© 2020 ASCO Power Technologies. All Rights Reserved
9
IO-70071
01/2020
For access to self-service tools and chat support visit se.com/us/en/work/support or call 1-888-778-2733 for technical assistance
ASCO Model 950 Surge Protective Device (SPD) and Fuse Box
Grounding and Bonding
System Grounding and Bonding
Environmental Specifications
SPD Component Specifications
Fuse Box Component
Specifications
Storage Environment
Equipment Performance
Unpacking & Preliminary
Inspection
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Medium voltage systems are ungrounded. Ungrounded systems are
inherently unstable and can produce excessively high line-to-ground
voltages during certain conditions. During these conditions, any elec-
trical equipment including an SPD may be subjected to voltages which
exceed their design ratings. This information is being provided to the
user so that an informed decision can be made before installing any
electrical equipment on an ungrounded power system.
Failure to follow these instructions will result in death or serious injury.
Inspect the entire shipping container for damage or signs of mishandling.
Remove the packing materials and further inspect the unit for any obvious
shipping damages.
If any damage was found and is a result of shipping or handling, immediately
file a claim with the shipping company and forward a copy to ASCO.
Relative Humidity Range: 0 - 95% Non-condensing
Operating Frequency: 50, 60Hz
Operating Temperature: -40°F (-40°C) to +185°F (+85°C)
NEMA 4 (IP66) Heavy Gauge Steel Enclosure Standard
Standard Size: 12 x 12 x 6 in. (305 x 305 x 152 mm.)
Weight: 65 lbs. (29.5 kg.) to 75 lbs. (34.5 kg.)
NEMA 4X Polycarbonate with Stainless Steel Lockable Latches
Standard Size: 18” x 16” x 10” (457mm x 406mm x 254mm)
Weight: 35 lbs. (15.9kg)
Store unit in a clean, dry environment. Storage temperature range is -40°F
(-40°C) to +185°F (+85°C). Avoid exposure to high condensation.
To obtain optimum surge suppression, locate the SPD as close as possible
to the circuitry being surge-limited to minimize the wire length. Minimizing
the wire length reduces the impedance between the circuitry and the SPD.
Refer to the Voltage Protection Rating (VPR) values on the SPD nameplate.
These VPR values were obtained by testing the SPD with six-inch long
leads (per UL1449). For every additional foot of wire beyond six inches, the
effective VPR increases by approximately 160 volts.
DANGER