE
Deviation for display
colour management
1... 9999 (E.U.)
5
92
di.St
Display Timeout
2
oFF (display always ON);
0.1... 99.59 (mm.ss).
oFF
93
fiLd
Filter on the displayed
value
1
oFF (filter disabled);
0.1... 20.0 (E.U.).
oFF
94
bG.F
Bar graph Function
0
nonE Bargraph not lit;
Pou
PID Output power;
PoS
Valve position (servomotor control);
Pr.tu Elapsed time of the program in execution;
Pr.td Time to end of the program in execution;
Pr.tS Time to end of the program segment in execution.
Pou
95
dSPu
Instrument status at
power ON
AS.Pr Starts in the same way it was prior to the power down;
Auto
Starts in Auto mode;
oP.0
Starts in manual mode with a power output equal to zero;
St.bY Starts in stand-by mode.
AS.Pr
96
oPr.E
Operative modes
enabling
ALL
All modes will be selectable by the next parameter;
Au.oP Auto and manual (
oPLo
) mode only will be selectable by the next para-
meter;
Au.Sb Auto and Stand-by modes only will be selectable by the next parameter.
ALL
97
oPEr
Operative mode selection
If oPr.E = ALL:
- Auto = Auto mode;
-
oPLo = Manual mode;
-
St.bY = Stand by mode.
If oPr.E = Au.oP: -
Auto = Auto mode;
- oPLo = Manual mode.
If oPr.E = Au.Sb: - Auto = Auto mode;
-
St.bY = Stand by mode.
Auto