Asco J 4000 Series Скачать руководство пользователя страница 18

ASCO 4ATE, 4ACTE, 4ADTE, 4NTE, 4NCTE, 4NDTE 

 

Installation Manual 

Page 18 

ASCO Power Technologies 

381333-445 B 

Troubleshooting 

 

Check in Numerical Sequence 

1 Operation

2 Generator

3 Voltage

For 4ATE, 4ACTE, 4ADTE the 
engine-generator set does not start 
when the transfer test button is 
pressed or when the Normal 
source fails. 

The outage must be long 
enough to allow for the feature 
1C time delay plus engine 
cranking and starting time. 

Starting control must be in 
automatic position.  Batteries 
must be charged and connected.  
Check wiring to the engine 
starting contacts.

For 4ATE, 4ACTE, 4ADTE the 
transfer switch does not transfer 
the load to the emergency source 
after the gen-set starts. 

Wait for the feature 2B time 
delay. For immediate transfer, 
press the transfer button 
(bypass timer).  If inphase 
transfer is active, wait for 
inphase condition. For 4NTE, 
4NCTE, 4NDTE press the 
transfer button. 

Is the generator accepted light 
on?  Generator output circuit 
breaker must be closed.  
Generator frequency must be 
correct. 

Refer to Group 
H controller 
User’s Guide 
381333-444 for 
voltage 
settings.  

For 4ATE, 4ACTE, 4ADTE the 
transfer switch does not transfer 
the load to normal source when 
normal returns or after transfer 
test. 

Wait for the feature 3A time 
delay. For immediate 
retransfer, press the transfer 
button (bypass timer).  If 
inphase transfer is active, wait 
for inphase condition. For 
4NTE, 4NCTE, 4NDTE press 
the transfer button.

Refer to Group 
H controller 
User’s Guide 
381333-444 for 
voltage 
settings. 

For 4ATE, 4ACTE, 4ADTE the 
generator does not stop after load 
retransfer to the normal source. 

Wait for the feature 2E delay. 
The 

Engine Control

 switch 

must be in the 

Auto

 position. 

Starting control must be in 
automatic position. 

For 4ATE, 4ACTE, 4ADTE the load 
is deenergized (off). 

 Load 

Disconnect Timer

 on display. 

Wait for the delayed-transition 
transfer timer. See the Group 
H User’s Guide 381333-444.

 - 

 

Group H controller 

Not in Auto light is always on. 

For 4NTE, 4NCTE, 4NDTE 
this light is always on, 
indicating it is a manual 
transfer switch. 

- - 

 

Group H controller Alert light is on. 

Read the display for more 
information.  Refer to  
User’s Guide 381333-444. 

- - 

 

Bypass-Isolation controller 

Not in Auto light is flashing. 

The ATS is not in an 
automatic operation mode 
because it is bypassed or 
isolated (not connected). 

The light will go off when the ATS 
is connected and un-bypassed. 

 

 

Bypass-Isolation controller 

alarm light is flashing. 

Alarm condition (1 flash a 
second) 
Diagnostic mode (5 flashes a 
sec.) 

 

 

Содержание J 4000 Series

Страница 1: ...ickup and dropout settings and adjustments Rating Label Each transfer switch contains a rating label to define the loads and fault circuit withstand closing ratings Refer to the label on the transfer switch for specific values Do not exceed the values on the rating label Exceeding the rating can cause person injury or serious equipment damage An experienced licensed electrician must install the sw...

Страница 2: ... secure P type 4X secure 304 stainless steel V type 4X secure 316 stainless steel Q type 12 secure Nameplate Catalog Number Identification The nameplate includes data for each specific 4000 Series transfer switch Use the switch only within the limits shown on this nameplate A typical Catalog Number is shown below with its elements explained Typical 4000 Series J4ATE catalog no for switched neutral...

Страница 3: ...h the National Electrical Code and local codes De energize the cables before making any line or auxiliary circuit connections Be sure that the Normal and Emergency line connections are in proper phase rotation Place the engine generator starting control in the OFF position Make sure engine generator is not in operation Testing Power Cables Do not connect the power cables to the transfer switch unt...

Страница 4: ...th this switch and connect the engine start wires to the appropriate terminal See Figure 1 and Table A Table A Engine Start Connections When normal source fails Terminals on terminal block TB contact closes TB1 and TB2 contact opens TB1 and TB3 NOTE To temporarily disable engine control from the automatic transfer switch you can unplug J3 from the small P3 receptacle at the bottom of the assembly ...

Страница 5: ...plate Also see User s Guide 381333 444 for voltage settings in the Group H controller Use extreme caution when using a meter to measure voltages in the following steps Do not touch power terminals shock burns or death could result 1 Close the normal source circuit breaker The normal source accepted and the load on normal lights should come on 2 Use an accurate voltmeter to check phase to phase and...

Страница 6: ...ed light is on 2 Press the transfer button The engine should start and run within 15 seconds For 4NTE 4NCTE 4NDTE the generator must be started manually at the generator The emergency source accepted light should come on 3 The transfer switch should transfer to the emergency position The load on emergency light should come on and the load on normal light should go off For 4NTE 4NCTE 4NDTE press th...

Страница 7: ...turned to TEST CONN or ISO Alarm Blinks yellow when an alarm condition is present Not in Auto Blinks yellow when the ATS is not in an automatic operation mode bypassed or rack not connected Allowable Positions of the Bypass Switch in relation to Positions of the Transfer Switch If Transfer Switch is Connected and in this position Bypass Switch can be in either Normal open Normal Emergency open Eme...

Страница 8: ...ass to the Normal Source When ATS is connected to Normal Source 1 Press and hold the Bypass to Normal button until the Bypassed to Normal light comes on Figure 5 Bypass to Normal button Figure 6 Bypass to Normal diagram Figure 7 Bypassed to Normal light Bypass to the Emergency Source When ATS is connected to Emergency Source 1 Press and hold the Bypass to Emergency button until the Bypassed to Eme...

Страница 9: ...e ATS on pages 7 8 2 Turn the Connection Isolation Handle counter clockwise about 9 10 turns until the window shows TEST The TEST light comes on The ATS can be tested operated now without load interruption see page 6 Figure 11 CONNECTED to TEST position Figure 12 The TEST light will illuminate Figure 13 Connection Isolation Handle turned to the TEST position NOTE In the TEST position the transfer ...

Страница 10: ...ls 3 Continue turning the Connection Isolation Handle counterclockwise approximately 5 6 turns until window shows ISOLATE The ISOLATED light comes on Figure 14 TEST to ISOLATE position Figure 15 The ISOLATED light will illuminate Figure 16 Connection Isolation Handle turned to the ISOLATE position continued on next page counterclockwise draws out the transfer switch Turn crank counter clockwise un...

Страница 11: ...mended Contact Inspection Contact condition should be checked annually Discoloration is normal Do not file contacts Instead use light emery paper to clean up the contact surfaces The non replaceable main contacts are designed to last the life of the transfer switch To prevent the possibility of fatal electrical shocks and burns bypass isolate and withdraw the transfer switch before working on it 1...

Страница 12: ... side rails and close the enclosure door Figure 19 Push in the isolated transfer switch Close enclosure door to prevent personal injury 2 Turn the Connection Isolation Handle clockwise approx 5 turns until the window shows TEST The TEST light comes on Figure 20 ISOLATE to TEST position Figure 21 The TEST light will illuminate Figure 22 Connection Isolation Handle turned to the TEST position 3 The ...

Страница 13: ...ncy light should come on If Feature 2B time delay is used there will be a delay before transfer to Emergency NOTE With Normal available the ATS will not stay in the emergency position unless Feature 3A time delay is used at least 30 seconds Solenoid interlock prevents you from closing the isolation contacts until the ATS is in the same position as the Bypass Switch 6 When the transfer switch is in...

Страница 14: ...t in Automatic light will turn off ATS is connected to Emergency Source 1 Press and hold the Unbypass button until the Bypassed to Emergency light goes off Figure 29 Unbypass to Emergency button Figure 30 Unbypass Emergency diagram Figure 31 Bypassed to Emergency light off The Not in Automatic light will turn off The Bypass Switch opens its normal contacts The Bypass Switch opens its emergency con...

Страница 15: ... up according to manufacturer s guidelines Manual Engine Start Active light is on Emergency Available light comes on 2 Press and hold the Bypass to Emergency button You will hear the Bypass Switch operate twice first open then close on emergency source Bypassed to Normal light goes off Bypassed to Emergency light comes on To Transfer the Load to Normal Source Normal Available light is on Bypassed ...

Страница 16: ...rts provide the Serial No Bill of Material No BOM and Catalog No from the transfer switch nameplate In the US call 800 800 2726 ASCO or contact customercare ascopower com Yearly Inspection Hazardous voltage capable of causing shock burns or death Deenergize both Normal Emergency power sources before performing inspections Clean the enclosure Deenergize all sources then brush and vacuum away any ex...

Страница 17: ...e of the operator of the transfer switch See Figures 33 34 35 and Table C 2 Move the maintenance handle up or down as shown to manually operate the transfer switch Operate both upper and lower contact shafts Observe the window indicators right side Remove the maintenance handle and store it on the lower left side NOTE If Normal and Emergency connections are reversed this operation is also reversed...

Страница 18: ...ansfer the load to normal source when normal returns or after transfer test Wait for the feature 3A time delay For immediate retransfer press the transfer button bypass timer If inphase transfer is active wait for inphase condition For 4NTE 4NCTE 4NDTE press the transfer button Refer to Group H controller User s Guide 381333 444 for voltage settings For 4ATE 4ACTE 4ADTE the generator does not stop...

Страница 19: ...sed to Normal light does not come on Is the Bypass Restricted light flashing Check that the Connection Isolation Handle is not between the TEST and CONN positions It should be in the CONN position The Connected light should be on The Bypass to Normal button does not operate the bypass switch The Bypassed to Normal light does not come on Is the Bypass Restricted light is on solid not flashing Is th...

Страница 20: ...0 12 13 HELP 800 800 2726 ASCO customercare ascopower com I inphase transfer feature 6 18 inspection 11 12 16 ISOLATE position 10 isolated light 7 10 15 installation 3 4 Isolation Connection Handle 2 9 10 12 13 L lamp test button 7 16 lights 5 7 10 12 15 17 18 line connections 3 Load Energized 7 load on emergency light 5 6 load on normal light 5 6 lubrication 16 M maintenance 11 17 maintenance han...

Отзывы: