![Aritech ATS 500A Series Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/aritech/ats-500a-series/ats-500a-series_installation-sheet_2972083007.webp)
P/N 466-
5570 (EN) • REV E • ISS 22MAR22
7 / 18
2, depending on the wire cross-sectional area, or IEC TS
60695-11-21, regardless of cross-sectional area.
Alternatively, such wires must comply with UL 2556 VW-1.
Appropriate wire cross-sectional area must be selected to
withstand 2 A current.
Use the mains connector terminal for connecting the AC mains
supply. A fixed cable or flexible mains lead to earthed mains
outlet can be used. When fixed wiring is used, insert
a dedicated all-pole circuit breaker in the power distribution
network. In all cases the mains connection must comply with
local regulations.
Always connect the building protective earthing wire and
ensure the connection is reliable. See also “Earthing” on page
8.
In case the panel is connected to the power grid using fixed
wiring, it is recommended that earth wire is longer than line
and neutral.
Do connect incoming line and neutral to mains connection
block according to the label. This assures that the line will be
protected by the mains fuse, and that service can be done by
service personnel.
Make sure that before connecting the mains power, the mains
power supply is disconnected.
When installing the mains power, use strain reliefs such as
cable ties and coupling PG16s to ensure proper wiring and
minimize the risk of wire damage during installation and use. If
product entry hole breakouts are used, it is required to also
make use of UL-V2 (or better) approved PG16 cable gland.
Refer to PG16 specification to meet minimum and maximum
cable diameters.
In all cases local regulations must be observed.
WARNING:
Electrocution hazard. To avoid personal injury or
death from electrocution, remove all sources of power and
allow stored energy to discharge before installing or removing
equipment.
Battery installation
WARNING!
Using incorrect types of batteries may cause risk
of fire, explosion or chemical leakage. Use only types of
batteries listed in “Specifications” on page 9.
To install the battery, do the following:
1. Make sure that your product settings allow you to open its
cover without starting the tamper alarm.
2. Make sure that the mains power is off and remove the
cover.
3. If necessary, remove the battery shield, unscrewing four
screws.
4. Connect the battery, sliding the product wires on the wire
connectors. Note that depending on the battery model, the
connectors can be located differently.
5. Mount the battery shield using four screws.
WARNING!
The battery shield must be mounted during normal
device operation.
In case a battery BS131 (12 V / 18 Ah) in an ATS1640 housing
is used in combination with ATS7700 PSTN expander board, it
is required to have double insulation in place. Use adequately
insulated wires for PSTN cabling, and make use of heat shrink.
Battery replacement
This product may contain one (or more) sealed, rechargeable,
BS-type lead-acid battery. Because removing a battery may
affect the product’s configuration settings or trigger an alarm,
only a qualified installer should remove the batteries.
To remove a battery:
1. Make sure that your product settings allow you to open the
cover without starting the tamper alarm.
2. Switch off the mains power, if necessary, and remove the
cover.
3. If necessary, remove the battery shield, unscrewing four
screws.
4. Disconnect the battery. Note that depending on the battery
model the connectors may be located differently.
5. Remove the battery from the holder.
Dispose of the battery as required by local ordinances or
regulations.
See the specifications for your product or contact technical
support for information on replacement batteries.
Mounting
The unit is mounted with screws or bolts through the mounting
holes in the rear section of the enclosure.
Important:
When the product is mounted to the wall,
assure that at least 3 times the weight of the product can be
supported. The product weight is the product itself plus battery
and accessories.
Ensure that the unit is mounted on a flat, solid, vertical surface
such that the base will not flex or warp when the mounting
screws and bolts are tightened.
Leave a 50 mm clearance between equipment enclosures
mounted side by side and 25 mm between the enclosure and
the sidewall.
The rechargeable battery must not be fitted until the control
panel is secured to the fixing surface. Under no circumstances
should the panel be transported with a battery fitted.
Take care that wire terminals are isolated. The use of cable
ties to neatly secure cables is recommended.
WARNING!
Use cables that comply with IEC 60332-1-2 and
IEC 60332-1-3, or IEC 60332-2-2, or IEC TS 60695-11-21, or
UL 2556 VW-1.
Use cables and connections that can withstand at least 2 A
current.
General installation guidelines
The Advisor Advanced control panels have been designed,
assembled, and tested to meet the requirements of current
Содержание ATS 500A Series
Страница 18: ...18 18 P N 466 5570 EN REV E ISS 22MAR22 ...