Gree GMV6 DC Inverter VRF Units Service Manual
168
"PH" Over Voltage
Pro tection for the DC Bus
of Compre ssor Drive r
The co mpr essor drive
boa rd o perates impr operly
Yes
Whether th e i nput voltage of the
unit excee ds 460V?
No
Replace th e compre ssor
drive boar d
Yes
Chang e the volta ge to
380V
2.136 "PL" Under Voltage Protection for DC Bus of Compressor
Drive
Fault display:
main board of outdoor unit displays
Applicable models: GMV6, GMV5, GMV5S series
Fault diagnosis:
When the input power cable of the main board has a voltage below 320 V, the unit triggers
protection against faults.
Possible causes:
■ The unit's input power cable has a vo
ltage below 320V;
■ The compressor drive board operates improperly.
Troubleshooting:
"PL" Under Vol tage
Pro tection for the DC Bus
of Compre ssor Drive r
The co mpr essor drive
boa rd o perates impr operly
Yes
Whether th e i nput voltage of the
unit fall s below 320V?
No
Replace th e compre ssor
drive boar d
Yes
Chang e the volta ge to
380V
2.137 "PJ" Inverter Compressor Startup Failure
Fault display:
main board of outdoor unit displays
Fault diagnosis:
Содержание AMV6
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM H X GMV 450WM H X Circuit diagram Physical position...
Страница 238: ...Gree GMV6 DC Inverter VRF Units Service Manual 236 High pressure sensor Low pressure sensor...
Страница 297: ...Gree GMV6 DC Inverter VRF Units Service Manual 295 GMV 400WM H X GMV 450WM H X...
Страница 300: ...Gree GMV6 DC Inverter VRF Units Service Manual 298 System principle diagram of GMV 400WM H X GMV 450WM H X...
Страница 303: ...JF00304228...