            Chapter 2 Installation And Operation   

ASCO Series 230 C2ADTL Transfer Switch User Manual 

2)    Remove all label covers on the arc chamber: A/B/C/N.    Insert the first pole partition between two arc chambers 

with the gap facing DOWN and insert another pole partition with the gap facing upward. Repeat for each slot 

between each pole. When finished, snap each label cover back into its 

original position

. Make sure that the 

correct label (LINE versus LOAD) is showing on the correct side. See Figure 2-4 for more details. 

 

Gap

Gap

Gap

Gap

A

B

C

N

Line Side

Load Side

Line Side

Label Cover

 

Figure 2-4    Pole Partition Installation   

     CAUTION

 

1. The gap in the pole partition is used to make room for the label covers and the base of the switch.    If the gap is inserted in the 

wrong direction, the label cover will not be able to be snapped back into position correctly. 

2. Make sure that the correct label (LINE versus LOAD) is showing on the correct side AND make sure that the corresponding 

phase labels on the cover (A/B/C/N) are in their correct positions as well with A Phase being closest to the main gear driver box 

area.     

 

3. Auxiliary Contacts (Optional Accessory) 

There are many different optional auxiliary contact configurations available for the C2ADTL TS unit, See the Figure 

2-5 below for what options exists. 

132AA

x1

x1

132AB

x2

x1

132AC

x2

x2

132B

x1

132BB

x2

x1

132BC

x2

x2

132CA

x1

x1

132CB

x2

x1

132CC

x2

x2

132C

x1

x1

132A

132BA

x1

x1

 

Down 

Содержание C2ADTL

Страница 1: ...may contact the nearest ASCO Power Technologies sales office or service center Copyright 2018 by ASCO Power Technologies All rights reserved The contents in this document are subject to change without notice ASCO Power Technologies Address 160 Park Avenue Florham Park NJ 07932 1049 USA Website www ascopower com Customer Service Hotline 800 800 ASCO E mail customercare asco com ...

Страница 2: ......

Страница 3: ...Description 4 1 5 Application Environment 4 1 6 Technical Parameters 5 Chapter 2 Installation And Operation 6 2 1 Installation 7 2 1 1 Installation of Transfer Switch 7 2 1 2 Accessory Installation 8 2 2 Operation 14 2 2 1 Manual Operation 14 2 2 2 Auto Operation 15 2 2 3 Padlock 15 Chapter 3 Maintenance and Troubleshooting 17 3 1 Start Up Function Test 17 3 2 Maintenance 19 3 3 Common Troubleshoo...

Страница 4: ......

Страница 5: ...n C2ADTL B3 0250 H E 0 0 Description Series 230 C2ADTL Automatic Transfer Switch C2ADTL Series 230 C2ADTL Automatic Transfer Switch Center off three position design Number of Poles Configuration B1 2 Poles Sigle Phase 220V 240V 2 Wire with Neutral Line 02 2 Poles Two Phase 220V 240V 2 Wire without Neutral Line B2 3 Poles Two Phase 220V 240V 3 Wire with Neutral Line 03 3 Poles Three Phase 380V 415V...

Страница 6: ...he auxiliary contacts can be used to indicate positions with the CLOSE contact see Schematic 1 132D 132F The auxiliary contacts can be used to indicate positions with the OPEN contact see Schematic 2 Schematic 1 132A 132C Diagram Schematic 2 132D 132F Diagram 132 A A Auxiliary Contact Function Code Position of The transfer switch Auxiliary Contact Function Code Position of The transfer switch Auxi...

Страница 7: ... Partition LIP1F0250 63121523 4 pcs 8 pcs 12 pcs Handle LHS3F 21502245 1 pcs 1 pcs 1 pcs Connection Cable Power Cable Signal Cable 04119032 1 set 1 set 1 set Fuse 0215 500MXP UDA 500 19040344 2 pcs 2 pcs 2 pcs User Manual Series 230 C2ADTL Transfer Switch User Manual 31012691 1 copy 1 copy 1 copy The following accessories are included as optional in the Series 230 C2ADTL automatic transfer switch ...

Страница 8: ... to 40 C Humidity Within 95 No condensation Pollution Class Class III Mounting Method Horizontal or Vertical Product Standards Met EN60947 6 1 and IEC60947 6 1 Environmental Standards Met RoHS and WEEE Fuse Auto Manual Toggle Switch Padlock Pull Tab Source II Load Side Source I Load Side Operating Handle Hole Source I Line Side Arc Chamber Auxiliary Contact Mounting Positions Label Cover Nameplate...

Страница 9: ...es 380 400 415 3 poles 4 poles Operating Voltage Range V Ue 220 230 240 380 400 0 7 1 2 Ue Ue 415 0 7 1 15 Ue Ue 208 0 75 1 2 Ue Utilization Category AC 33B Rated Insulation Voltage Ui V 800 Rated Impulse Withstand Voltage Uimp kV 12 Rated Short time Making Capacity Icm peak kA 31 5 Rated Short circuit Withstand Current Icw kA 0 1s 15 Rated Conditional Short circuit Current Iq rms kA 200 FUSE 150 ...

Страница 10: ...UTION is used in this manual to warn of a hazardous situation which if not avoided could result in minor or moderate injury NOTICE NOTICE is used in this manual to comments or suggestion of a fault situation which if not avoided could result in fault An experienced licensed electrician must install the ATS Each automatic transfer switch contains a rating label Name plate to define the loads Ampere...

Страница 11: ...install Class C Surge Protection Devices when using automatic transfer switches and the right wiring methods See Appendix 1 Surge Protection Device for additional details and recommended wiring methods 3 Isolation function The C2ADTL transfer switch is not suitable for isolation and a switch disconnector must be installed when isolation function is needed 2 1 1 Installation of Transfer Switch Inst...

Страница 12: ... bridging busbar between the Source I load side terminal and the Source II load side terminal with the long center plate of bridging busbar against the arc chamber wall surface 3 Fix the bridging busbar with M10 30 terminal screws included with the package Bridging busbar Bridging busbar Load Connection busbar Source I Connection busbar Source II Connection busbar Load Side Line Side Bolt assembly...

Страница 13: ...Chapter 2 Installation And Operation 9 ASCO Series 230 C2ADTL Transfer Switch User Manual Gap Figure 2 3 Pole Partition ...

Страница 14: ...n CAUTION 1 The gap in the pole partition is used to make room for the label covers and the base of the switch If the gap is inserted in the wrong direction the label cover will not be able to be snapped back into position correctly 2 Make sure that the correct label LINE versus LOAD is showing on the correct side AND make sure that the corresponding phase labels on the cover A B C N are in their ...

Страница 15: ...tact Order Code and Installation The Auxiliary Contact Locations are shown in Figure 2 6 Location I Auxiliary Contact Mounting Location II Auxiliary Contact Mounting Figure 2 6 Auxiliary Contact Location Definition The installation procedures are as follows 1 With the auxiliary contact screw holes facing outward snap the 4 claws into the corresponding 4 holes on the transfer switch side plate and ...

Страница 16: ... Figure 2 8 Auxiliary Contact Installation on Top of Another Contact NOTICE 1 The center sticker on the auxiliary contact that is in direct contact with the side plate must be removed before installation of the additional auxilary contact on top of it 2 Keep the center sticker on the outer most auxiliary contact in place to avoid any debris or dust from getting inside 3 The maximum auxiliary conta...

Страница 17: ...ent Ith A Rated insulation voltage V Rated impulse withstand voltage Uimp kV Protection class of enclosure Pollution degree Maximum cable cross section 16 690 4 IP20 3 2 5mm2 b Additional Information AC 15 DC 12 DC 13 Ue V Ie A Ue V Ie A P W Ie A P W 230 6 24 10 240 2 48 400 4 72 4 288 0 8 58 690 2 125 2 250 0 55 69 250 0 55 138 0 27 68 CAUTION In order to obtain higher reliability the auxiliary c...

Страница 18: ... the position has successfully switched to Position II 2 When the window initially displays I Normal Source do the following operations as needed If you need to switch it to the Position OFF Center Off Position rotate the handle 90 degrees clockwise After hearing a click and the window displays OFF it indicates that the position has successfully switched to Position OFF If you need to switch it to...

Страница 19: ... Make sure toggle switch lines up with the correct indication position mark 3 Once auto manual toggle switch is in the AUTO Position the switch will automatically transfer to the position that is currently set in the controller For a description of how to set the positions in the controller refer to the Series 230 C1000 Controller User Manual or Series 230 C2000 Controller User Manual WARNING 1 If...

Страница 20: ...ansfer switch to Position OFF according to the directions shown in the position indicator window CAUTION When the switch is not in OFF Position the padlock pull tab cannot be pulled in place 3 Finally pull the padlock pull tab out and lift up to expose the lock hole Then insert the proper padlock into the hole to lock it CAUTION The specified diameter of the C2ADTL transfer switch padlock must be ...

Страница 21: ...on green This should indicate your wiring is correct If using the C2000 controller Double check and measure the dual supply voltage to make sure voltages are consistent to what is indicated on the C2000 controller DANGER When measuring Voltage pay attention to not touch the terminals and copper bars otherwise it could result in death or serious injury 3 To Test Electric Operation This is used to t...

Страница 22: ... II If the switch is in Location I scrolling the menu to X I and press Enter the switch will not tranfer 2 Return To The Original Control Mode After completing the electric operation test you can return to the original control mode by using the menu settings Using C1000 Controller 1 According to The 230 Series Automatic Transfer Switch C1000 Intelligent Controller User Manual the DIP 7 8 is set to...

Страница 23: ... AUTO Position Check to make sure the handle has been removed from the handle hole Check to make sure the padlock pull tab has been pushed all the way down to the original unlocked position The padlock pull tab cannot be pulled up Check if OFF is displayed in the position indicator window Check to make sure the auto manual toggle switch is in MANUAL Position For all other issues please contact Eme...

Страница 24: ...ator turns red 2 The SPD remote signal contact becomes an open circuit 7 The Wiring method show in Appended Figure 3 is forbidden If SPD is wired similar to Appended Figure 3 the wiring needs to be modified to Appended Figure 1 or Appended Figure 2 Source I Source II MCB or Fuse Class C Surge Protection Device Surge Protection Device Wiring from Main Circuit to Grand lenth 0 5m Connection Wiring L...

Страница 25: ...Appendix 1 21 ASCO Series 230 C2ADTL Transfer Switch User Manual Appendix 2 Glossary ATS Automatic Transfer Switch NC Normally Closed NO Normally Open ...

Отзывы: