Recommended mechanical brake connection:
According to EN 81-1, disconnection of the mechanical brake coils from electrical current must
be ensured by at least two contactors. The main-contactors disconnecting the motor current
may be used for this purpose also.
Recommended mechanical brake connection is shown below:
The main contactors (KPA and KPB) must be used to disconnect the DC supply of the mechanical
brake. On the other hand, the brake contactor must be used to disconnect the AC supply.
Disconnecting the DC supply directly while AC supply is still connected will cause arcs on the
contact plates and will shorten the lifetime of the contacts. For that reason, the contacts on DC
circuit must only be opened after the AC supply is cut-off. This will ensure that the contacts will
only be used to disconnect the mechanical brake supply only in emergency situations.
Only the main terminals (not auxillary terminals) of the contactors must be used in the
mechanical brake circuit.
A suitable varistor must be used to filter the instantaneous high-voltage peaks on the
brake coil.
L
N
L
N
KFR: Mechanical brake contactor
KPA, KPB: Motor contactors
ADrive
Содержание ADrive VVVF
Страница 1: ...ADrive VVVF Motor Sürücü VVVF Drive KULLANICI KILAVUZU USER MANUAL TR EN ...
Страница 12: ...ARKEL ADrive 12 ENGLISH TÜRKÇE ...
Страница 46: ...ARKEL ADrive 46 ENGLISH TÜRKÇE Uygun sigorta kontaktör ve kablo kesitleri için bkz Bölüm 6 ...
Страница 50: ...ARKEL ADrive 50 ENGLISH TÜRKÇE ...
Страница 80: ...ARKEL ADrive 80 ENGLISH TÜRKÇE 22 NOTLAR ...
Страница 163: ...ARKEL 161 ADrive ENGLISH TÜRKÇE 22 NOTES ...
Страница 166: ...TÜRKÇE ENGLISH Bu sayfa bilerek boş bırakılmıştır This page is intentionally left blank ...