Ascon Tecnologic - e31- - OPERATING INSTRUCTIONS - PAG. 10

7.  PROGRAMMABLE PARAMETERS TABLE

Here below is a description of all the parameters available 
on the instrument.  Some of them may not be present, either 
due to the fact they depend on the type of instrument or be-
cause they are automatically disabled as unnecessary.

Parameter

Description

Range

Def. Note

1

 

SLS

Minimum Set Point

-99.9 ÷ HS

-50.0

2

 

SHS

Maximum Set Point

LS ÷ 999

99.9

3

 

SP

Set Point

LS ÷ HS

0.0

4

 

SPE

Set Point Eco

SP ÷ SHS

0.0

5

 

iuP

Unit of measurement and 

resolution (decimal point)

C0

  °C, resolution 1°;

F0

  °F, resolution 1°;

C1

  °C, resolution 0.1°;

F1

  °F, resolution 0.1°.

C1

6

 

iFt

Measurement filter

oF

  Filter disabled;

0.1 ÷ 20.0 s

2.0

7

 

iC1

Pr1 Probe Calibration

-30.0 ÷ +30.0°C/°F

0.0

8

 

iC2

Pr2 Probe Calibration

-30.0 ÷ +30.0°C/°F

0.0

9

 

iCU

Display offset

-30.0 ÷ +30.0°C/°F

0.0

10

 

iP2

Input Pr2 usage

oF

 Unused;

EP

  Do not use;

Au

  Auxliary probe;

dG

  Digital Input.

dG

11

 

iFi

Function and logic function-

ing of the Digital Input 

(adding the “-” minus sign 

the logic is inverted)

0

 

No function;

1, 2

  Open Door;

3

 

Open Door with Output Lock;

4

 

External Alarm;

5

 

External alarm with output disabling;

6

 

Normal/Eco select;

7

 

On/Stand by select;

8

 

Do not use;

9

 

Defrost cycle start;

10

  Defrost cycle end.

0

12

 

iti

Digital Input Delay

oF

 Disabled;

-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).

oF

13

 

iEt

Eco Mode activation delay 

at Door closed

oF

 Disabled;

-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).

oF

14

 

itt

Max. time functioning in 

Eco Mode

oF

 Disabled;

-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).

oF

15

 

idS

Variable normally displayed

P1

  Probe Pr1 measure;

P2

  Probe Pr2 measure;

P3

  Do not use;

Ec

 Measure 

Pr1

 in Normal mode  

ECO

 label when in ECO mode;

SP

  Set Point;

oF

  Display not lit.

P1

16

 

rd

Differential (Hysteresis)

0.0 ÷ 30.0°C/°F

2.0

17

 

rEd

Differential (Hysteresis) in 

ECO mode

0.0 ÷ 30.0°C/°F

2.0

18

 

rt1

Output activation time for 

Pr1 probe error

oF

 Disabled;

-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).

oF

19

 

rt2

Output deactivation time 

for Pr1 probe error

oF

 Disabled;

-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).

oF

20

 

rHC

Output operating mode

H

 Heating;

C

 Cooling;

nr

  Do not use;

HC

  Do not use;

C3

  Do not use.

C

21

 

ddL

Display Lock during defrost

oF

  Not active;

on

  Active at last measure;

Lb

  Active with label  

dEF

 during defrost and  

PdF

 at defrost.

oF

22

 

dcd

Defrost activation time for 

continuous compressor 

operating

oF

 Disabled;

-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).

oF

23

 

dde

Defrost duration

oF

 Disabled;

-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).

oF

24

 

ddi

Defrosting interval

oF

 Disabled;

-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).

oF

25

 

dSd

Delay first defrost after 

power-on

oF

  Defrost at power-on;

-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).

oF

26

 

PP1

Out delay at switching-on

oF 

Disabled;

-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).

oF

27

 

PP2

Out delay after switch-

ing OFF

oF 

Disabled;

-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).

oF

28

 

PP3

Delay between two output 

switching-ON

oF 

Disabled;

-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).

oF

Parameter

Description

Range

Def. Note

29

 

Pod

Output delay at power ON

oF 

Disabled;

-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).

oF

30

 

AAy

Temperature Alarm 1 type

1

  Absolute for 

Pr1

 with label 

Hi

 - 

Lo

;

2

  Relative to Pr1 with label 

Hi

 - 

Lo

;

3

  Absolute for 

Au

 with label 

Hi

 - 

Lo

;

4

  Relative to 

Au

 with label 

Hi

 - 

Lo

;

5

  Absolute for 

Pr1

 with no label;

6

  Relative to 

Pr1

 with no label;

7

  Absolute for 

Au

 with no label;

8

  Relative to 

Au

 with no label.

1

31

 

AHA

High temperature Alarm 

threshold

oF

 Disabled;

-99.9 ÷ +999°C/°F.

oF

32

 

ALA

Low temperature Alarm 

threshold

oF

 Disabled;

-99.9 ÷ +999°C/°F

oF

33

 

AAd

Temperature Alarms 

Differential

0.0 ÷ 30.0°C/°F

1.0

34

 

AAt

Temperature Alarms Delay

oF

 Disabled;

-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).

oF

35

 

APA

Temperature Alarms delay 

at power ON

oF

 Disabled;

-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).

2.00

36

 

AdA

Temperature Alarms delay 

and unlock display delay 

after defrost

oF

 Disabled;

-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).

1.00

37

 

AoA

Open Door Alarm Delay

oF

 Disabled;

-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).

3.00

38

 

obu

Buzzer function mode

oF

  Function disabled;

1

 

Active for alarms only;

2

 

Active for key pressed only;

3

 

Active for alarms and key pressed.

3.00

39

 

tUF

/

 Key Function

oF

  No function;

1

  Do not use;

2

  ECO Mode selection;

3

  Switch ON/Switch OFF (Stand-by);

4

  Do not use.

oF

40

 

tFb

/Aux Key Function

oF

41

 

tLo

Keyboard lock function 

delay

oF

 Disabled;

-1 ÷ -59 (s) ÷ 1 ÷ 30 (min).

oF

42

 

tEd

Set Point visibility with 

 

key fast procedure

0

 None;

1

 SP;

2

 SPE;

3

 

SP and SPE;

4

 

Active SP;

5, 6

  Do not use.

1

43

 

tPP

Password to Access 

Parameter functions

oF

 Disabled;

001 ÷ 999.

oF

Содержание e31 Series

Страница 1: ...ypically used in cooling ap plications with ON OFF temperature control and defrost control with intervals time by stopping compressor The instrument has 1 relay output and 2 NTC temperature probes inp...

Страница 2: ...PROGRAMMING 2 1 Fast Set point programming The normal mode to program the setpoint is done by mo mentarily pressing the key the display shows SP or SPE alternated to the programmed value To change it...

Страница 3: ...is protected If the dp LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and keeping it pressed also press the button The...

Страница 4: ...d also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for flush in panel mounting Mak...

Страница 5: ...ternal Buzzer SPST NO NO NO C SPDT NO NO NC C 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different condi tions ON Means that the controller uses the control function...

Страница 6: ...The digital input function is defined using the iFi parameter and the action is delayed for the time programmed with pa rameter iti The iFi parameter can be configured for the following functions 0 D...

Страница 7: ...n All these functions are disabled if the relative parameters are set to OFF oF 5 7 Defrost control The automatic defrost control is made with the stopping compressor method it occurs by interval time...

Страница 8: ...rms delay activation time Tempera ture alarms are enabled at the end of the exclusion times and are activated after the AAt time when the temperature measured by the probe exceeds or goes below the re...

Страница 9: ...ent are being supplied directly or through the key AC supply Supply adapter 12 VDC Power supply Enter PWS 12 V A B C TTL USB to PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info please...

Страница 10: ...Do not use HC Do not use C3 Do not use C 21 ddL Display Lock during defrost oF Not active on Active at last measure Lb Active with label dEF during defrost and PdF at defrost oF 22 dcd Defrost activat...

Страница 11: ...scon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characte...

Страница 12: ...2 50 C 90 C with probe NTC 103AT11 11 HOW TO ORDER a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Relay output SPST NO 30A AC1 resistive load R Relay output SPST NO 16A AC1 resist...

Отзывы: