Ascon Tecnologic - e31- - OPERATING INSTRUCTIONS - PAG. 10
7. PROGRAMMABLE PARAMETERS TABLE
Here below is a description of all the parameters available
on the instrument. Some of them may not be present, either
due to the fact they depend on the type of instrument or be-
cause they are automatically disabled as unnecessary.
Parameter
Description
Range
Def. Note
1
SLS
Minimum Set Point
-99.9 ÷ HS
-50.0
2
SHS
Maximum Set Point
LS ÷ 999
99.9
3
SP
Set Point
LS ÷ HS
0.0
4
SPE
Set Point Eco
SP ÷ SHS
0.0
5
iuP
Unit of measurement and
resolution (decimal point)
C0
°C, resolution 1°;
F0
°F, resolution 1°;
C1
°C, resolution 0.1°;
F1
°F, resolution 0.1°.
C1
6
iFt
Measurement filter
oF
Filter disabled;
0.1 ÷ 20.0 s
2.0
7
iC1
Pr1 Probe Calibration
-30.0 ÷ +30.0°C/°F
0.0
8
iC2
Pr2 Probe Calibration
-30.0 ÷ +30.0°C/°F
0.0
9
iCU
Display offset
-30.0 ÷ +30.0°C/°F
0.0
10
iP2
Input Pr2 usage
oF
Unused;
EP
Do not use;
Au
Auxliary probe;
dG
Digital Input.
dG
11
iFi
Function and logic function-
ing of the Digital Input
(adding the “-” minus sign
the logic is inverted)
0
No function;
1, 2
Open Door;
3
Open Door with Output Lock;
4
External Alarm;
5
External alarm with output disabling;
6
Normal/Eco select;
7
On/Stand by select;
8
Do not use;
9
Defrost cycle start;
10
Defrost cycle end.
0
12
iti
Digital Input Delay
oF
Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
13
iEt
Eco Mode activation delay
at Door closed
oF
Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
14
itt
Max. time functioning in
Eco Mode
oF
Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
15
idS
Variable normally displayed
P1
Probe Pr1 measure;
P2
Probe Pr2 measure;
P3
Do not use;
Ec
Measure
Pr1
in Normal mode
+
ECO
label when in ECO mode;
SP
Set Point;
oF
Display not lit.
P1
16
rd
Differential (Hysteresis)
0.0 ÷ 30.0°C/°F
2.0
17
rEd
Differential (Hysteresis) in
ECO mode
0.0 ÷ 30.0°C/°F
2.0
18
rt1
Output activation time for
Pr1 probe error
oF
Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
19
rt2
Output deactivation time
for Pr1 probe error
oF
Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
20
rHC
Output operating mode
H
Heating;
C
Cooling;
nr
Do not use;
HC
Do not use;
C3
Do not use.
C
21
ddL
Display Lock during defrost
oF
Not active;
on
Active at last measure;
Lb
Active with label
dEF
during defrost and
at defrost.
oF
22
dcd
Defrost activation time for
continuous compressor
operating
oF
Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
23
dde
Defrost duration
oF
Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
24
ddi
Defrosting interval
oF
Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
25
dSd
Delay first defrost after
power-on
oF
Defrost at power-on;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
26
PP1
Out delay at switching-on
oF
Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
27
PP2
Out delay after switch-
ing OFF
oF
Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
28
PP3
Delay between two output
switching-ON
oF
Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
Parameter
Description
Range
Def. Note
29
Pod
Output delay at power ON
oF
Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
30
AAy
Temperature Alarm 1 type
1
Absolute for
Pr1
with label
Hi
-
Lo
;
2
Relative to Pr1 with label
Hi
-
Lo
;
3
Absolute for
Au
with label
Hi
-
Lo
;
4
Relative to
Au
with label
Hi
-
Lo
;
5
Absolute for
Pr1
with no label;
6
Relative to
Pr1
with no label;
7
Absolute for
Au
with no label;
8
Relative to
Au
with no label.
1
31
AHA
High temperature Alarm
threshold
oF
Disabled;
-99.9 ÷ +999°C/°F.
oF
32
ALA
Low temperature Alarm
threshold
oF
Disabled;
-99.9 ÷ +999°C/°F
oF
33
AAd
Temperature Alarms
Differential
0.0 ÷ 30.0°C/°F
1.0
34
AAt
Temperature Alarms Delay
oF
Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
35
APA
Temperature Alarms delay
at power ON
oF
Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
2.00
36
AdA
Temperature Alarms delay
and unlock display delay
after defrost
oF
Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
1.00
37
AoA
Open Door Alarm Delay
oF
Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
3.00
38
obu
Buzzer function mode
oF
Function disabled;
1
Active for alarms only;
2
Active for key pressed only;
3
Active for alarms and key pressed.
3.00
39
tUF
/
Key Function
oF
No function;
1
Do not use;
2
ECO Mode selection;
3
Switch ON/Switch OFF (Stand-by);
4
Do not use.
oF
40
tFb
/Aux Key Function
oF
41
tLo
Keyboard lock function
delay
oF
Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 30 (min).
oF
42
tEd
Set Point visibility with
key fast procedure
0
None;
1
SP;
2
SPE;
3
SP and SPE;
4
Active SP;
5, 6
Do not use.
1
43
tPP
Password to Access
Parameter functions
oF
Disabled;
001 ÷ 999.
oF