Ascon Tecnologic - KM1E/KR1E - Wine - ENGINEERING MANUAL - PAG. 20
]
AL1 group - Alarm 1 parameters
no. Param.
Description
Dec.
Point
Values
Default
22
AL1t
Alarm 1 type
0
nonE
Alarm not used;
LoAb
Absolute low alarm;
HiAb
Absolute high alarm;
LHAo
Windows alarm in alarm outside the windows;
LHAI
Windows alarm in alarm inside the windows;
SE.br
Sensor Break.
HiAb
23
Ab1
Alarm 1 function
0
0... 7:
+1 Not active at power up;
+2 Latched alarm (manual reset);
+4 Acknowledgeable alarm.
0
24
AL1L
- For High and low alarms, it is the low limit
of the AL1 threshold;
- For band alarm, it is low alarm threshold
dp
From -1999 to AL1H (E.U.)
-1999
25
AL1H
- For High and low alarms, it is the high
limit of the AL1 threshold;
- For band alarm, it is high alarm threshold
dp
From AL1L to 9999 (E.U.)
9999
26
AL1
AL1 threshold
dp
From AL1L to AL1H (E.U.)
0
27
HAL1
AL1 hysteresis
dp
1... 9999 (E.U.)
1
28
AL1d
AL1 delay
0
0 oFF;
1... 9999 (s)
oFF
29
AL1o
Alarm 1 enabling during Stand-by mode and
out of range conditions
0
0 Never;
1 During stand by mode;
2 During overrange and underrange;
3 During overrange, underrange and stand-by.
0
]
AL2 group - Alarm 2 parameters
no. Param.
Description
Dec.
Point
Values
Default
30
AL2t
Alarm 2 type
0
nonE
Alarm not used;
LoAb
Absolute low alarm;
HiAb
Absolute high alarm;
LHAo
Windows alarm in alarm outside the windows;
LHAI
Windows alarm in alarm inside the windows;
SE.br
Sensor Break.
Loab
31
Ab2
Alarm 2 function
0
0... 7:
+1 Not active at power up;
+2 Latched alarm (manual reset);
+4 Acknowledgeable alarm.
0
32
AL2L
- For High and low alarms, it is the low limit
of the AL2 threshold;
- For band alarm, it is low alarm threshold
dp
From -1999 to AL2H (E.U.)
-1999
33
AL2H
- For High and low alarms, it is the high
limit of the AL2 threshold;
- For band alarm, it is high alarm threshold
dp
From AL2L to 9999 (E.U.)
9999
34
AL2
AL2 threshold
dp
From AL2L to AL2H (E.U.)
0
35
HAL2
AL2 hysteresis
dp
1... 9999 (E.U.)
1
36
AL2d
AL2 delay
0
0 oFF;
1... 9999 (s)
oFF
37
AL2o
Alarm 2 enabling during Stand-by mode and
out of range conditions
0
0 Never;
1 During stand by mode;
2 During overrange and underrange;
3 During overrange, underrange and stand-by.
0
]
rEG group - Control Parameters
no. Param.
Description
Dec.
Point
Values
Default
38
HSt.H
Hysteresis of the Heating action
1... 999 (E.U.)
39
HSt.C
Hysteresis of the Cooling action
1... 999 (E.U.)
40
od
Delay at Power ON
oFF
Function not used;
0.01... 99.59 hh.mm.