Ascon Tecnologic - KX5P Line - ENGINEERING MANUAL - PAG. 18
[89] diSP - Display management
Available:
Always.
Range:
nonE
Standard display;
Pou
Power output;
PoS
Valve position (servomotor control);
SPF
Final set point;
Spo
Operative set point;
AL1
Alarm 1 threshold;
AL2
Alarm 2 threshold;
AL3
Alarm 3 threshold;
Pr.tu
During a soak, the instrument shows the
elapsed time of the soak;
• During a ramp the display shows the opera-
tive set point;
• At the end of the program execution, the
instrument shows “P.End” messages alter-
nately with the measured value;
• When no program is running, the instrument
will show the standard display;
Pr.td
During a soak, the instrument will show the
remaining time of the soak (count down);
• During a ramp the display will show the op-
erative set point. At the end of the program
execution, the instrument shows
P.End
mes-
sage alternately with the measured value;
• When no program is running, the instrument
will show the standard display.;
P.t.tu
When the programmer is running, the display
shows the total elapsed time. At the end of the
program execution, the instrument show
t.End
message alternately with the measured value;
P.t.td
When the programmer is running, the display
shows the total remaining time (count down).
At the end of the program execution, the in-
strument shows
P.End
message alternately
with the measured value;
PErc
Percent of the power output used during soft
start (when the soft start time is equal to
infinite, the limit is ever active and it can be
used also when ON/OFF control is selected).
[90] di.CL - Display colour
Available:
Always.
Range:
0 The display colour is used to show the actual
deviation (PV - SP);
1 Display red (fix);
2 Display green (fix);
3 Display orange (fix).
[91] AdE - Deviation for display colour management
Available:
When [90] di.CL = 0.
Range:
1... 9999 engineering units.
[92] diS.t - Display time out
Available:
Always.
Range:
oFF
The display is always ON;
0.1... 99.59 minutes and seconds.
Note:
This function allows to turn OFF the display when no
alarm is present and no action is made on the instrument.
When diS.t is different from OFF and no button is pressed
for more than the programmed time out, the display goes
OFF and only 4 segments of the less significant digit are
turned ON in sequence in order to show that the instru-
ment is working correctly. If an alarm occurs or a button
is pressed, the display returns to the normal operation.
[93] FiLd - Filter on the displayed value
Available:
Always.
Range:
0.0
oFF (Filter disabled);
0.1... 20.0 in engineering units.
Note:
This is a “window filter” related to the set point, it is applied
to the displayed value only and it have no effect on the
other functions of the instrument (control, alarms, etc.).
[94] bG.F - Bargraph function
Available:
Always.
Range:
nonE
Bargraph not lit;
Pou
Output power calculated by PID (single ac-
tion: 0... 100%, double action: -100... +100%);
PoS
Valve position (servomotor control);
Pr.tu
Elapsed time of the program in execution;
Pr.td
Time to end of the program in execution;
Pr.tS
Time to end of the program segment in
execution;
Note:
Displaying values using the bar graph is possible only
if the variables involved are configured.
If it has been chosen to display the time of the
program; the bargraph is off if the option is not
configured; has the first LED lit if the option is
configured but not running.
[95] dSPu - Instrument Status at power up
Available:
Always.
Range:
AS.Pr Starts in the same way it was prior to the
power down;
Auto
Starts in Auto mode;
oP.0
Starts in manual mode with a power output
equal to zero;
St.bY
Starts in stand-by mode.
Notes: 1.
When you change the value of [96] oPr.E, the in-
strument forces [97] oPEr parameter equal to Auto.
2.
During program execution the instrument stores
the segment currently in use and, by a 30 minutes
interval, it stores also t he elapsed time of the soak.
If a power down occurs during program execution, at
the next power up the instrument is able to continue
the program execution starting from the segment in
progress at power down and, if the segment was a
soak, it is also capable to restart from the soak time
minus the stored elapsed time. In order to obtain this
features, the “[95] dSPu - Status of the instrument at
power up” parameter must be set to “AS.Pr”. If the
“[95] dSPu” parameter is different from “AS.Pr” the
storing function is inhibited.
[96] oPr.E - Operative modes enabling
Available:
Always.
Range:
ALL
All modes will be selectable by the next
parameter.
Au.oP Auto and manual (oPLo) mode only will be
selectable by the next parameter.
Au.Sb Auto and Stand-by modes only will be se-
lectable by the next parameter.
Note:
Changing the value of [96] oPr.E, the instrument
forces [97] oPEr parameter to Auto.