Issue December 2017 

5 / 7 

8.

 

Installation instructions 

General 

 

Installation of explosion-safe equipment such as this product must be carried out by personnel specially trained 

and qualified to do this, following the relevant requirements of the installation standard EN 60079-14. 

 

For the installation and use of this product the relevant safety regulations and also the generally recognized latest 

state of the technology apply. Also follow the national regulations and legal requirements relating to electrical 

connections to the electricity grid. 

 

Isolate power prior to installation. 

 

All models are fitted with a connection box with cable glands & terminals and 5m cable 

 

Follow the instructions as stated under the previous heading ‘General’. 

 

Ensure that the cable gland fits the individual cable used with respect to clamping size and type of cable. If not 

then apply a suitable cable gland and make sure that it is approved for its application. 

 

Connect an external earth wire to the external earth boss and ensure that this is sufficiently connected to 

electrical ground. 

 

The electrical power supply must be connected to the supplied power cable 

 

For connection the cable use an electrical isolating switch or a junction box which is explosion-safe in 

accordance with the classification of its environment. 

 

9.

 

Opening of the housing 

The unit contains no components that need direct access in normal operation. The following warning is marked: “The 

air conditioning unit is modified to explosion-safe meeting ATEX requirements II 3 G. No serviceable parts inside. Refer 

to qualified personnel as substitution of parts may impair the suitability for use in hazardous areas.” 

The housing may only be opened under non-hazardous safe conditions. To do this follow the instructions as described 

under the following heading ‘Repair’. 

 

10.

 

Maintenance 

For the maintenance of the AR-054 air conditioning units the requirements as stated in EN 60079-17 apply. 

If the air conditioning unit and the connection cable are no longer in good condition or are very dirty or damaged they 

must be repaired or cleaned immediately. 

The power supply to the air conditioning units must be switched off and may only be restored after the maintenance 

has been carried out and approved. 

For the advised maintenance cycles of the air conditioning unit we refer to the operation manual provided by the 

original equipment manufacturer. 

The batteries of the infra-red remote control may only be replaced by batteries of the same size and type as provided 

with the original product. 

 

11.

 

Repair 

Repairs to the AR-054 air conditioning unit may only be executed by applying original parts that are assessed, 

converted and marked by Artidor. Repairs may only be carried out by qualified skilled workers who have been trained 

in accordance with EN 60079-19. Applying of non-assessed, non-converted, non-marked parts may lead to injury to 

persons and damage to equipment. 

Содержание AR-054 series

Страница 1: ...User manual Explosion safe window air conditioning system Type series AR 054 II 3 G Ex ic nAC h IIC T3 Gc ...

Страница 2: ...it when it is damaged During installation of the air conditioning unit national safety regulations must be observed Only use the air conditioning unit under the environmental conditions for which it is specified Deviating environmental conditions can contribute to damage to the equipment and may lead to possible danger to the life of the user Do not use the air conditioning unit at temperatures de...

Страница 3: ...l covered by a non metallic hood The electronically driven fan provides air flow on both sides of the system The infra red remote control contains electronics PCB with a display and membrane pushbuttons all housed in a non metallic housing containing two 2 1 5 V DC AAA dry cell batteries The ambient temperature allowed for the apparatus is 20 C to 45 C 3 Characteristics The characteristics can be ...

Страница 4: ...N 60079 11 2012 EN 60079 15 2010 EN 80079 36 2016 and EN 80079 37 2016 Certification document Unit assessment certificate Ambient temperature 20 C to 45 C Sealed against moisture and dust IP54 according to EN 60529 Material housing inside part Sheet steel frame and non metallic cover Material housing outside part Sheet steel plating Connection H07 RN F 3 x 1 5 mm connection cable length 5 meter Ea...

Страница 5: ...g The unit contains no components that need direct access in normal operation The following warning is marked The air conditioning unit is modified to explosion safe meeting ATEX requirements II 3 G No serviceable parts inside Refer to qualified personnel as substitution of parts may impair the suitability for use in hazardous areas The housing may only be opened under non hazardous safe condition...

Страница 6: ...ive for repair If the housing is opened care must be taken of the following The housing must not be opened unless power is switched off prior to repair The housing must not be opened unless the area has been known to be non hazardous If opened the AR 054 air conditioning unit shall be dismantled in a logical sequence 12 Removal re use For processing regarding disposal or reuse of the product and i...

Страница 7: ...Manual explosion safe window air conditioning system AR 054 Issue December 2017 7 7 This document can be subject to change without notice ...

Отзывы: