900 Series V5.1: Installation Guide, February 2000
17
Figure 12: Wiring options for the Mini Switch Monitor
To install a Mini Switch Monitoring Unit:
1. Mount the switch monitor unit as required.
2. Connect the communication line to the Line 1 and Line 2 inputs. Note that the inputs
are unpolarised but it is recommended that Line 1 is kept negative for consistency.
3. There are three wiring options for the Mini Switch Monitor as shown in Figure 12.
Connect the switch contacts to the switch inputs as desired. Installing the 20 kOhm
end-of-line resistor enables the switch inputs to be monitored for open or short
circuits.
4. A software controlled remote indicator (alarm LED) output is supplied. Connect an
external LED to the remote outputs. During installation the device should be correctly
orientated, if the LED needs to be visible. The LED output drives a standard Aritech
remote indicator.
Fire contacts
Red
Black
Yellow
Green
White -
Remote LED
LINE
2*
LINE
1*
20 kOhm ± 10% 1/3 W
1 kOhm
fire contact
Fire and fault contacts
Red
Black
Yellow
Green
White -
LINE
2*
LINE
1*
1 kOhm
fire contact
20 kOhm
± 10% 1/3 W
Fault contact
Fire, pre-alarm and fault contacts
Red
Black
Yellow
Green
Violet +
White -
LINE
2*
LINE
1*
Remote LED
Fault connection
20 kOhm
± 10% 1/3 W
1 kOhm
10 kOhm
Fire
contact
Pre-alarm
contact
* L1 and L2 are polarity insensitive but it is
recommended to keep L1 negative for continuity.
Remote LED