ASCO 4ATE, 4ACTE, 4ADTE, 4NTE, 4NCTE, 4NDTE
Installation Manual
Page 4
ASCO Power Technologies
381333-445 B
Engine Starting Contacts
All customer connections, including the engine control contact
connections, are located on terminal block TB which is
mounted on the top right side of the enclosure. Refer to the
wiring diagram provided with this switch and connect the
engine start wires to the appropriate terminal. See Figure 1
and Table A.
Table A. Engine Start Connections.
When normal
source fails
Terminals on
terminal block TB
contact closes
TB1 and TB2
contact opens
TB1 and TB3
NOTE
: To temporarily disable engine control from the
automatic transfer switch you can unplug J3 from the
small P3 receptacle at the bottom of the assembly. Be
sure to reconnect plug J3 to the P3 receptacle for
automatic transfer switch operation.
Figure 1. Engine start & auxiliary circuit TB