INSTALLATION
IM14229-5
GB
1) The valve must only be supplied with 24V DC ±10% and a max. ripple of 10% (no supply via diode bridge). Overvolt-
age or a ripple rate exceeding these tolerances can damage the electronics.
2) The max. current at the digital output is 200 mA/4.8W (PNP output). The output is protected against short circuit and
overload.
3) If a relay (inductive load) is connected to the pressure switch output, a freewheel diode or a varistor must be used.
4) A shielded cable must be used for protection against interference and EMC.
5) The valve body must be grounded with the earthing terminal PE (dia. M4)
2.
ELECTRICAL CONNECTION
CONNECTOR PINNING / CABLE WIRING
1
2
3
5
4
5-pin M12 female connector
250 Ohm
at current
setpoint
Valve
M12 connector
+24V supply voltage
Supply voltage GND
Setpoint GND
(only for 6-wire cable)
Setpoint
0-10V
(or 0-20 / 4-20mA)
Feedback
0-10V
(or 0-20 / 4-20mA)
Control
Analog output:
Only at current output:
max. 500 ohm
PNP when setpoint is reached
(setpoint=feedback)
Shield
=200mA max./4.8W
Inductive
load
M4 connection
on valve body
Connector housing
Digital output:
❉
A 6-wire cable with separate analog ground is used for cable lengths over 2 m to set off the voltage
drop for the setpoint.
Pin
Description
5-wire cable
6-wire cable
1
24V voltage supply
brown
brown
2
Analog setpoint input
white
white
3
Supply ground
blue
green
Analog ground
❉
yellow
4
Analog output (feedback)
black
pink
5
Digital output (pressure switch)
grey
grey
Body
EMC screen
shield
shield