2.
Standard urinals that are used with mains water supply must use a recommended DC pipe Interrupter
in accordance with EN 1717 up to category 5 for back-siphonage between solenoid valve and spreader
as shown. Follow the DC interrupter installation guide for installation
*The vertical distance above the outlet may need to be increased greater than 150mm.
Refer to manufactures instructions for more details.
Installation requirements
for DC pipe interrupters
• It is the installers responsibility
to select and install a DC pipe
interrupter as required by water
quality regulators specification
and ensure it is under normal
circumstance free from leakage.
• Ensure the DC pipe interrupter
is WRAS approved and meets
the requirements of EN 1717
and the following IRN’s should
be considered – IRN R001, IRN
R165*.
• Ensure there are no restrictions
(valves, flow regulators and obstruc
-
tions) between the DC pipe
interrupter and urinal spreader
as they will cause water discharge
form the DC interrupter.
• Please refer to the DC pipe inter-
rupter
instruction prior to install.
• Ensure to install the DC pipe
interrupter in correct orientation
URINAL PLUMBING ARRANGEMENTS FOR STANDARD URINALS WITH
MAINS WATER SUPPLY AND USE OF A DC PIPE INTERRUPTER
310
x
130
A
285
610
to floor
320
315
Solenoid
valve fitting
with 2x couplers
Use standard street
elbow or pre bended
copper tube.
For copper tube bend
detail see page 10
Distance between
solenoid valve and DC
pipe interrupter ≤ 200mm
recommended
see notes
Concealed
breacked
(supplied)
DC pipe
interrupter
8