Chapter 2 Installation And Operation 13
ASCO Series 230 C2ADTL Transfer Switch User Manual
Punch out the small
holes, Then insert
cable clamp
Figure 2-10 Schematic Diagram for Cable Routing
5. Auxiliary Contact Specifications:
a) Ratings:
Rated thermal
current
Ith /A
Rated insulation
voltage
V
Rated impulse withstand
voltage
Uimp/kV
Protection class
of enclosure
Pollution
degree
Maximum cable
cross section
16
690
4
IP20
3
2.5mm
2
b) Additional Information:
AC-15
DC-12
DC-13
U
e
/ V
I
e
/ A
U
e
/ V
I
e
/ A
P / W
I
e
/ A
P / W
230
6
24
10
240
2
48
400
4
72
4
288
0.8
58
690
2
125
2
250
0.55
69
250
0.55
138
0.27
68
CAUTION
!
In order to obtain
higher reliability
, the auxiliary contact circuit should meet the requirments: Current
≥
5mA