39
commissioning
Test function and combustion analysis
The boiler has two pressure test points to measure
the combustion gas temperature, the combustive air
and the concentrations of O and CO on the outside
of the flue gas header.
To access these pressure test points, unscrew the
screw which holds the blanking cover and its seal
together.
Checking the gas setting
To carry out combustion analysis, the test function
must be activated.
Maximum gas flow combustion analysis
Activate the test function at the maximum heating
power, press the
+
button.
Wait for the boiler to stabilise before carrying out the
combustion analysis. Check the CO value according
to the table opposite.
N.B: when the front combustion chamber panel is
open, the CO2 value drops by 0.3%.
If the values taken differ from the table, adjust the gas
valve following the procedure described below.
Adjust the CO content to
± 0.2
by turning setting
screw
50
(
2.5 mm allen key
)
- tighten to lower the CO value
- unscrew to increase the CO value
Set the content by turning the screw about a 1/4 of a
turn then wait after each change for approximately 1
minute for the CO value to stabilise, then repeat.
Minimum gas flow combustion analysis
Activate the test function at minimum power by
pressing the
-
button.
Wait for the boiler to stabilise before carrying out the
combustion analysis. Check the CO value according to
the table above.
Important: do not remove silencer
13
N.B: when the combustion chamber is open, the
CO2 value drops by 0.3%.
If the values taken differ from the table, adjust the gas
valve following the procedure described below.
To adjust the CO value, remove cap
2
, adjust the CO
content to
± 0.2
by turning setting screw
51
(
4 mm al-
len key
)
- unscrew to lower the CO value
- tighten to increase the CO value
Set by turning the screw about a 1/4 of a turn then wait
after each change for approximately 1 minute for the
CO value to stabilise, then repeat.
Once the settings and analyses are complete, exit test
mode, and reposition the blanking cover and its seal
correctly.
Maximum or
minimum CO
1 kW
18 kW
4 kW
CO
(%)
G0
9.0 ± 0.
9. ± 0.
9.3 ± 0.
G31
10. ± 0.
10.3 ± 0.
10. ± 0.
8
50
Only a 2.5 mm allen
key must be used. Do
not use a screwdriver
2
Only a 4 mm allen key
must be used. Do not
use a screwdriver
51
Test function
The PCB allows the appliance to be forced to minimum
or maximum power.
Activate the test function by pressing the
Reset
button for 5 seconds, the boiler switches to maximum
heating power, the following appears on the display:
To select the function at maximum domestic hot
water, press the
button, the following appears
on the display :
To select the function at minimum domestic hot
water, press the
button, the following appears
on the display :
The function is automatically deactivated after 10
minutes or by pressing the
Reset
button.
Note: the appliance can be forced to minimum or
maximum power from menu 7 (see the section on
the display - setting - diagnostics menu).
WARNING!
By activating the test function, the
temperature of the water sent to the installation is
limited to 88°C; caution is therefore required with
regard to low-temperature installations.