Ascon Tecnologic - KX5P Line - ENGINEERING MANUAL - PAG. 26
[148] P1.E3 - Events of the third group
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
and
[144] P1.S3 is different from
oFF
.
Range:
00.00... 11.11 where:
0
Event OFF;
1
Event ON.
Note:
For more details see [138]P1.E1 parameter.
[149] P1.S4 - Set point of the fourth soak
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
and
[144] P1.S3 is different from
oFF
.
Range:
From [75] SPLL to [76] SPHL;
oFF
Program end.
Note:
For more details see [139]P1.S2 parameter.
[150] P1.G4 - Gradient of the fourth ramp
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
,
[144] P1.S3 is different from
oFF
and
[149] P1.S4 is different from
oFF
Range:
0.1... 999.9 enginering units per minute;
inF
Step transfer.
[151] P1.t4 - Time of the fourth soak
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
,
[144] P1.S3 is different from
oFF
and
[149] P1.S4 is different from
oFF
.
Range:
0.00... 99.59 time units.
[152] P1.b4 - Wait band of the fourth soak
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
,
[144] P1.S3 is different from
oFF
and
[149] P1.S4 is different from
oFF
.
Range:
From OFF to 9999 engineering units.
Note:
For more details see [137] P1.b1 parameter.
[153] P1.E4 - Event of the fourth segment
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
,
[144] P1.S3 is different from
oFF
and
[149] P1.S4 is different from
oFF
.
Range:
00.00... 11.11 where:
0
Event OFF;
1
Event ON.
Note:
For more details see [138] P1.E1 parameter.
[154] P1.S5 - Set point of the fifth soak
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
,
[144] P1.S3 is different from
oFF
and
[149] P1.S4 is different from
oFF
.
Range:
From [75] SPLL to [76] SPHL;
oFF
Program end.
Note:
For more details see [139] P1.S2 parameter.
[155] P1.G5 - Gradient of the fifth ramp
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
,
[144] P1.S3 is different from
oFF
,
[149] P1.S4 is different from
oFF
and
[154] P1.S5 is different from
oFF
.
Range:
0.1... 999.9 enginering units per minute;
inF
Step transfer.
[156] P1.t5 - Time of the fifth soak
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
,
[144] P1.S3 is different from
oFF
,
[149] P1.S4 is different from
oFF
and
[154] P1.S5 is different from
oFF
.
Range:
0.00... 99.59 time units.
[157] P1.b5 - Wait band of the fifth soak
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
,
[144] P1.S3 is different from
oFF
,
[149] P1.S4 is different from
oFF
and
[154] P1.S5 is different from
oFF
.
Range:
From OFF to 9999 engineering units.
Note:
For more details see [137] P1.b1 parameter.
[158] P1.E5 - Event of the fifth segment
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
,
[144] P1.S3 is different from
oFF
,
[149] P1.S4 is different from
oFF
and
[154] P1.S5 is different from
oFF
.
Range:
00.00... 11.11 where:
0
Event OFF;
1
Event ON.
Note:
For more details see [138]P1.E1 parameter.
[159] P1.S6 - Set point of the sixth soak
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
,
[144] P1.S3 is different from
oFF
,
[149] P1.S4 is different from
oFF
and
[154] P1.S5 is different from
oFF
.
Range:
From [75] SPLL to [76] SPHL;
oFF
Program end.
Note:
For more details see [139]P1.S2 parameter.
[160] P1.G6 - Gradient of the sixth ramp
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
,
[144] P1.S3 is different from
oFF
,
[149] P1.S4 is different from
oFF
,
[154] P1.S5 is different from
oFF
and
[159] P1.S6 is different from
oFF
.
Range:
0.1... 999.9 enginering units per minute;
inF
Step transfer.
[161] P1.t6 - Time of the sixth soak
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
,
[144] P1.S3 is different from
oFF
,
[149] P1.S4 is different from
oFF
,
[154] P1.S5 is different from
oFF
and
[159] P1.S6 is different from
oFF
.
Range:
0.00... 99.59 time units.
[162] P1.b6 - Wait band of the sixth soak
Available:
When [129] P1.F is different from
nonE
,
[139] P1.S2 is different from
oFF
,
[144] P1.S3 is different from
oFF
,
[149] P1.S4 is different from
oFF
,
[154] P1.S5 is different from
oFF
and
[159] P1.S6 is different from
oFF
.
Range:
From OFF to 9999 engineering units.
Note:
For more details see [137] P1.b1 parameter.