Gree GMV6 DC Inverter VRF Units Service Manual
97
Yes
"d4" Inlet Pi pe Tempe ratu re
Sen sor Fault
Remove the foreign
matters and plug it tightly
The detection circuit may
ope rate impro perly
Yes
Replace th e main control
boa rd
No
Is th e p roblem so lve d after
the inlet pi pe temper atu re sensor
is re placed?
Whether th e i nter face
terminal between the main boa rd
and inl et pipe temperature sensor gets loose
or contains foreig n matters?
No
2.46 "d5" Middle Part Temperature Sensor Fault (Reserved)
2.47 "d6" Outlet Pipe Temperature Sensor Fault
Fault display:
wired controller of indoor unit and receiver of indoor unit display
Fault diagnosis:
The temperature sensor detection circuit samples the AD value of temperature sensor and
determines the range of AD value. When the sampled AD value exceeds the limits for 5 consecutive
seconds, the fault is generated.
Possible causes:
■ Poor contact between the outlet pipe temperature sensor and the main board interface;
■ Abnormal outlet pipe temperature sensor;
■ Abnormal detection circuit.
Troubleshooting: