background image

506860-03

Issue  1946

Page 22 of 27

Display

Display and action (normal operation)

Display and action (configuration and test mode)

Power-Up

Display string displays > number of unit stages > pause > 

AC

 or 

HP

 unit > pause > unit capacity in BTUs > pause > 

RPM setting of outdoor fan. If 3 horizontal bars are displayed during any sequence of this string, it indicates that the 

specific parameter is not configured.

-

Idle mode - decimal blinks at 1 Hz > 0.5 second ON, 0.5 second OFF

A

A

 in the display string represents the ambient 

temperature in °F at the outdoor sensor on the outdoor 

unit.

Enter 

A

 test mode: Display will string active error code(s) 

E

, ambient 

A

, coil 

c

 and discharge 

d

 temperature in °F at 

outdoor unit.

c

Enter A test mode: Display will string active error codes (

E

), ambient (

A

), coil (

c

), and discharge (

d

) temperature in °F 

at outdoor unit.

d

d

 - dehumidification mode string > 

d

 > pause > 

F

 

(Outdoor fan) RPM > pause > 

A

 (ambient temp displayed) 

> pause > repeat mode. 

IMPORTANT

: On 2-stage unit, 

R to DS link must be cut and correct RPM outdoor fan 

profile selected for outdoor fan to operate at lower RPM 

speed when EDA is active.

Enter 

d

 test mode: Forced defrost. (System must be 

configured as HP. Unit must be running in heating 

mode). Test defrost will terminate when coil terminate 

temperature is reached (or 10 seconds, whichever is 

longer) or 14 minutes if coil temperature remains below 

terminate temperature or by pushing button down for less 
than 2 seconds. Enter 

A

 test mode: Display will string 

active error codes 

E

, ambient 

A

, coil 

c

 and discharge 

d

 

temperature in °F at outdoor unit.

dF

dF

 displays when system is in defrost mode - unit must be running in heating mode, outdoor ambient must be below 

65°F and outdoor coil temperature must be below defrost termination temperature.

F*

F

 in the display string indicates RPM setting output on 

terminals PWM and com (used with EBM motors). RPM 

displayed does not apply to motor connected on ECM Y1 

and ECM Y2.

Enter 

F

 test mode: Control outputs DC Voltage onto 

PWM and com terminals. Outdoor fan will cycle ON for 

10 minutes at 490 RPM. To exit test - Push and hold 

button until three horizontal bars display. Release button, 

outdoor fan will cycle OFF. (Test DOES NOT output DC 

voltage to ECM Y1 and ECM Y2 terminals)

H1

Heat stage 1 string display > pause > 

F

 outdoor fan RPM displayed > pause > 

A

 (ambient temperature displayed > 

pause > repeat mode.

H2

Heat stage 2 string display > pause > 

F

 outdoor fan RPM displayed > pause > 

A

 (ambient temperature displayed > 

pause > repeat mode.

C1

Cool stage 1 string display > pause > 

F

 outdoor fan RPM displayed > pause > 

A

 (ambient temperature displayed > 

pause > repeat mode.

C2

Cool stage 2 string display > pause > 

F

 outdoor fan RPM displayed > pause > 

A

 (ambient temperature displayed > 

pause > repeat mode.

* Information will be displayed, but does not apply to this product.

Table 8. Field Test and Program Menu Options

Содержание 4SHP16LS Series

Страница 1: ...local codes in any way The installation must comply with all provincial state and local codes as well as the National Electrical Code U S or Canadian Electrical Code Canada Compliance should be determ...

Страница 2: ...ing parts 4 Handle refrigerant with caution refer to proper MSDS from refrigerant supplier 5 Use care when lifting avoid contact with sharp edges Installation NOTE In some cases noise in the living ar...

Страница 3: ...cted by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and...

Страница 4: ...24 3 8 3 4 36 3 8 7 8 48 3 8 7 8 60 3 8 1 1 8 For installations exceeding 50 refer to long line set guidelines Be extra careful with sharp bends Tubing can kink very easily and if this occurs the enti...

Страница 5: ...UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid lin...

Страница 6: ...hown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSE...

Страница 7: ...ound Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVI...

Страница 8: ...ES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and co...

Страница 9: ...of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier...

Страница 10: ...id refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder R...

Страница 11: ...nch with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valv...

Страница 12: ...ring 2 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a proper conduit fitting Un...

Страница 13: ...OR AIR HANDLER RSBus RSBus OPTIONAL DISCHARGE AIR SENSOR COMFORT SYNCTM THERMOSTAT COMFORT SYNCTM ENABLED HEAT PUMP RSBus OPTIONAL OUTDOOR AIR SENSOR OPTIONAL DISCHARGE AIR SENSOR COMFORT SYNCTM ENAB...

Страница 14: ...or varying lengths of line set refer to Table 4 for refrigerant charge adjustment A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustme...

Страница 15: ...ocked out until power to the board is interrupted then re established or until the error is cleaned NOTE The control board ignores input from the low pressure switch terminals as follows During the TE...

Страница 16: ...m the Comfort Sync thermostat must be used The complete configuration of the outdoor unit is performed using the Comfort Sync thermostat For complete details on how to integrate this unit into a Comfo...

Страница 17: ...nication problem Hardware problem on the control Cycle power on control Replace if problem prevents service and is persistent Cleared 300 seconds after fault recovered E131 Corrupted control parameter...

Страница 18: ...r unit blower motor dirty filters or clogged refrigerant filter Confirm that the evaporator coil is clean The alarm clears after a power rest E412 The outdoor unit pressure is above the required limit...

Страница 19: ...ed by allowing the unit to run for 90 seconds before checking discharge sensor resistance If the discharge sensor resistance is not within range after 90 seconds the board will count one fault After 5...

Страница 20: ...Hz Idle Mode Decimal point blinks at 1 Hz 0 5 second on 0 5 second off Display OFF Soft Disabled Top and bottom horizontal line and decimal point blink at 1 Hz Soft Disabled Top and bottom horizontal...

Страница 21: ...650 pause A104 pause Outdoor Coil Temperature OCT Any time OCT is sensed in operating range value is displayed if unit is in diagnostic mode Following string is repeated if 2nd stage heat is active wi...

Страница 22: ...minutes if coil temperature remains below terminate temperature or by pushing button down for less than 2 seconds Enter A test mode Display will string active error codes E ambient A coil c and disch...

Страница 23: ...g procedure must be repeated Table 9 Configuring Unit Capacity Display Code Procedure Solid Pt Release push button Allows user to select type and number of stages on outdoor unit IMPORTANT Field repla...

Страница 24: ...ent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODI...

Страница 25: ...t may engage auxiliary heat during the defrost cycle to satisfy a heating demand however the unit will run to normal operation at the conclusion of the defrost cycle In case of extended power outage I...

Страница 26: ...506860 03 Issue 1946 Page 26 of 27 4SHP16LS124 36 48 Wiring Diagrams...

Страница 27: ...506860 03 Issue 1946 Page 27 of 27 4SHP16LS160...

Отзывы: