900 SERIES
Surge Protective Device
ASCO Model 950 Surge Protective Device (SPD) and Fuse Box
Operation
Figure 4:
Component Optional Monitoring Mechanical Drawings (Dimensions - in.)
Maintenance
Troubleshooting and Service
Operation
Model 950 requires minimal maintenance. We recommend periodic
inspection of fuses during any scheduled shutdown periods. Keep the SPD
free of dirt and debris.
The ASCO 950 surge protector has little to troubleshoot. Only a
nonfunctional SPD will open the fuses. Opened fuses should be replaced
with the same make, model and amperage. Do not replace with fuses
under 15A, due to the possibility of inadvertent nuisance tripping. Do NOT
replace opened fuses with ones rated 200A and higher as this will not
properly disconnect the SPD from the electrical system. If a fuse is opened
or a service condition is believed to exist please contact ASCO Power
Technologies.
For application questions, chat support is available at:
se.com/us/en/work/support or call 1-888-778-2733 for technical assistance
Model 950 does not have operational indicators. When an upstream
overcurrent protection fuse within the fuse box opens, the SPD should be
evaluated for proper operation.
Front View
Side View