Ascon Tecnologic - KM1E/KR1E - Wine - ENGINEERING MANUAL - 

PAG. 6

6  CONFIGURATION PROCEDURE

6.1  Introduction

When the instrument is switched ON, it starts immediately working 
in accordance with the parameters values loaded in memory.
The instrument behaviour and its performance are governed 
by the value of the stored parameters.
At the first start up the instrument will use a “default” param-
eter set (factory parameter set); this set is a generic one  
(e.g. a TC Pt100 input is programmed).

D

D

Before connecting the output actuators

,  

we recommend to configure the parameters to suit your 
application (e.g.: input type, Control strategy, alarms, etc.).

D

D

Do not change the 

[6] Unit (Engineering Unit)

 value 

during process control as the temperature values 
inserted by the user (thresholds, limits etc.) are not 
automatically rescaled by the instrument.

To change these parameters you need to enter the 

Configuration mode

”.

6.2  Instrument description

This instrument is a special version derived from our standard 
KUBE line and dedicated to the specific needs of wine making 
and oenology markets with the following features:

 

Temperature ON/OFF control with hysteresis, Heating (set 
point SP) or Cooling (set point SP2);

 

Highly readable display whose color indicates if control is 
in Heating (Red) or Cooling (Green) mode selected, for a 
safe control.

Suitable for the following control modes:

 

One circuit control (Out1 relay for Heating and Cooling – 
see [1] node = 1 at page 6);

 

2 circuits control (Out1 relay for Heating and Out2 relay for 
Cooling – see [1] node = 2 at page 6) with manual selec-
tion Heating or Cooling;

 

2 circuits control (Out1 relay for Heating and Out2 relay for 
Cooling – see [1] node = 3 at page 6) with automatic Heat-
ing and Cooling action;

 

Select Heating or Cooling manually by dedicated front button, 
or digital input, or serial communication, or automatically;

 

Select Control run (Auto) or stop (Stand-By) manually by dedi-
cated front button, or digital input, or serial communication;

 

Alarms low (AL1) and high (AL2) and sensor break detec-
tion with relay output Out3;

 

Temperature sensor break detection with manual forcing of 
control output;

 

Easy to configure for the installer (wine market preconfig-
ure), easy to use for the operator (dedicated front buttons);

 

Controller and/or software configuration backup using the 
key (

A01

) through the serial port;

 

3 separated menus: operator (free access), limited access 
(protected), configuration (protected).

With its high standard of adaptability this instrument is able 
to cover all wine market needs at highest reliability level.

6.3  Instrument behaviour at Power ON

At power ON the instrument can start in one of the following 
mode depending on its configuration:

Auto mode

 

The upper display shows the measured value;

 

The lower display shows the Set point value;

 

The decimal figure of the less significant digit of the lower 
display is OFF;

 

The instrument is performing the standard closed loop control.

Standby mode

 (

St.bY

).

 

The upper display shows the measured value;

 

The lower display shows alternately the set point value and 
the message 

St.bY

 or 

od

;

 

The instrument does not perform any control (the control 
outputs are OFF);

 

The instrument is working as an indicator.

We define all the above described conditions as “

Standard 

display

”.

6.4 

Entering the “Configuration modes”

6.4.1  Complete configuration procedure

The configuration parameters are collected in various 
groups.  Every group defines all parameters related with a 
specific function (e.g.: control, alarms, output functions).

1. 

Push the 

 button for more than 5 seconds.  The upper 

display will show 

PASS

 while the lower display shows 

0

.

2. 

Using 

 and 

 buttons set the programmed password.

Notes:   1. 

The factory default password for configuration 
parameters is equal to 

30

.

2. 

During parameter modification the instrument 
continue to perform the control. 
In certain conditions, when a configuration change 
can produce a heavy bump to the process, it is 
advisable to temporarily stop the controller from 
controlling during the programming procedure 
(control output will be OFF). 
A password equal to 

2000 + the programmed 

value

 (e.g. 2000 + 30 = 2030). 

The control will restart automatically when the 
configuration procedure will be manually closed.

3. 

Push the 

 button 

If the password is correct the display shows the acronym of 
the first parameter group preceded by the symbol: 

]

In other words the upper display shows: 

]inp

  

(group of the 

Input parameters

).

The instrument is in configuration mode.

6.5 

How to exit the “Configuration mode”

Push 

 button for more than 5 seconds, the instrument 

returns to the “

Standard display

”.

Содержание K 1E Series

Страница 1: ...racteristics 1 It should be easily accessible 2 There is minimum vibrations and no impact 3 There are no corrosive gases 4 There are no water or other fluids i e condensation 5 The ambient temperature...

Страница 2: ...Pin q1 4 mm 0 055 in max Stripped wire L 5 5 mm 0 21 in Note Terminal 4 can be programmed as Digital Input DI2 connecting a free of voltage contact between terminals 4 and 11 0 12 V SSR Drive Output O...

Страница 3: ...igital input 1 Digital input 2 5 6 11 4 KR1E Maximum contact resistance 100 Contact rating DI1 10 V 6 mA DI2 12 V 30 mA Logic inputs driven by 24 VDC Digital Input 2 4 15 16 Digital Input 1 KM1E 5 6 1...

Страница 4: ...Vout 0 5 VDC Logic level 1 12 V 20 15 mA max 3 4 4 Output 4 OP4 SSR Output SSR 4 Out4 4 16 KM1E SSR 11 4 KR1E Logic level 0 Vout 0 5 VDC Logic level 1 12 V 20 20 mA max Note Overload protected 3 5 Se...

Страница 5: ...oom temperature Electromagnetic compatibility and safety requirements Compliance directive EMC 2004 108 CE EN 61326 1 directive LV 2006 95 CE EN 61010 1 Installation category II Pollution category 2 T...

Страница 6: ...sy to use for the operator dedicated front buttons Controller and or software configuration backup using the key A01 through the serial port 3 separated menus operator free access limited access prote...

Страница 7: ...in Appendix A 6 8 Configuring all the parameters In the following pages we are going to describe all the instrument s parameters However the instrument will only show the parameters applicable to its...

Страница 8: ...4 or UPDN it will be forced to nonE too 4 Changing 8 io4F on to 8 io4F Out4 makes the 19 O4F parameter visible and equal to nonE 9 diF1 Digital input 1 function Available Always oFF No function Range...

Страница 9: ...e 1 Alarm 1 2 Alarm 2 4 Sensor break burn out 8 Overload on Out4 short circuit on the Out4 15 o2Ac Out 2 action Available When 1 nodE is equal to 1 and 13 o2F is dif ferent from nonE Range dir Direct...

Страница 10: ...nd low alarms is the low limit of the AL1 threshold For band alarm is the low alarm threshold Available When 22 AL1t is different from nonE Range From 1999 to 25 AL1H engineering units 25 AL1H For Hig...

Страница 11: ...ode and out of range indications Available When 30 AL2t different from nonE Range 0 Never 1 During Standby 2 During overrange and underrange 3 During overrange underrange and stand by rEG group Contro...

Страница 12: ...ontrol alarms etc 53 dSPu Status of the instrument at power up Available Always Range AS Pr Starts in the same way it was prior to the power down Auto Starts in Auto mode St bY Starts in stand by mode...

Страница 13: ...s The instru ment will come back to the Standard display 7 PARAMETER PROMOTION Another important step of the instrument configuration is due to the possibility to create a custom HMI interface in orde...

Страница 14: ...different phases can require different control actions As an example a cooling action is frequently required during fermentation but in other phases an heating action can be necessary to obtain specif...

Страница 15: ...will show on the upper display the acronym of the first parameter promoted to this level and on the lower one its value 6 Using the buttons assign to this parameter the desired value 7 Press the butto...

Страница 16: ...bsolute alarms are operative or not according to the ALxo Alarm x enabling during Stand by mode parameter setting 2 Switching to Standby mode during self tune execution causes the the self tune functi...

Страница 17: ...Make sure that there are no loose terminals 5 Before turning ON the instrument make sure it is perfectly dry 6 Apply the power supply to the instrument 10 3 Disposal The appliance or the product must...

Страница 18: ...F Ir cA Exergen IRS K 46 785 C 50 1445 F Ptc 3 dp Decimal Point Position linear inputs 0 0 3 0 Decimal Point Position different than linear inputs 0 1 4 SSC Initial scale read out for linear inputs dp...

Страница 19: ...16 o3F Out3 function nonE Output not used AL Alarm output or bo Out of range or burn out indicator P FAL Power failure indicator bo PF Out of range Burnout and Power failure indicator St By Standby st...

Страница 20: ...nd by 0 AL2 group Alarm 2 parameters no Param Description Dec Point Values Default 30 AL2t Alarm 2 type 0 nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAo Windows alarm in ala...

Страница 21: ...function AAc Alarm reset ASi Alarm acknowledge chSP Sequential set point selection note St by Standby mode The first pression puts the instrument in standby mode while a second one puts the instrumen...

Страница 22: ...by 24 6 Totalizer of control relay worked hours number of hours the control relay has been in ON condition 7 Totalizer of control relay worked days with threshold number of hours the control relay ha...

Страница 23: ...Ascon Tecnologic KM1E KR1E Wine ENGINEERING MANUAL PAG 23...

Страница 24: ...Ascon Tecnologic KM1E KR1E WINE ENGINEERING MANUAL PAG 24...

Отзывы: