14
Enter Password 0000 (Default)
Desired RH
This menu is displayed when RH sensor is selected
Desired RH: XX %
Default: 50%
Current RH: XX%
Steam Generation
Steam Gen (Default)
Manual Drain
Manual Fill
Unit Stop
Modulating Fill Cycle
Enabled (Default)
Disabled
If modulating fill cycle is enabled:
Fill Valve Off Time
30 seconds
Fill Valve On Time
10 seconds
Error Reset
Error Reset
Error Reset?
Confirm Cancel
Aquastat
Temperature of water 180°F/80°C
The maximum is 80°C/180°F, the minimum is 4°C/40°F. If
the set point is lower than 40°F, then function is disabled. When
disabled the unit will go into a 3 minute warm-up when turned on.
Network Setup
Disabled
Disabled (Default)
Enabled
Mode Change
Slave ID 1 (Default)
Value: 1 to 127
Communication Type
MODBUS
MODBUS (Default)
PSP (includes LonWorks/BACNet)
Password
New Password
0-9 Default: 0000
A-Z
a-z
End of Life
500
(Run Time Accumulation Hours)
750
1000 (Default)
1250
1500
1750
2000
2250
2500
2750
3000
No Beds
LT RT move the cursor UP DN to increase/decrease value
Operation Setup
Operation Setup
Содержание HumidiClean HC-6100 Series
Страница 28: ...HC6100 Wye Wiring layout 28...
Страница 29: ...HC6100 Delta Wiring layout 29...
Страница 30: ...30 HC6100 PAR Single Phase Wiring Layout...
Страница 31: ...HC6300 Wye Wiring layout 31...
Страница 32: ...HC6300 Delta Wiring layout 32...
Страница 33: ...HC6500 Wye Wiring layout 33...
Страница 34: ...HC6500 Delta Wiring layout 34...
Страница 35: ...35 HC6500 WYE 2 contactors Wiring Layout...
Страница 36: ...36 HC6500 Delta 2 contactors Wiring Layout...
Страница 37: ...HC6700 Wye Wiring layout 37...