 ARITERM GSM A2

ARITERM SWEDEN AB

 

  

Installation instructions - 

2011.11.24 - Page 5/8

Input 1 (Ing1 - COM): Alarm or status changes
Alarm relay from the burner to the stove. (grey-brown)
When the burner or stove is started SMS 

Started1(Msg100) 

is sent.

When the burner or stove is stopped SMS 

Stopped1(Msg101) 

is sent.

When the burner or stove stops during operational stoppage SMS 

Alarm1(Msg102) 

is sent. 

Input 2 (Ing2 - COM): Smoke gas alarm  
5358 Smoke gas sensor.
Settable temperature limit (Tmp2). Factory setting 240˚, setting range 20-300˚.
If the temperature is above the temperature limit for longer than 10 minutes, SMS   

Flue gas Alarm (Msg103) 

is sent.

To modify the temperature limit:
Send:  

Temp??

As a response you get:  Temp**1,+053,   *2,+240,   *3,+053,   *4,+050,   *5,+053,   *
Example: We wish to change the temperature limit to +180 degrees.
Send:  

Temp!*2,+180,* 

 (no spaces)

As a response you get:  Temp**1,+053,   *2,

+180

,   *3,+053,   *4,+050,   *5,+053,   *

Input 3 (Ing3 - COM): Level alarm pellet store  
Level alarm fuel. 1350 Capacitive sensor. 
If the pellets are missing for more than 10 sec. SMS 

Storage Alarm (Msg107) 

is sent.

Input 4 (Ing4 - COM): Temperature alarm
5292 Tank sensor.
Settable temperature limit (Tmp4). Factory setting 50˚, setting range 10-90˚.
Sends SMS 

TempAlarm (Msg108)

 if the temperature has fallen below the temperature  

limit (Tmp4) for more than 5 mins.
At first start: The function is deactivated until the temperature rises above the  
temperature limit.

To modify the temperature limit:

Send: 

Temp?

?

As a response you get:    Temp**1,+053,    *2,+240,    *3,+053,    *4,+050,    *5,+053,    *

Example: We wish to change the temperature limit to +80 degrees

Send:

 Temp!*4,+080,* 

(no spaces)

As a response you get:    Temp**1,+053,     *2,+240,    *3,+053,    *4,

+080

,    *5,+053,   *

Relay 1 (REL-1)
Remote input burner or stove (red-black)
Operate with SMS:  

Remote

  Relay 1 draws for 5 secs.

Relay 2 (REL-2)
Remote input burner or stove (red-black
Operate with SMS:  

Remote2

  Relay 2 draws for 5 secs.

To check the system send SMS 

Status?

Response:
Status Ariterm:
Supply 12.30 volt
GSM signal: 4
Temp.Internal    +061
Temp. Flue gas   +250
Alarm1   (Msg102)     Alarm2   (Msg106)

Other

The unit remembers the last status after the power cut

Technical data

Dimensions  

105 x 80 x 30 mm

Voltage 

10 - 28 VDC

Current consumption 

Standby approx 20 mA

Inputs 

4 alarm zones NO or NC or temperatures

Outputs 

2 Closing relay outputs 1A 24V AC/DC

Temperature measurements  Internally in the unit, can be supplemented 
 

with temperature sensors on inputs 1 - 4

Temperature range 

-20 to +55 degrees C

Send SMS  

Ariterm!!01

  

at following connection:

Содержание GSM A2

Страница 1: ...INSTALLATION and OPERATING INSTRUCTIONS ARITERM GSM A2 ...

Страница 2: ...ol CC05 it must be connected according to image A and B The Remote function must be activated in the controller Service menu See manual 2 Carefully slide the SIM card into the A2 s upper edge with the chip towards you and the bevel down to the left Image C 3 Connect 9208 AC DC adapter 24Vdc to a wall socket When the voltage supply is connected the Status flashes quickly for 30 40 seconds then 1 5 ...

Страница 3: ...RITERM SWEDEN AB Installation instructions 2011 11 24 Page 3 8 Image B Image C 2 Grey Grey Brown Black Red Red Black Brown 1350 Capacitive sensor EC1808 Brown Black Blue 5292 Tank sensor Ing4 5358 Smoke gas sensor Ing2 ...

Страница 4: ...anges Alarm relay from the burner to the stove grey brown When the burner or stove is started SMS Started1 Msg100 is sent When the burner or stove is stopped SMS Stopped1 Msg101 is sent When the burner or stove stops during operational stoppage SMS Alarm1 Msg102 is sent Input 2 Ing2 COM Alarm or status changes Alarm relay from the burner to the stove grey brown When the burner or stove is started ...

Страница 5: ... limit Tmp4 Factory setting 50 setting range 10 90 Sends SMS TempAlarm Msg108 if the temperature has fallen below the temperature limit Tmp4 for more than 5 mins At first start The function is deactivated until the temperature rises above the temperature limit To modify the temperature limit Send Temp As a response you get Temp 1 053 2 240 3 053 4 050 5 053 Example We wish to change the temperatur...

Страница 6: ... 5 s Activate relay REL 1 5 s GSM Ariterm initiation ok Return SMS with Status Response Return SMS with all entered numbers Return SMS with temp With CC05 an ack nowledgement is obtained via Ing1 GSM Ariterm initiation ok Return SMS with all entered numbers Return SMS with all entered numbers Return SMS with voltage With CC05 an ack nowledgement is obtained via Ing1 With CC05 an ack nowledgement i...

Страница 7: ...it 1 started Unit 1 gives alarm for operational stoppage Information about type of operational stoppage is read off on unit display The unit alarms for too low level in pellets store Unit 2 started Unit 2 gives alarm for operational stoppage Received after initiation Unit stopped via button or Remote Comments Smoke gas temperature has exceeded set value for more than 10 min Boiler temperature has ...

Страница 8: ...tion operation and maintenance Ariterm Sweden AB s applicable warranties are not binding Ariterm reserves the right to make changes to components and specifications without prior notice Ariterm Sweden AB Flottiljvägen 15 SE 392 41 Kalmar www ariterm se ...

Отзывы: