93 / GB
MENU
SUB-MENU
PARAMETER DESCRIPTION
RANGE
DEFAULT
17
5
2
Comfort Function
Disabled
Time based
Always Active
HC-HP
HC-HP 40°C
Green Mode
Green Mode
17
5
3
Max HP charging time
30 ÷ 240 min.
120 min.
17
5
4
Antilegionella Function
ON - OFF
ON
17
5
5
Antilegionella start time [hh:mm]
[00:00-24:00]
01:00
17
5
6
Thermal Cleance Cycle frequency
24h ÷ 481 (= 30 days)
481 (= 30 days)
17
6
Manual Mode - 1
17
6
0
Manual mode activation
OFF - ON
OFF
17
6
1
HP circulator control
OFF
Low Speed
High Speed
OFF
17
6
2
Diverter valve control
DHW
CH
DHW
17
6
3
Diverter valve COOLING
CH
COOLING
CH
17
6
4
Auxiliary circulator
OFF - ON
OFF
17
6
5
Output AUX 1/2 contact
OFF - ON
OFF
17
6
6
Test resistance 1
OFF - ON
OFF
17
6
7
Test resistance 2
OFF - ON
OFF
17
6
8
Test resistance 3
OFF - ON
OFF
17
6
9
Anode output
OFF - ON
OFF
17
7
Manual Mode - 2
17
7
0
Manual mode activation
OFF - ON
OFF
17
7
1
Force Hp Heat
OFF - ON
OFF
17
7
2
Force Hp Cool
OFF - ON
OFF
17
7
3
Rating heating mode
OFF - ON
OFF
17
7
4
Rating cooling mode
OFF - ON
OFF
17
7
5
Compressor frequency setting
18 ÷ 120 Hz
120 Hz
17
7
6
Fan 1 rpm setting
0 ÷ 1000 rpm
0 rpm
17
7
7
Fan 2 rpm setting
0 ÷ 1000 rpm
0 rpm
17
7
8
TDM aux output (NOT used)
OFF - ON
OFF
17
7
9
Ext Unit Electric Heater Activation
OFF - ON
OFF
17
8
Test & Utilities
17
8
0
Air-purge function
OFF - ON
OFF
17
8
1
Floor drying cycle
OFF
Functional Heating
Curing Heating
Functional H Curing Heating
Curing H Functional Heating
Manual
OFF
17
8
2
Floor drying total Remaining Days
only read
17
8
3
Floor drying functional Remaining Days
only read
17
8
4
Floor drying curing Remaining Days
only read
17
8
5
Refrigerant Recover
OFF - ON
OFF
17
8
6
Resistance Power Rating Configuration
2+2(+2) kW
2+4 kW
2+2(+2) kW
17
8
7
Defrost
OFF - ON
OFF
17
8
8
TDM Flow Sensor Type
Self-Recognition
DN 15
DN 20
Self-Recognition
17
9
Energy Manager Statistics
only read
17
9
0
HP Running hours (h/10)
only read
17
9
1
HP On cycles (n/10)
only read
17
9
2
Resistor Stage 1 running hours (h/10)
only read
17
9
3
Resistor Stage 2 running hours (h/10)
only read