background image

506860-03

Issue  1946

Page 2 of 27

This unit uses R-410A, which is an ozone-friendly HFC 

refrigerant. The unit must be installed with a matching 

indoor coil and line set. A filter drier approved for use with 

R-410A is installed in the unit.

IMPORTANT

This product has been designed and 

manufactured to meet ENERGY STAR criteria for energy 

efficiency when matched with appropriate coil components. 

However,  proper  refrigerant  charge  and  proper  air  flow 

are  critical  to  achieve  rated  capacity  and  efficiency. 

Installation of this product should follow the manufacturer’s 

refrigerant  charging  and  air  flow  instructions. 

Failure to 

confirm proper charge and airflow may reduce energy 

efficiency and shorten equipment life.

When servicing or repairing HVAC components, ensure 

the fasteners are appropriately tightened. Table 1 shows 

torque values for fasteners.

Table 1. Torque Table

Fastener

Torque

Stem Caps

8 ft. lbs.

Service Port Caps

8 ft. lbs.

Sheet Metal Screws

16 in. lbs.

#8 Machine Screws

16 in. lbs.

#10 Machine Screws

28 in. lbs.

Compressor Bolts

90 in. lbs.

Inspection of Shipment

Upon receipt of equipment, carefully inspect it for possible 

shipping damage. If damage is found, it should be noted 

on the carrier’s freight bill. Take special care to examine 

the unit inside the carton if the carton is damaged. Any 

concealed damage discovered should be reported to the 

last carrier immediately, preferably in writing, and should 

include a request for inspection by the carrier’s agent.

If any damages are discovered and reported to the carrier 

DO NOT INSTALL THE UNIT

, as claim may be denied.

Check the unit rating plate to confirm specifications are as 

ordered.

Safety Precautions

Follow all safety codes. Wear safety glasses and work 

gloves. Use quenching cloth for brazing operations. 

Have fire extinguisher available. Read these instructions 

thoroughly and follow all warning or cautions attached to 

the unit.
1.  Always wear proper personal protection equipment.
2.  Always disconnect electrical power before removing 

panel or servicing equipment.

3.  Keep hands and clothing away from moving parts.
4.  Handle refrigerant with caution; refer to proper MSDS 

from refrigerant supplier.

5.  Use care when lifting, avoid contact with sharp edges.

Installation

NOTE: 

In some cases, noise in the living area has been 

traced  to  gas  pulsations  from  improper  installation  of 

equipment.

•  Locate unit away from windows, patios, decks, etc. 

where unit operation sounds may disturb customer.

•  Leave some slack between structure and unit to 

absorb vibration.

•  Place a sound-absorbing material, such as Isomode, 

under the unit if it will be installed in a location or 

position that will transmit sound or vibration to the 

living area or adjacent buildings.

•  Install the unit high enough above the ground or roof to 

allow adequate drainage of defrost water and prevent 

ice buildup.

•  In heavy snow areas, do not locate the unit where 

drifting snow will occur. The unit base should be 

elevated above the depth of average snows.

NOTE: 

Elevation  of  the  unit  may  be  accomplished 

by constructing a frame using suitable materials. If a 

support frame is constructed, it must not block drain 

holes in unit base.

•  When installed in areas where low ambient 

temperatures exist, locate unit so winter prevailing 

winds do not blow directly into outdoor coil.

•  Locate unit away from overhanging roof lines which 

would allow water or ice to drop on, or in front of, coil 

or into unit.

When outdoor unit is connected to factory-approved indoor 

unit, outdoor unit contains system refrigerant charge for 

operation with matching indoor unit when connected by 15 

ft. of field-supplied tubing. For proper unit operation, check 

refrigerant charge using charging information located on 

control box cover.

Outdoor Section

Zoning ordinances may govern the minimum distance the 

condensing unit can be installed from the property line. 

Install on a Solid, Level Mounting Pad

The outdoor section is to be installed on a solid foundation. 

This foundation should extend a minimum of 2” (inches) 

beyond the sides of the outdoor section. To reduce the 

possibility of noise transmission, the foundation slab 

should NOT be in contact with or be an integral part of the 

building foundation. See Figure 1.

If conditions or local codes require the unit be attached to 

pad or mounting frame, tie down bolts should be used and 

secured to unit base pan.

Содержание 4SHP16LS Series

Страница 1: ...local codes in any way The installation must comply with all provincial state and local codes as well as the National Electrical Code U S or Canadian Electrical Code Canada Compliance should be determ...

Страница 2: ...ing parts 4 Handle refrigerant with caution refer to proper MSDS from refrigerant supplier 5 Use care when lifting avoid contact with sharp edges Installation NOTE In some cases noise in the living ar...

Страница 3: ...cted by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and...

Страница 4: ...24 3 8 3 4 36 3 8 7 8 48 3 8 7 8 60 3 8 1 1 8 For installations exceeding 50 refer to long line set guidelines Be extra careful with sharp bends Tubing can kink very easily and if this occurs the enti...

Страница 5: ...UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid lin...

Страница 6: ...hown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSE...

Страница 7: ...ound Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVI...

Страница 8: ...ES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and co...

Страница 9: ...of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier...

Страница 10: ...id refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder R...

Страница 11: ...nch with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valv...

Страница 12: ...ring 2 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a proper conduit fitting Un...

Страница 13: ...OR AIR HANDLER RSBus RSBus OPTIONAL DISCHARGE AIR SENSOR COMFORT SYNCTM THERMOSTAT COMFORT SYNCTM ENABLED HEAT PUMP RSBus OPTIONAL OUTDOOR AIR SENSOR OPTIONAL DISCHARGE AIR SENSOR COMFORT SYNCTM ENAB...

Страница 14: ...or varying lengths of line set refer to Table 4 for refrigerant charge adjustment A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustme...

Страница 15: ...ocked out until power to the board is interrupted then re established or until the error is cleaned NOTE The control board ignores input from the low pressure switch terminals as follows During the TE...

Страница 16: ...m the Comfort Sync thermostat must be used The complete configuration of the outdoor unit is performed using the Comfort Sync thermostat For complete details on how to integrate this unit into a Comfo...

Страница 17: ...nication problem Hardware problem on the control Cycle power on control Replace if problem prevents service and is persistent Cleared 300 seconds after fault recovered E131 Corrupted control parameter...

Страница 18: ...r unit blower motor dirty filters or clogged refrigerant filter Confirm that the evaporator coil is clean The alarm clears after a power rest E412 The outdoor unit pressure is above the required limit...

Страница 19: ...ed by allowing the unit to run for 90 seconds before checking discharge sensor resistance If the discharge sensor resistance is not within range after 90 seconds the board will count one fault After 5...

Страница 20: ...Hz Idle Mode Decimal point blinks at 1 Hz 0 5 second on 0 5 second off Display OFF Soft Disabled Top and bottom horizontal line and decimal point blink at 1 Hz Soft Disabled Top and bottom horizontal...

Страница 21: ...650 pause A104 pause Outdoor Coil Temperature OCT Any time OCT is sensed in operating range value is displayed if unit is in diagnostic mode Following string is repeated if 2nd stage heat is active wi...

Страница 22: ...minutes if coil temperature remains below terminate temperature or by pushing button down for less than 2 seconds Enter A test mode Display will string active error codes E ambient A coil c and disch...

Страница 23: ...g procedure must be repeated Table 9 Configuring Unit Capacity Display Code Procedure Solid Pt Release push button Allows user to select type and number of stages on outdoor unit IMPORTANT Field repla...

Страница 24: ...ent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODI...

Страница 25: ...t may engage auxiliary heat during the defrost cycle to satisfy a heating demand however the unit will run to normal operation at the conclusion of the defrost cycle In case of extended power outage I...

Страница 26: ...506860 03 Issue 1946 Page 26 of 27 4SHP16LS124 36 48 Wiring Diagrams...

Страница 27: ...506860 03 Issue 1946 Page 27 of 27 4SHP16LS160...

Отзывы: