16
1X-E4 Series Operation Manual
Resetting the control panel
Note:
Investigate all alarms and system faults before resetting the control panel.
To reset the control panel and clear all current system events, press the Reset
button. System events that have not been resolved continue to be highlighted
when the reset process ends.
Stopping or restarting sounders
To stop the sounders, press the All Sounders Stop button. To restart stopped
sounders, press the All Sounders Start button and the Confirm button. A steady
All Sounders Start LED indicates that all sounders are active (sounding).
Note:
Sounder functionality is defined by your system configuration settings and
stopped sounders that were activated by a fire alarm may restart automatically if
another fire alarm event in a new zone is detected. Contact your fire alarm and
evacuation system installation or maintenance contractor to confirm your
configuration details.
Enabling or disabling a configured fire routing delay
To enable a configured fire routing delay, press the Fire Routing Delay button. To
disable the delay, press the button again.
Note:
Availability of this feature is subject to configuration and its functionality
may vary for each zone. Contact your fire system installation or maintenance
contractor to confirm your configuration details.
Enabling or disabling a configured extended fire routing delay
If configured, the extended fire routing delay is enabled or disabled at the same
time as the standard fire routing delay.
The extended fire routing delay becomes the active delay when sounders are
stopped (by pressing the All Sounders Stop button) and remain stopped when
the standard fire routing delay time has elapsed.
The extended fire routing delay also becomes the active delay when an extended
fire routing delay switch is activated while the standard fire routing delay elapses.