45
SETTINGS - ADJUSTMENT - PROBLEM IDENTIFICATION MENUS
5
3
DIAGNOSTICS
5
3
4
Zone 2 heat request
0 = OFF
1 = ON
6
ZONE 3 PARAMETER
6
0
ZONE 3 TEMPERATURE SETTING
6
0
2
Heating fixed temperature setting
“Heating fixed temp”
from 35 to 82 °C
(high temperature - para. 420
=1)
70
Activated only with temperature
control and fixed temperature
(see 621)
from 20 to 45 °C
(high temperature - para. 420
=0)
20
6
2
ZONE 3 SETTING
6
2
0
Heating appliance temperature value setting 0 = from 20 to 45°C
(low temper ature)
1 = from 35 to 85°C
(high temperature)
1
select in the appliance type
base
6
2
1
Basic heating control type selection type
depending on the peripheral devices
connected
0 = fixed flow temperature
1 = device On/Off
2 = NOT PRESENT
3 = external sensor only
4 = NOT PRESENT
1
To activate heating control,
press the AUTO button. The
display lights up the AUTO
symbol
6
2
2
Slope
from 0_2 to 0_8
(low temperature)
from 1_0 to 3_5
1_5 (high temperature)
- see graph on page 42
If the external sensor is used, the boiler calculates the most suitable heating flow temperature taking the external
temperature and the type of appliance into account.
The type of curve must be chosen according to the type of appliance radiator and the heat losses present in the building.
6
2
3
Parallel curve shift Zone 2 Offset
from - 7 to + 7 (low temperature)
0
from - 14 to + 14 (high temperature)
To adapt the thermal curve to the appliance requirements, it is possible to perform a parallel shift of the curve in order
to alter the calculated flow temperature and therefore the ambient temperature.
By accessing this parameter or pressing the buttons 12 the curve can be shifted in a parallel manner as indicated in the
figure shown below.
The value is indicated on the display:
- from -7 to +7 (low temperature)
- from -14 to +14 (high temperature)
Each step represents a flow temperature increase/decrease of 1°C in relation to the
set-point value.
6
2
4
Compensation
from 0 to 20
20
if setting = 0, the temperature
taken from the ambient sensor
does not affect the calculation
of the setting. If setting = 20,
the temperature taken has
maximum influence on the
setting.
6
2
5
Zone 3 heating MAXIMUM temperature
setting
from 35 to 85 °C
82
if parameter 620 = 1
from 20 to 45 °C
45
if parameter 620 = 0
6
2
6
Zone 3 heating MINIMUM temperature
setting
from 35 to 85 °C
35
if parameter 620 = 1
from 20 to 45 °C
25
if parameter 620 = 0
6
3
DIAGNOSTICS
6
3
4
Zone 3 heat request
0 = OFF
1 = ON
8
SERVICE PARAMETERS
8
0
BOILER STATISTICS-1
8
0
0
Number of diverter valve cycles (n x10)
8
0
1
Time of circulator on (h x 10)
8
0
2
Number of boiler circulator cycles (n x10)
menu
sub-menu
Parameter Description
value
default setting