Table 48-1.  LonWorks Variable List

49

Map Descriptor Name

Data Array 

Name

Data Array 

Offset

 Lon Function Function

Node 

Name    

SNVT Type

SNVT 

option

oFILLSTATUS

BITA

0

NVPO

Server    

Lon_1

SNVT_switch

state

oDRAINSTATUS

BITA

1

NVPO

Server    

Lon_1

SNVT_switch

state

oCON1

BITA

2

NVPO

Server    

Lon_1

SNVT_switch

state

oCON2

BITA

3

NVPO

Server    

Lon_1

SNVT_switch

state

oCON3

BITA

4

NVPO

Server    

Lon_1

SNVT_switch

state

oCON4

BITA

5

NVPO

Server    

Lon_1

SNVT_switch

state

oCOMTYPE

BITB

0

NVPO

Server    

Lon_1

SNVT_switch

state

oRH_SELECT

BITB

1

NVPO

Server    

Lon_1

SNVT_switch

state

oHL_SELECT

BITB

2

NVPO

Server    

Lon_1

SNVT_switch

state

oOUTTEM_SELECT

BITB

3

NVPO

Server    

Lon_1

SNVT_switch

state

oNETWORK_ENABLE

BITB

4

NVPO

Server    

Lon_1

SNVT_switch

state

oMOD_FILL_ENABLE

BITB

5

NVPO

Server    

Lon_1

SNVT_switch

state

oRH_REQUIRE

SINTA

0

NVPO

Server    

Lon_1

SNVT_lev_percent

-

oOUTPUT

SINTA

1

NVPO

Server    

Lon_1

SNVT_count_f

-

oWATER_LEVEL

SINTA

2

NVPO

Server    

Lon_1

SNVT_count_f

-

oRUN_STATUS

SINTA

3

NVPO

Server    

Lon_1

SNVT_count_f

-

oBEDLIFE_H

SINTA

4

NVPO

Server    

Lon_1

SNVT_count_f

-

oBEDLIFE_M

SINTA

5

NVPO

Server    

Lon_1

SNVT_count_f

-

oRUNTIME_H

SINTA

6

NVPO

Server    

Lon_1

SNVT_count_f

-

oRUNTIME_M

SINTA

7

NVPO

Server    

Lon_1

SNVT_count_f

-

oDRAINTIME_H

SINTA

8

NVPO

Server    

Lon_1

SNVT_count_f

-

oDRAINTIME_M

SINTA

9

NVPO

Server    

Lon_1

SNVT_count_f

-

oIDLETIME_H

SINTA

10

NVPO

Server    

Lon_1

SNVT_count_f

-

oIDLETIME_M

SINTA

11

NVPO

Server    

Lon_1

SNVT_count_f

-

oRH_VALUE

SINTA

12

NVPO

Server    

Lon_1

SNVT_lev_percent

-

oDUCT_VALUE

SINTA

13

NVPO

Server    

Lon_1

SNVT_lev_percent

-

oOUTSIDE_TEMP

SINTA

14

NVPO

Server    

Lon_1

SNVT_temp_p

-

oWATER_TEMP

SINTA

15

NVPO

Server    

Lon_1

SNVT_temp_p

-

oHEAT_TEMP

SINTA

16

NVPO

Server    

Lon_1

SNVT_temp_p

-

oFAULT

SINTA

17

NVPO

Server    

Lon_1

SNVT_count_f

-

oCON_NUMBER

SINTA

18

NVPO

Server    

Lon_1

SNVT_count_f

-

oHEAT_POWER

SINTA

19

NVPO

Server    

Lon_1

SNVT_count_f

-

oLANGUAGE

SINTB

0

NVPO

Server    

Lon_1

SNVT_count_f

-

oRH_SET

SINTB

1

NVPO

Server    

Lon_1

SNVT_lev_percent

-

oHL_POINT

SINTB

2

NVPO

Server    

Lon_1

SNVT_lev_percent

-

oOUTTEMP_H

SINTB

3

NVPO

Server    

Lon_1

SNVT_temp_p

-

oOUTTEMP_L

SINTB

4

NVPO

Server    

Lon_1

SNVT_temp_p

-

oOUTRH_L

SINTB

5

NVPO

Server    

Lon_1

SNVT_lev_percent

-

oRUN_MODE

SINTB

6

NVPO

Server    

Lon_1

SNVT_count_f

-

oWATER_TEMP_SET

SINTB

7

NVPO

Server    

Lon_1

SNVT_temp_p

-

oBED_LIFE

SINTB

8

NVPO

Server    

Lon_1

SNVT_count_f

-

oDRAIN_FREQ

SINTB

9

NVPO

Server    

Lon_1

SNVT_count_f

-

oDRAIN_TIME

SINTB

10

NVPO

Server    

Lon_1

SNVT_count_f

-

oSENSER_TYPE

SINTB

11

NVPO

Server    

Lon_1

SNVT_count_f

-

oPID_DIV

SINTB

12

NVPO

Server    

Lon_1

SNVT_count_f

-

oPID_PB

SINTB

13

NVPO

Server    

Lon_1

SNVT_count_f

-

oPID_SI

SINTB

14

NVPO

Server    

Lon_1

SNVT_count_f

-

oPID_DG

SINTB

15

NVPO

Server    

Lon_1

SNVT_count_f

-

oMOD_FILL_FREQ

SINTB

16

NVPO

Server    

Lon_1

SNVT_count_f

-

oMOD_FILL_TIME

SINTB

17

NVPO

Server    

Lon_1

SNVT_count_f

-

oWATER_TEMP_COMP

SINTB

18

NVPO

Server    

Lon_1

SNVT_temp_p

-

oHEAT_TEMP_COMP

SINTB

19

NVPO

Server    

Lon_1

SNVT_temp_p

-

iCOMTYPE

BITB_in

0

NVUI

Server    

Lon_1

SNVT_switch

state

iRH_SELECT

BITB_in

1

NVUI

Server    

Lon_1

SNVT_switch

state

iHL_SELECT

BITB_in

2

NVUI

Server    

Lon_1

SNVT_switch

state

iOUTTEM_SELECT

BITB_in

3

NVUI

Server    

Lon_1

SNVT_switch

state

iNETWORK_ENABLE

BITB_in

4

NVUI

Server    

Lon_1

SNVT_switch

state

iMOD_FILL_ENABLE

BITB_in

5

NVUI

Server    

Lon_1

SNVT_switch

state

iLANGUAGE

SINTB_in

0

NVUI

Server    

Lon_1

SNVT_count_f

-

iRH_SET

SINTB_in

1

NVUI

Server    

Lon_1

SNVT_lev_percent

-

iHL_POINT

SINTB_in

2

NVUI

Server    

Lon_1

SNVT_lev_percent

-

iOUTTEMP_H

SINTB_in

3

NVUI

Server    

Lon_1

SNVT_temp_p

-

iOUTTEMP_L

SINTB_in

4

NVUI

Server    

Lon_1

SNVT_temp_p

-

iOUTRH_L

SINTB_in

5

NVUI

Server    

Lon_1

SNVT_lev_percent

-

iRUN_MODE

SINTB_in

6

NVUI

Server    

Lon_1

SNVT_count_f

-

iWATER_TEMP_SET

SINTB_in

7

NVUI

Server    

Lon_1

SNVT_temp_p

-

iBED_LIFE

SINTB_in

8

NVUI

Server    

Lon_1

SNVT_count_f

-

iDRAIN_FREQ

SINTB_in

9

NVUI

Server    

Lon_1

SNVT_count_f

-

iDRAIN_TIME

SINTB_in

10

NVUI

Server    

Lon_1

SNVT_count_f

-

iSENSER_TYPE

SINTB_in

11

NVUI

Server    

Lon_1

SNVT_count_f

-

iPID_DIV

SINTB_in

12

NVUI

Server    

Lon_1

SNVT_count_f

-

iPID_PB

SINTB_in

13

NVUI

Server    

Lon_1

SNVT_count_f

-

iPID_SI

SINTB_in

14

NVUI

Server    

Lon_1

SNVT_count_f

-

iPID_DG

SINTB_in

15

NVUI

Server    

Lon_1

SNVT_count_f

-

iMOD_FILL_FREQ

SINTB_in

16

NVUI

Server    

Lon_1

SNVT_count_f

-

iMOD_FILL_TIME

SINTB_in

17

NVUI

Server    

Lon_1

SNVT_count_f

-

iWATER_TEMP_COMP

SINTB_in

18

NVUI

Server    

Lon_1

SNVT_temp_p

-

iHEAT_TEMP_COMP

SINTB_in

19

NVUI

Server    

Lon_1

SNVT_temp_p

-

Содержание HumidiClean HC-6100 Series

Страница 1: ...ge Warning Labels 2 3 Description of Model Number 4 Installation 6 12 Display Menu 13 16 Start Up Procedure and Operation 16 17 Maintenance 18 22 Troubleshooting 22 27 Typical Wiring Schematic 28 37 R...

Страница 2: ...RCUIT BREAKER OR SAFETY SWITCH BEFORE OPENING ANY COVERS AND DOORS 3 Before servicing the humidifier learn where the high voltage parts are KEEP HANDS AND METAL TOOLS AWAY FROM THESE AREAS Warning All...

Страница 3: ...ply and have one OFF isolated and one ON position only clearly marked with O and I symbols 60417 2 IEC 5008 and 60417 2 IEC 5007 see 10 2 2 with the actuating directions in accordance with IEC60447 Ci...

Страница 4: ...nt A claim should be filed with the transportation company and reported to Armstrong if any items are missing or damaged 2 Check Local Codes The installation of HumidiClean should be in accordance wit...

Страница 5: ...Detail A Pitch Min 1 Per 12 Back to Unit P Trap Drain Every 20 of Piping or at Bottom of Vertical Run 24 2 Insulated Copper 24 1 Copper Min Pitched 1 Per 12 Min to Open Drain 1 ID Hose Air Gap Fused...

Страница 6: ...ny potable or purified water supply Water pressure must be 25 120 psig Water temperature must be less than 60 C 140 F 1 Install a shut off valve near the unit 2 Connect the water supply to the 3 8 com...

Страница 7: ...Steam Output kg hr lb hr Steam Output kg hr lb hr Nominal Amperage Rating Three Phase Steam Output kg hr lb hr Nominal Amperage Rating Three Phase Steam Output kg hr lb hr Nominal Amperage Rating Thr...

Страница 8: ...ipe and hose cuffs provided We do not suggest steam distribution piping of field supplied rubber based compounds to be used for any HumidiClean application Pitch pipe back to unit 25 mm 1 per foot The...

Страница 9: ...o keep the electric cabinet in compliance with IP32 Wiring for low voltage controls should not be run in same conduit as the power supply Use of shielded wire or a separate dedicated metal conduit is...

Страница 10: ...Switch To Set Up 1 S1 1 3 Off S1 2 On 2 S3 1 On S3 2 3 4 Off 3 S2 1 2 3 Off 4 Select 0 10vdc Signal Type in the Operational Setup Menu 5 Select Humidistat Sensor Select in the Operational Setup Menu F...

Страница 11: ...4 2 on S4 1 3 Off S3 1 on S3 2 3 4 off 24Vac S4 1 3 on S4 2 Off S3 2 on S3 1 3 4 off 10Vac S4 1 3 on S4 2 Off S3 3 on S3 1 2 4 off 5Vac S4 1 3 on S4 2 Off S3 4 on S3 1 2 3 off 4 on 5 off Thermistor 4...

Страница 12: ...n there is insufficient air flow in a duct system A duct pressure switch is preferred as an airflow sensor The pressure switch should open on insufficient airflow opens on fault Airflow switch should...

Страница 13: ...Unit configuration setup English English Default Chinese Unit Status 1 Unit Demand XXX Demand Steam Output XXX lb hr Steam Output Unit Status 2 Water Level Normal Water Level State Low Normal and High...

Страница 14: ...ure of water 180 F 80 C The maximum is 80 C 180 F the minimum is 4 C 40 F If the set point is lower than 40 F then function is disabled When disabled the unit will go into a 3 minute warm up when turn...

Страница 15: ...15 Default PID Settings PB Proportion Brand 0 900 PID PB 10 PID IRV 10 IRV Integral Reset Value 0 500 PIDF DG 200 PID SI 10 DG Derivative Gain 0 500 SI Interval 0 30 Records Error List 01 05 04 01 16...

Страница 16: ...ectrical compartment for any loose or disconnected component wiring Check all high voltage screw terminal connections at contactor terminal strip fuse block power module for tightness 2 Remove Side Pa...

Страница 17: ...read from the humidistat or calculated by reading the relative humidity and setpoint If the demand sig nal drops below 2 or the high limit sail switch circuit opens the contactor s will open and the u...

Страница 18: ...bed does not appear to be saturated with mineral deposit a full bed will weigh 1 1 kg 2 6 lbs dry and if the drain screen is clear you have two options a Reset the Ionic Bed service life Proceed with...

Страница 19: ...PERATION section after the HumidiClean has accumulated 90 of the selected Service Life in hours of heater on time the STATE LED will flash blink in yellow At this time the ionic beds in the tank shoul...

Страница 20: ...Make sure access panel gasket is lapped over all edges of tank access opening Replace and secure tank access panel 7 Make sure both access doors panels are secure 8 Turn on power at circuit breaker 2...

Страница 21: ...ng the probe and wire locations Note Level control float switches are used for DI RO or very pure water Cleaning should not typically be required 5 Unscrew the probes from the level canister using the...

Страница 22: ...midification Group at Phone 269 273 1415 Humidifier will not fill with water when power is applied 1 Make sure the status in menu is Steam Gen 2 Make sure STATE LED is red If so refer to MAINTENANCE o...

Страница 23: ...s OK the PC board is likely defective b If voltage is 17 20 VAC with circuit open but does not drop when water contacts the two electrodes the water may be too pure consult factory or if the voltage d...

Страница 24: ...float lever arm swings freely 2 The fill valve may be stuck open Turn off power to the humidifier If fill valve does not close clean or replace valve 3 If the high water circuit is closed and the fil...

Страница 25: ...mately 8 with wires disconnected If resistance is OK check voltage drops across the contactor b If no voltage to contactor coil check continuity of wires from PC board to contactor If continuity is OK...

Страница 26: ...RH A high limit humidistat RH sensor is recommended to prevent this See Installation section Water in bottom of cabinet 1 Verify that pressure equalizing tubing is hooked up from top of electrode lev...

Страница 27: ...rnal temperature exceeds safe level Check low water in tank scale buildup on Thermocouple heating element surface defective Thermocouple See Clearing Error Codes section 6 WATER LEVEL HAS NOT DROPPED...

Страница 28: ...HC6100 Wye Wiring layout 28...

Страница 29: ...HC6100 Delta Wiring layout 29...

Страница 30: ...30 HC6100 PAR Single Phase Wiring Layout...

Страница 31: ...HC6300 Wye Wiring layout 31...

Страница 32: ...HC6300 Delta Wiring layout 32...

Страница 33: ...HC6500 Wye Wiring layout 33...

Страница 34: ...HC6500 Delta Wiring layout 34...

Страница 35: ...35 HC6500 WYE 2 contactors Wiring Layout...

Страница 36: ...36 HC6500 Delta 2 contactors Wiring Layout...

Страница 37: ...HC6700 Wye Wiring layout 37...

Страница 38: ...DM hose cuff B2851 1 1 2 IDx9 5 8 EPDM hose cuff B2250 1 IDx18 EPDM hose cuff A9620 1 Hardware Assembly B5287 Passivated Tank D2171 25 S assy Ionic Bed HC 6000 six required for HC 6100 and HC 6300 B52...

Страница 39: ...B5045 2 B5046 2 380 B5049 1 B5050 1 B5045 1 B5046 1 480 B5049 3 B5050 3 B5045 3 B5046 3 600 B5049 4 B5050 4 B5045 4 B5046 4 Without TC 5PCS Unit With TC 1PCS Unit Without TC 5PCS Unit With TC 1PCS Uni...

Страница 40: ...A7618A Clamp Hose Flat 63 Olive B2716 11 Hose Clamp Minerature Worm B2911 8 25 Fill Valve RDHC6000 001 21 Tubing Rd 7 8 Od Silicon A19699 23 Clamp Hose Flat 88 B2716 18 22 Tee Barbed HDPE 5 8 A23237...

Страница 41: ...c 14 5 16 8 277Vac 24 across H1 H4 600Vac 15 30kW 346Vac 22 7 26 3 380Vac 40 across H1 H5 208Vac and 380Vac9 18kW 220Vac 15 3 17 7 480Vac 53 across H1H6 240Vac 9 18kW 240Vac 18 2 21 1 600Vac 97 across...

Страница 42: ...out TC 5PCS Unit With TC 1PCS Unit Without TC 5PCS Unit With TC 1PCS Unit Without TC 5PCS Unit With TC 1PCS Unit Without TC 8PCS Unit With TC 1PCS Unit B5435 1 B5436 1 B5435 1 B5436 1 B5435 1 B5436 1...

Страница 43: ...rgency button The indicator LED D47 on main board will remain ON Keep the power supply on for at least 8 seconds This is the step to erase the old code c Turn off the power supply and put dip switch S...

Страница 44: ...pen folder button on the right of textbox Send File Name to open the latest code please see figure 3 below You will then have to locate the bin file that you downloaded from the website and then hit o...

Страница 45: ...de into board Please see figure 4 below Fig 4 Message Unlock Involved Lock Regions Window f When sending was finished you will be asked to lock all locks that you have opened just now click the button...

Страница 46: ...ect different port Please see instruction details for Modbus_RTU used in HC6000 When you want to use modules please change the configuration from communication to PSP per menu See section 3 2 3 commun...

Страница 47: ...ime out from low to high level 8 Water level above high level time out 9 Water level has not dropped below low level during an emptydrain 10 End of bed dring 30019 Contactor number 30020 Contactor Pow...

Страница 48: ...rcuit is open 3 Illegal level switch state 4 Unit have reached 100 of bed life 5 Fill time out to low level 6 Water level dropped below level during normal run 7 Fill time out from low to high level 8...

Страница 49: ...O Server Lon_1 SNVT_temp_p oOUTRH_L SINTB 5 NVPO Server Lon_1 SNVT_lev_percent oRUN_MODE SINTB 6 NVPO Server Lon_1 SNVT_count_f oWATER_TEMP_SET SINTB 7 NVPO Server Lon_1 SNVT_temp_p oBED_LIFE SINTB 8...

Страница 50: ...5 D Drain Back 20 508 29 3 16 748 E Drain Side 9 1 8 232 11 1 2 293 F Steam Discharge Tube 2 3 8 60 2 3 8 60 G Steam Outlet Side 7 1 2 190 9 1 2 241 H Steam Outlet Front 14 1 3 364 12 7 8 328 J Supply...

Страница 51: ...6700 Front Side Top Views Q B G A D E Water Supply Port Under Cabinet H J K L M C F Electrical Supply Under Cabinet 1 Drain Under Cabinet Knock Out for Humidistat Knock Out for Humidistat Physical Dat...

Страница 52: ...er basis or theory is limited to Armstrong s repair or replacement of the part or product excluding any labor or any other cost to remove or install said part or product or at Armstrong s option to re...

Отзывы: