Manual explosion-safe window air conditioning system AR-054
Issue December 2017
4 / 7
5.
Application
The series AR-054 explosion-safe window air conditioning units have been designed for and are suitable for use in
hazardous classified areas due to flammable gases, vapors and mist. Because they are explosion-safe and certified on
the basis of Group II Category 3 G of the ATEX directive they are suitable for use in explosion hazardous areas
classified as zone 2.
If use in special environmental conditions is required, please contact the manufacturer Artidor Explosion Safety B.V.
6.
Technical Data
Explosion safety category:
ATEX II 3 G
European directives:
2014/30/EU (EMC) and 2014/34/EU (ATEX 114)
Protection against ignition:
Ex ic nAC h IIC T3 Gc (A/C unit)
Ex ic IIC T6 Gc (remote control)
Standards applied:
EN 60079-0:2012 / A11:2013, EN 60079-11:2012, EN 60079-15:2010,
EN 80079-36:2016 and EN 80079-37:2016
Certification document:
Unit assessment certificate
Ambient temperature:
-20 ˚C to +45 ˚C
Sealed against moisture and dust:
IP54 according to EN 60529
Material housing inside part:
Sheet steel frame and non-metallic cover
Material housing outside part:
Sheet steel plating
Connection:
H07 RN-F 3 x 1,5 mm² connection cable, length 5 meter
Earth connection:
External, M6, stainless steel
7.
Marking and warning on the equipment
Labels are attached to the air conditioning AR-054 for marking purposes. The specific marking label depends on the
applicable model of the air conditioning system and will be created according to the unit assessment certificate. All
necessary warnings are marked.
Example of a window air conditioning unit label
AR-054 AIR CONDITIONER
II 3 G Ex ic nAC h IIC T3 Gc
Type: AR-054/040
230 VAC 50 Hz
Cert. ARTIDOR 17ATEX9999
1.300 Watt
TF & Serial No.: AS123456
Year: 2017
ARTIDOR Explosion Safety B.V.
Emopad 38, 5663 PB Geldrop, The Netherlands, www.artidor.com