Chapter 3: Configuration and commissioning
76
1X-X3E Series Installation Manual
Event
Response time
Fire routing fault
Less than 30 seconds
Earth fault
Less than 100 seconds
Battery charger fault
Less than 100 seconds
No batteries found fault
Less than 3 minutes
Mains fault
Less than 3 minutes
Low battery fault
Less than 100 seconds
Fuse/protection fault
Less than 3 minutes
System fault
Less than 100 seconds
Battery high resistance fault
Less than 4 hours