Ascon Tecnologic - e31- - OPERATING INSTRUCTIONS - PAG. 3

To exit the programming mode, press no keys for about 30 s 
or keep the 

 key pressed for 2 s.

Previous

Param.

Normal mode

Parameter select

(Program mode)

Parameters set

Next

Param.

2 s

5 s

Increase

value

Decrease

value

-25.5

sLs

-30.0

2.3 

Parameter protection using the password

The instrument has a parameter protection function using a 
password that can be personalised through the 

tPP

 parameter

To protect the parameters, set the desired password number 
in the parameter 

tPP

.

When the protection is activate, press the 

 key to access 

the parameters and keep it pressed for about 5 s, after which 
the display shows 

r.p

.

Press the 

 key, the display shows 

0

, using the 

/

 keys, 

insert the programmed password number and press the key 

 

again.

If the password is correct the instrument displays the code of 
the first parameter and it will be possible to program the in-
strument in the same way described in the previous section.
The password protection can be disabled by setting 

tPP

 = 

oF

.

2 s

5 s

Increase

value

Decrease

value

-25.5

 rp

   0

 sls

Normal mode

Password

request

Parameter

(Program mode)

Password

correct

Insert password

Note: 

If the Password gets lost, just switch OFF and ON the 
instrument, push 

 key during the initial test keeping 

it pressed for 5 s.  In this way it is possible to access all 
the parameters, verify and modify the parameter 

tPP

.

2.4 

Customized mode parameter programming 

(parameters programming level)

The password hides all the configuration parameters behind a 
factory set password to avoid unwanted changes to the con-
troller parameters.  To make a parameter accessible without 
having to enter the password when 

tPP

 password protection 

is activate, use the procedure that follows:
Enter the program mode using the 

tPP

 Password and select the 

parameter that must be accessible (no password protection).
Once a parameter is selected, if the 

dp LED flashes

 the 

parameter is programmable by entering the password (is 

protected

”).  If the 

dp LED is steady ON

 the parameter is 

programmable without password (is “

unprotected

”).

To change the parameter visibility, press the 

 key and 

keeping it pressed also press the 

 button.

The 

dp LED

 changes its state indicating the new level of 

parameter accessibility (

ON

 = not protected;  

flashing

 = password protected).

In case some parameters are not protected, accessing the 
programming mode the display first shows the not protected 
parameters, then the 

r.p

 parameter (through which will be 

possible to access the “protected” parameters).

Normal mode

2 s

5 s

Increase

value

Decrease

value

-25.5

 r.p

Previous

Param.

Not protected

parameter

Parameters set

Password

request

Insert password

Password OK

Next

Param.

Increase

value

Decrease

value

AHA

 35.0

   0

 sls

Program Mode

2.5 

Reset parameters to default value

The instrument allows the reset of the parameters to values 
programmed in factory as default
To restore the default parameters value set value 

-48

 at 

r.p

 

password request  Therefore, to make the reset to the default 
parameters, enable the Password using the 

tPP

 parameter 

so that the 

r.p

 setting is requested, at this point insert 

-48

 

instead of the programmed access password.
Once confirmed the password with the 

 key the display 

shows “

---

” for 2 s therefore the instrument resets all the 

parameters to factory default setting.

2.6 

Keyboard lock function

On the instrument it is possible to completely lock the keyboard.
This function is useful when the controller is in an accessible 
area and the changes must be avoided.
To activate the keyboard lock it is enough to program the 
parameter 

tLo

 to a value different from 

oF

.

The 

tLo

 value is the keys inactivity time after which the key-

board will be automatically locked.
Therefore, pressing no buttons for the time set at 

tLo

, the in-

strument automatically disable the normal functions of the keys.
When the keyboard is locked, if any of the key is pressed, 
the display showss 

Ln

 to indicate that the lock is active.

To unlock the keyboard it is enough to contemporarily push 

 + 

 keys and keep them pushed for 5 s, after which the 

label 

LF

 appears on the display and all the key functions will 

be available again.

Содержание e31 Series

Страница 1: ...ypically used in cooling ap plications with ON OFF temperature control and defrost control with intervals time by stopping compressor The instrument has 1 relay output and 2 NTC temperature probes inp...

Страница 2: ...PROGRAMMING 2 1 Fast Set point programming The normal mode to program the setpoint is done by mo mentarily pressing the key the display shows SP or SPE alternated to the programmed value To change it...

Страница 3: ...is protected If the dp LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and keeping it pressed also press the button The...

Страница 4: ...d also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for flush in panel mounting Mak...

Страница 5: ...ternal Buzzer SPST NO NO NO C SPDT NO NO NC C 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different condi tions ON Means that the controller uses the control function...

Страница 6: ...The digital input function is defined using the iFi parameter and the action is delayed for the time programmed with pa rameter iti The iFi parameter can be configured for the following functions 0 D...

Страница 7: ...n All these functions are disabled if the relative parameters are set to OFF oF 5 7 Defrost control The automatic defrost control is made with the stopping compressor method it occurs by interval time...

Страница 8: ...rms delay activation time Tempera ture alarms are enabled at the end of the exclusion times and are activated after the AAt time when the temperature measured by the probe exceeds or goes below the re...

Страница 9: ...ent are being supplied directly or through the key AC supply Supply adapter 12 VDC Power supply Enter PWS 12 V A B C TTL USB to PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info please...

Страница 10: ...Do not use HC Do not use C3 Do not use C 21 ddL Display Lock during defrost oF Not active on Active at last measure Lb Active with label dEF during defrost and PdF at defrost oF 22 dcd Defrost activat...

Страница 11: ...scon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characte...

Страница 12: ...2 50 C 90 C with probe NTC 103AT11 11 HOW TO ORDER a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Relay output SPST NO 30A AC1 resistive load R Relay output SPST NO 16A AC1 resist...

Отзывы: