Code

Diagnostic Codes / Status of Equipment

Action Required to Clear and Recover

E180

Outdoor air temperature sensor failure. Only shown if 

shorted or out of range (Communicating systems only)

Compare outdoor sensor resistance to temperature 

resistance charts in unit installation instructions. Replace 

sensor pack if necessary. At beginning of (any) configuration, 

furnace or air handler control will sense outdoor air and 

discharge air temperature sensor(s) If detected (reading 

in range), appropriate feature will be set as installed and 

that could be seen in 'About ' screen. In normal operation 

after control recognizes sensors, alarm will be sent if valid 

temperature reading is lost. To get rid of setting and alarm, 

redo configuration and make sure that temperature sensor is 

marked as not installed in indoor Unit ‘About’ screen. When 

indoor unit control is replaced thermostat will ‘tell’ new control 

if temperature sensor is in system or not. Clears 30 seconds 

after fault recovered.

E409

LSOM - Compressor low voltage.

Secondary voltages below 18VAC. After 10 minutes, operation 

is discontinued. Clears the code after voltage is higher than 

20VAC for 2 seconds or after power reset.

E410

The outdoor unit pressure is below the required limit.

Unit pressure is below the lower limit. The system is shut 

down. The low pressure switch for R-410A will open at 40 

PSIG and close at 90 PSIG. Confirm that the system is 

properly charged with refrigerant. Check TXV, indoor unit 

blower motor, dirty filters or clogged refrigerant filter. Confirm 

that the evaporator coil is clean. The alarm clears after the 

pressure switch closes or after a power rest.

E411

The low pressure switch has opened 5 times during one 

cooling cycle. As a result, the system will shut down.

Open low pressure switch error count reached 5 strikes. The 

low pressure switch for R-410A will open at 40 PSIG and 

close at 90 PSIG. Confirm that the system is properly charged 

with refrigerant. Check TXV, indoor unit blower motor, dirty 

filters or clogged refrigerant filter. Confirm that the evaporator 

coil is clean. The alarm clears after a power rest.

E412

The outdoor unit pressure is above the required limit. The 

system will shut down.

Unit pressure is above the upper limit. System is shut down. 

The high pressure switch for R-410A will open at 590 PSIG 

and close at 418 PSIG. Confirm that the system is properly 

charged with refrigerant. Check condenser fan motor, TXV, 

indoor unit blower motor, stuck reversing valve or clogged 

refrigerant filter. Confirm that the outdoor unit is clean. The 

alarm clears after 4 consecutive normal compressor run 

cycles, the pressure switch closes or a power reset.

E413

The high pressure switch has opened 5 times during one 

cooling cycle. As a result, the Comfort Sync thermostat 

will shut down.

Open high pressure switch error count reached 5 strikes. 

System is shut down. The high pressure switch for R-410A will 

open at 590 PSIG and close at 418 PSIG. Confirm that the 

system is properly charged with refrigerant. Check condenser 

fan motor, TXV, indoor unit blower motor, stuck reversing 

valve or clogged refrigerant filter. Confirm that the outdoor unit 

is clean. The alarm clears after a power reset.

E414

The discharge line temperature is higher than the 

recommended upper limit of 279°F.

Discharge line temperature is > 279°F. Confirm that the 

system is properly charged with refrigerant. Check system 

operating pressures and compare to unit charging charts in 

installation manual. Confirm that the outdoor unit is clean. The 

alarm clears after the discharge temperature is < 225°F.

E415

The discharge line temperature has been consistently 

higher than the recommended upper limit of 279°F.

Discharge line high temperature error count reached 5 

strikes. Confirm that the system is properly charged with 

refrigerant. Check system operating pressures and compare 

to unit charging charts in installation manual. Confirm that the 

outdoor unit is clean. The alarm clears after the discharge 

temperature is < 225°F. The alarm clears after a power reset.

NOTE

Additional codes may be found in the Comfort Sync room thermostat manual.

Table 5. 7-Segment Alert and System Status Codes

Содержание 4SHP16LS Series

Страница 1: ...local codes in any way The installation must comply with all provincial state and local codes as well as the National Electrical Code U S or Canadian Electrical Code Canada Compliance should be determ...

Страница 2: ...ing parts 4 Handle refrigerant with caution refer to proper MSDS from refrigerant supplier 5 Use care when lifting avoid contact with sharp edges Installation NOTE In some cases noise in the living ar...

Страница 3: ...cted by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and...

Страница 4: ...24 3 8 3 4 36 3 8 7 8 48 3 8 7 8 60 3 8 1 1 8 For installations exceeding 50 refer to long line set guidelines Be extra careful with sharp bends Tubing can kink very easily and if this occurs the enti...

Страница 5: ...UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid lin...

Страница 6: ...hown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSE...

Страница 7: ...ound Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVI...

Страница 8: ...ES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and co...

Страница 9: ...of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier...

Страница 10: ...id refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder R...

Страница 11: ...nch with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valv...

Страница 12: ...ring 2 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a proper conduit fitting Un...

Страница 13: ...OR AIR HANDLER RSBus RSBus OPTIONAL DISCHARGE AIR SENSOR COMFORT SYNCTM THERMOSTAT COMFORT SYNCTM ENABLED HEAT PUMP RSBus OPTIONAL OUTDOOR AIR SENSOR OPTIONAL DISCHARGE AIR SENSOR COMFORT SYNCTM ENAB...

Страница 14: ...or varying lengths of line set refer to Table 4 for refrigerant charge adjustment A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustme...

Страница 15: ...ocked out until power to the board is interrupted then re established or until the error is cleaned NOTE The control board ignores input from the low pressure switch terminals as follows During the TE...

Страница 16: ...m the Comfort Sync thermostat must be used The complete configuration of the outdoor unit is performed using the Comfort Sync thermostat For complete details on how to integrate this unit into a Comfo...

Страница 17: ...nication problem Hardware problem on the control Cycle power on control Replace if problem prevents service and is persistent Cleared 300 seconds after fault recovered E131 Corrupted control parameter...

Страница 18: ...r unit blower motor dirty filters or clogged refrigerant filter Confirm that the evaporator coil is clean The alarm clears after a power rest E412 The outdoor unit pressure is above the required limit...

Страница 19: ...ed by allowing the unit to run for 90 seconds before checking discharge sensor resistance If the discharge sensor resistance is not within range after 90 seconds the board will count one fault After 5...

Страница 20: ...Hz Idle Mode Decimal point blinks at 1 Hz 0 5 second on 0 5 second off Display OFF Soft Disabled Top and bottom horizontal line and decimal point blink at 1 Hz Soft Disabled Top and bottom horizontal...

Страница 21: ...650 pause A104 pause Outdoor Coil Temperature OCT Any time OCT is sensed in operating range value is displayed if unit is in diagnostic mode Following string is repeated if 2nd stage heat is active wi...

Страница 22: ...minutes if coil temperature remains below terminate temperature or by pushing button down for less than 2 seconds Enter A test mode Display will string active error codes E ambient A coil c and disch...

Страница 23: ...g procedure must be repeated Table 9 Configuring Unit Capacity Display Code Procedure Solid Pt Release push button Allows user to select type and number of stages on outdoor unit IMPORTANT Field repla...

Страница 24: ...ent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODI...

Страница 25: ...t may engage auxiliary heat during the defrost cycle to satisfy a heating demand however the unit will run to normal operation at the conclusion of the defrost cycle In case of extended power outage I...

Страница 26: ...506860 03 Issue 1946 Page 26 of 27 4SHP16LS124 36 48 Wiring Diagrams...

Страница 27: ...506860 03 Issue 1946 Page 27 of 27 4SHP16LS160...

Отзывы: