Gree GMV6 DC Inverter VRF Units Service Manual
139
2.93 "J2" Compressor 2 Over-current Protection
Fault display:
main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
When the operating current of the compressor detected by the current sensor or circuit exceeds the
limit, the unit will stop working.
Possible causes:
■ The unit's parameters are abnormal;
■ The drive module is abnormal;
■ The compressor is abnormal.
Troubleshooting:
"J2" Compressor 2
Over-current Protection
The co mpr essor is
abn ormal
Yes
Yes
Replace th e compre ssor
No
Replace th e d rive modu le
If th e h igh pressu re valu e o f
the unit is still above 60°C when the compre ssor
runs at the lowest fre quency, the compre ssor may ha ve ena bled
normal over-current protection. In this case, check whether th e fan
ope rate s prop erly an d whe ther the ambient temper atu re i s normal
and whether the power sup ply is n ormal
(320V-460V)
Power on aga in the units
based on the cap aci ty a nd number of
indo or units enab led previously in the
case of protection state
Whether th e d rive modu le i s normal?
Yes
Yes
Is th e p rotection still occurring
afte r po we r-on?
Yes
Содержание AMV6
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM H X GMV 450WM H X Circuit diagram Physical position...
Страница 238: ...Gree GMV6 DC Inverter VRF Units Service Manual 236 High pressure sensor Low pressure sensor...
Страница 297: ...Gree GMV6 DC Inverter VRF Units Service Manual 295 GMV 400WM H X GMV 450WM H X...
Страница 300: ...Gree GMV6 DC Inverter VRF Units Service Manual 298 System principle diagram of GMV 400WM H X GMV 450WM H X...
Страница 303: ...JF00304228...