Soft light adjustment
1
1
The soft light can be adjusted between the maximum power
(shown on the display as “00”, i.e. 100%) and the minimum
power (shown on the display as “01”, i.e. 1%). The boiler is
factory set to a value which is suitable for the ignition with any
type of gas (approx. 33%).
The value set expressed as a percentage, can be displayed and
adjusted as indicated in Section 3.6.1 (parameter 1)
Maximun Heating Power adjustment
2
2
The maximum heating power can be adjusted to between the
maximum power allowed by the boiler (24kW) and the minimum
power (8kW). The value is factory set to 70% of the maximum
power.
The value set (expressed as a percentage) canbe displayed and
modified as illustrated in Section 3.6.1 (parameter 2).
The display shows the value between 100% ("00" on the display)
and 1% ("01") of this interval.
Ignition Delay adjustment
3
3
The ignition delay can be adjusted to between 0 and 7
minutes. The delay is factory set to 2 minutes.
The value set can be displayed and modified as illustrated in
Section 3.6.1 (parameter 3)
Maximun Central Heating temperature
4
4
This parameter allows the setting of the maximum temperature for
the central heating circuit. The value is factory set at 82°C and
can be adjusted as illustrated in Section 3.6.1 (parameter 4).
Minimum Central Heating temperature
5
5
This parameter allows the setting of the minimum temperature for
the central heating circuit. The value is factory set at 42°C and
can be adjusted as illustrated in Section 3.6.1 (parameter 5).