Ascon Tecnologic - KM1E/KR1E - Wine - ENGINEERING MANUAL - PAG. 18
Appendix A
]
inP GROUP - Main and auxiliary input configuration
no. Param.
Description
Dec.
Point
Values
Default
1
node
Operative mode selection
0
1
Heat or Cool using Out1 only;
2
Heat or Cool using Out1 (H) and Out2 (C);
3
Heat and cool Out1 (H) and Out2 (C).
1
2
SEnS
Sensor selection (according to the HW)
Model D
0
Pt1
RTD Pt 100
(-200... 850°C/-328... 1562°F);
Pt10 RTD Pt 1000
(-200... 500°C/-328... 932°F);
0.60 0... 60 mV;
12.60 12... 60 mV;
0.20 0... 20 mA;
4.20 4... 20 mA;
0.5
0... 5 V;
1.5
1... 5 V, ;
0.10 0... 10 V;
2.10 2... 10 V;
J
TC J
(-50... +1000°C/-58... +1832°F);
crAL TC K
(-50... +1370°C/-58... +2498°F);
S
TC S
(-50... 1760°C/-58... +3200°F);
r
TC R
(-50... +1760°C/-58... +3200);
t
TC T
(-70... +400°C/-94... +752°F);
Ir.J
Exergen IRS J (-46... +785°C/-50... 1445°F);
Ir.cA Exergen IRS K (-46... +785°C/-50... 1445°F).
Pt1
Model P
Ptc
PTC KTY81-121
(-55... 150°C/-67... 302°F);
ntc
NTC 103-AT2
(-50... 110°C/-58... 230°F);
0.60 0... 60 mV;
12.60 12... 60 mV;
0.20 0... 20 mA;
4.20 4... 20 mA;
0.5
0... 5 V;
1.5
1... 5 V, ;
0.10 0... 10 V;
2.10 2... 10 V;
J
TC J
(-50... +1000°C/-58... +1832°F);
crAL TC K
(-50... +1370°C/-58... +2498°F);
S
TC S
(-50... 1760°C/-58... +3200°F);
r
TC R
(-50... +1760°C/-58... +3200);
t
TC T
(-70... +400°C/-94... +752°F);
Ir.J
Exergen IRS J (-46... +785°C/-50... 1445°F);
Ir.cA Exergen IRS K (-46... +785°C/-50... 1445°F).
Ptc
3
dp
Decimal Point Position (linear inputs)
0
0... 3
0
Decimal Point Position (different than linear inputs)
0/1
4
SSC
Initial scale read-out for linear inputs
dp
-1999... 9999
0
5
FSc
Full Scale Readout for linear inputs
dp
-1999... 9999
1000
6
unit
Engineering unit
°C/°F
°C
7
Fil
Digital filter on the measured value
1
0 oFF;
0.1... 20.0 s
1.0
8
IO4.F
I/O 4 function
on
Output used as PWS for TX;
out4
Output 4 (digital output 4);
dG2c
Digital input 2 driven by contact;
dG2U
Digital input 2 driven by voltage.
out4
9
diF1
Digital Input 1 function
none
Not used;
AAc
Alarm reset;
ASi
Alarm acknowledge (ACK);
HoLd
Hold of the measured value;
St.by
Stand by mode (transition).
1
st
contact closure = Standby mode,
2
nd
closure = Auto mode;
St.b2
Manual mode (status).
Contact closed = Stand by, open = Auto;
Hc.tr
Control action & set point selection (transition)
Each contact closure reverts the control action
from Heat (SP1) to Cool (Sp2) and viceversa;;
HC.St
Control action and set point selection (status)
Contact closed = Cool (SP2),
Contact open = Heat (SP1).
oFF
10
diF2
Digital Input 2 function
oFF
11
di.A
Digital Inputs Action
(DI2 only if configured)
0 DI1 direct action, DI2 direct action;
1 DI1 reverse action, DI2 direct action;
2 DI1 direct action, DI2 reverse action;
3 DI1 reverse action, DI2 reverse action.
0