4.1. System
overview
4.1.1. System
design
The design of an intrinsically safe fire detection system must only undertaken by
engineers familiar with codes of practice for detection systems and hazardous area
electrical systems.
The fire detection performance of the Series 970 Intrinsically Safe range is the same as
that of its standard counterparts, the Series 950 range. Performance information given in
the Series 950 installation section is therefore applicable to the Intrinsically Safe range.
The BASEEFA certification of the Intrinsically Safe devices covers their characteristics as
components of an intrinsically safe system and indicates that they can be used with a
margin of safety in such systems. The precise way to connect and configure the system
is covered by an additional, "system'’ certification. The system parameters, given below,
detail cable parameters and permissible configurations of monitors, manual call points
and safety barriers that are certified by BASEEFA. If you wish to install a system outside
the parameters given, you cannot use the Apollo certification and must seek independent
certification from a competent certification body.
RLY
SW
SW
Typical circuit to interface opto output
relay:
Note: Line 1 and Line 2 are polarity insensitive but it is
recommended to keep L1 negative for consistency.
Switch closed
Fault
OPTO
OPTO
Series 950 loop
RLY
OPTO
OPTO
À
Normally open fault contacts
Á
Fire alarm contacts
Â
Pre-alarm contacts