Chapter 3: Configuration and commissioning
1X-X3E Series Installation Manual
59
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Display
Description
Mixed zone. The control panel automatically
distinguishes between an automatic alarm (generated by
a detector) and a manual alarm (generated by a manual
call point fitted with a 100 Ω resistor).
This option is not available to zones configured in the
extinguishing area.
Automatic zone. All fire alarms are treated as reported
by a detector, even if the fire alarm is reported by a
manual call point in the zone.
This is the option applied for zones configured in the
extinguishing area.
Manual zone. All fire alarms are treated as reported by a
manual call point, even if the fire alarm is reported by a
detector in the zone.
This option is not available to zones configured in the
extinguishing area.
Changing user level passwords
Use the corresponding menu option (shown below) to change the default user
level passwords.
Operator user level password
Basic installer user level password
Advanced installer user level password
To change the first two digits of a user level password:
1. Set the display for the desired user level password, and then press Enter.
2. Set the display as shown below, and then press Enter.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
Содержание 1 3E Series
Страница 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Страница 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Страница 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Страница 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Страница 113: ......
Страница 114: ......