Ascon Tecnologic - KM1E/KR1E - Wine - ENGINEERING MANUAL - PAG. 20

 

]

AL1 group - Alarm 1 parameters

no. Param.

Description

Dec. 

Point

Values

Default

22 

AL1t

Alarm 1 type

0

nonE 

Alarm not used;

LoAb 

Absolute low alarm;

HiAb 

Absolute high alarm;

LHAo 

Windows alarm in alarm outside the windows;

LHAI 

Windows alarm in alarm inside the windows;

SE.br 

Sensor Break.

HiAb

23 

Ab1

Alarm 1 function

0

0... 7:

+1  Not active at power up;

+2  Latched alarm (manual reset);

+4  Acknowledgeable alarm.

0

24 

AL1L

 

- For High and low alarms, it is the low limit 

of the AL1 threshold;

 

- For band alarm, it is low alarm threshold

dp

From -1999 to AL1H (E.U.)

-1999

25 

AL1H

 

- For High and low alarms, it is the high 

limit of the AL1 threshold;

 

- For band alarm, it is high alarm threshold

dp

From AL1L to 9999 (E.U.)

9999

26 

AL1

AL1 threshold

dp

From AL1L to AL1H (E.U.)

0

27 

HAL1

AL1 hysteresis

dp

1... 9999 (E.U.)

1

28 

AL1d

AL1 delay

0

0 oFF;

1... 9999 (s)

oFF

29 

AL1o

Alarm 1 enabling during Stand-by mode and 

out of range conditions

0

 0  Never;

 1  During stand by mode;

 2  During overrange and underrange;

 3  During overrange, underrange and stand-by.

0

 

]

AL2 group - Alarm 2 parameters

no. Param.

Description

Dec. 

Point

Values

Default

30 

AL2t

Alarm 2 type

0

nonE 

Alarm not used;

LoAb 

Absolute low alarm;

HiAb 

Absolute high alarm;

LHAo 

Windows alarm in alarm outside the windows;

LHAI 

Windows alarm in alarm inside the windows;

SE.br 

Sensor Break.

Loab

31 

Ab2

Alarm 2 function

0

0... 7:

+1  Not active at power up;

+2  Latched alarm (manual reset);

+4  Acknowledgeable alarm.

0

32 

AL2L

 

- For High and low alarms, it is the low limit 

of the AL2 threshold;

 

- For band alarm, it is low alarm threshold

dp

From -1999 to AL2H (E.U.)

-1999

33 

AL2H

 

- For High and low alarms, it is the high 

limit of the AL2 threshold;

 

- For band alarm, it is high alarm threshold

dp

From AL2L to 9999 (E.U.)

9999

34 

AL2

AL2 threshold

dp

From AL2L to AL2H (E.U.)

0

35 

HAL2

AL2 hysteresis

dp

1... 9999 (E.U.)

1

36 

AL2d

AL2 delay

0

0 oFF;

1... 9999 (s)

oFF

37 

AL2o

Alarm 2 enabling during Stand-by mode and 

out of range conditions

0

 0  Never;

 1  During stand by mode;

 2  During overrange and underrange;

 3  During overrange, underrange and stand-by.

0

 

]

rEG group - Control Parameters

no. Param.

Description

Dec. 

Point

Values

Default

38 

HSt.H

Hysteresis of the Heating action

1... 999 (E.U.)

39 

HSt.C

Hysteresis of the Cooling action

1... 999 (E.U.)

40 

od

Delay at Power ON

oFF 

Function not used;

0.01... 99.59 hh.mm.

Содержание K 1E Series

Страница 1: ...racteristics 1 It should be easily accessible 2 There is minimum vibrations and no impact 3 There are no corrosive gases 4 There are no water or other fluids i e condensation 5 The ambient temperature...

Страница 2: ...Pin q1 4 mm 0 055 in max Stripped wire L 5 5 mm 0 21 in Note Terminal 4 can be programmed as Digital Input DI2 connecting a free of voltage contact between terminals 4 and 11 0 12 V SSR Drive Output O...

Страница 3: ...igital input 1 Digital input 2 5 6 11 4 KR1E Maximum contact resistance 100 Contact rating DI1 10 V 6 mA DI2 12 V 30 mA Logic inputs driven by 24 VDC Digital Input 2 4 15 16 Digital Input 1 KM1E 5 6 1...

Страница 4: ...Vout 0 5 VDC Logic level 1 12 V 20 15 mA max 3 4 4 Output 4 OP4 SSR Output SSR 4 Out4 4 16 KM1E SSR 11 4 KR1E Logic level 0 Vout 0 5 VDC Logic level 1 12 V 20 20 mA max Note Overload protected 3 5 Se...

Страница 5: ...oom temperature Electromagnetic compatibility and safety requirements Compliance directive EMC 2004 108 CE EN 61326 1 directive LV 2006 95 CE EN 61010 1 Installation category II Pollution category 2 T...

Страница 6: ...sy to use for the operator dedicated front buttons Controller and or software configuration backup using the key A01 through the serial port 3 separated menus operator free access limited access prote...

Страница 7: ...in Appendix A 6 8 Configuring all the parameters In the following pages we are going to describe all the instrument s parameters However the instrument will only show the parameters applicable to its...

Страница 8: ...4 or UPDN it will be forced to nonE too 4 Changing 8 io4F on to 8 io4F Out4 makes the 19 O4F parameter visible and equal to nonE 9 diF1 Digital input 1 function Available Always oFF No function Range...

Страница 9: ...e 1 Alarm 1 2 Alarm 2 4 Sensor break burn out 8 Overload on Out4 short circuit on the Out4 15 o2Ac Out 2 action Available When 1 nodE is equal to 1 and 13 o2F is dif ferent from nonE Range dir Direct...

Страница 10: ...nd low alarms is the low limit of the AL1 threshold For band alarm is the low alarm threshold Available When 22 AL1t is different from nonE Range From 1999 to 25 AL1H engineering units 25 AL1H For Hig...

Страница 11: ...ode and out of range indications Available When 30 AL2t different from nonE Range 0 Never 1 During Standby 2 During overrange and underrange 3 During overrange underrange and stand by rEG group Contro...

Страница 12: ...ontrol alarms etc 53 dSPu Status of the instrument at power up Available Always Range AS Pr Starts in the same way it was prior to the power down Auto Starts in Auto mode St bY Starts in stand by mode...

Страница 13: ...s The instru ment will come back to the Standard display 7 PARAMETER PROMOTION Another important step of the instrument configuration is due to the possibility to create a custom HMI interface in orde...

Страница 14: ...different phases can require different control actions As an example a cooling action is frequently required during fermentation but in other phases an heating action can be necessary to obtain specif...

Страница 15: ...will show on the upper display the acronym of the first parameter promoted to this level and on the lower one its value 6 Using the buttons assign to this parameter the desired value 7 Press the butto...

Страница 16: ...bsolute alarms are operative or not according to the ALxo Alarm x enabling during Stand by mode parameter setting 2 Switching to Standby mode during self tune execution causes the the self tune functi...

Страница 17: ...Make sure that there are no loose terminals 5 Before turning ON the instrument make sure it is perfectly dry 6 Apply the power supply to the instrument 10 3 Disposal The appliance or the product must...

Страница 18: ...F Ir cA Exergen IRS K 46 785 C 50 1445 F Ptc 3 dp Decimal Point Position linear inputs 0 0 3 0 Decimal Point Position different than linear inputs 0 1 4 SSC Initial scale read out for linear inputs dp...

Страница 19: ...16 o3F Out3 function nonE Output not used AL Alarm output or bo Out of range or burn out indicator P FAL Power failure indicator bo PF Out of range Burnout and Power failure indicator St By Standby st...

Страница 20: ...nd by 0 AL2 group Alarm 2 parameters no Param Description Dec Point Values Default 30 AL2t Alarm 2 type 0 nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAo Windows alarm in ala...

Страница 21: ...function AAc Alarm reset ASi Alarm acknowledge chSP Sequential set point selection note St by Standby mode The first pression puts the instrument in standby mode while a second one puts the instrumen...

Страница 22: ...by 24 6 Totalizer of control relay worked hours number of hours the control relay has been in ON condition 7 Totalizer of control relay worked days with threshold number of hours the control relay ha...

Страница 23: ...Ascon Tecnologic KM1E KR1E Wine ENGINEERING MANUAL PAG 23...

Страница 24: ...Ascon Tecnologic KM1E KR1E WINE ENGINEERING MANUAL PAG 24...

Отзывы: