71 / GB

 

 

ATTENTION:

The electrical connections shall be made after completing all hydraulic connections.

         

ATTENTION:

After Power OFF of the external unit, is needed to wait at least 5 minutes before turn it ON again.

The internal and external units must be powered separately according to what is indicated on the tables. Between the internal and 
external units should also be made a EBUS 2 connection. This connection may be made through the use of a cable of reduced section 
(recommended section 0,75 mm

2

). Do not let this cable walk along a power connection.

Electrical circuit

•  Check that the voltage and frequency of power supply from the network coincide with the data shown in the data plate of the 

appliance (see table)

•  In order to ensure greater security, the main electrical system should be checked by a qualified technician before proceeding with 

the installation (see note).

•  It is recommended to verify the presence of surge protection devices (SPD), in compliance with the national regulations in force (IEC 

60364 and its national harmonizations), in the power supply line and the presence of residual-current devices and magneto-thermal 
switches on the electrical board which powers the external and internal unit separately. However, it is recommended to install an 
SPD even if the risk level resulting from CRL calculation is low.

•  The electrical system must meet all the legal requirements in force.
•  The manufacturer is not liable for any damage caused by installation with improper grounding or abnormalities in the electrical 

system.

•  Check that the installation is adequate to support the power consumption of the installed units, indicated on the data plate of the 

product.

•  The electrical connections must be carried out with the aid of a fixed supply connection (do not use mobile sockets) and equipped 

with a bipolar switch, having a distance between the contacts of at least 3 mm.

•  It is essential to connect the appliance to a correctly grounded electrical circuit, as to ensure the safety of the installation.
•  It is also forbidden to use for the grounding of the system and the hydraulic connection of the heating tubes.
•  The manufacturer is not liable for any damage caused by installation with improper grounding or implant level anomalies electric.
•  Connect the power cord to a 230V-50Hz or (400V-50Hz), verifying the polarizations of the L-N (or L1, L2, L3, N) connection and the 

connection to the earth. The section of the used cables must comply with the power of the installation (see plate characteristic). 

•  For the electrical connection of the installation, you shall not use power strips, extension cords and adapters. It is also prohibited to 

use the hydraulic pipes and heating system pipes to ground the installation (see table of electrical connections).

The section of the power supplier’s cables, showed in a table, must be considered as minimal.
The system is not protected against lightning. If you need to change the fuses, use fast fuses.

Warning: Before obtaining access to terminals, all supply circuits must be disconnected.

ELECTRICAL WIRING

TABLE OF ELECTRICAL CONNECTIONS

EXTERNAL UNIT

40 M EXT 50 M EXT 70 M EXT 70 M-T EXT 90 M-T EXT 110 M-T EXT 90 M  EXT 110 M EXT

Nominal running current / phase

A

6.4

8

11

3.8

6

7,3

18

22

Maximum running current / phase

A

9

11

16

5.4

8,4

10

23

27

Cutout - Circuit Breaker size

A

12-C type
13-C type

16-C type

20-C type

10-C type

12-C type
13-C type

13-C type

32-C type

32-C type

Differential Circuit Breaker size  
(RCCB)

mA

30 - F or B type

30 - B type

30 - F or B type

Starting current

A

< 3

Nominal Voltage

V

230

230

230

400

400

400

230

230

Operating voltage limits

V

216-243

216-243

216-243

376-424

376-424

376-424

216-243

216-243

Cos phi

> 0,9

Power supply cable

Reference

H07RN-F

Min. cables 

section

3G2,5

3G4

3G4

5G2,5

5G2,5

5G2,5

3G6

3G6

Max diameter 

[mm]

14

16.2

16.2

17

17

17

18

18

Recommended 

cables section

3G4

3G4

3G4

5G4

5G4

5G4

3G6

3G6

Max diameter 

[mm]

16.2

16.2

16.2

19,9

19,9

19,9

18

18

Communication cable

Reference

H05RN-F

Cables section

2 x 0,75 mm

2

Содержание 3300949

Страница 1: ...IT NIMBUS PLUS M NET ISTRUZIONI TECNICHE PER L INSTALLAZIONE E LA MANUTENZIONE TECHNICAL INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE OK 420000453002 3300949 3300950 3300951 3300952 3300953...

Страница 2: ...ianto 17 Vaso d espansione 17 Preparazione alla messa in funzione dell impianto del circuito di riscaldamento raffrescamento 17 Installazione vaschetta raccogli condensa 17 Collegamenti idraulici Conn...

Страница 3: ...odotto o dal mancato adeguamento dell installazione alle istruzio ni fornite in questo manuale Installare l apparecchio su base solida non soggetta a vibrazioni Rumorosit durante il funzionamento Non...

Страница 4: ...Proteggere con adeguato materiale l ap parecchio e le aree in prossimit del luogo di lavoro Danneggiamento dell apparecchio o di og getti circostanti per proiezione di schegge colpi incisioni Movimen...

Страница 5: ...del sistema mediante un ulteriore cir cuito aria Non posizionare contenitori per liquidi n altri oggetti sulle unit interna ed esterna In prossimit dell installazione non devono es sere posizionati og...

Страница 6: ...fornitura dell acqua non superi i 5 bar In caso contrario provvedere all installazione di un riduttore di pressione Per evitare congelamenti nelle tubazioni qualora si rile vino condizioni di rischio...

Страница 7: ...nsultare il Catalogo Prodotti UNIT ESTERNA L unit esterna fornita uno dei modelli seguenti NIMBUS 40 M EXT NIMBUS 50 M EXT NIMBUS 70 M EXT NIMBUS 70 M T EXT NIMBUS 90 M EXT NIMBUS 90 M T EXT NIMBUS 11...

Страница 8: ...tore automatico 8 Resistenza elettrica supplementare 9 Sonda di temperatura mandata all impianto 10 Termostato di sicurezza a riarmo manuale 11 Termostato di sicurezza a riarmo auto A Mandata acqua ca...

Страница 9: ...tare 2kW 2Kw UNIT INTERNA WH M 1Z 2Z Dimensioni e Pesi mm Vista complessiva A Mandata acqua calda fredda dall unit esterna G 1 M B Ritorno acqua fredda calda all unit esterna G 1 M C Mandata acqua cal...

Страница 10: ...idraulico 14 Degasatore automatico 15 Vaso espansione 16 Degasatore automatico 17 Sonda di temperatura mandata all impianto di riscaldamento raffrescamento 18 Termostato di sicurezza a riarmo manuale...

Страница 11: ...scarico 2 Valvola di sicurezza 3 bar 3 Manometro 4 Sonda temperatura mandata ZONA1 5 Sonda temperatura ritorno ZONE 1 6 Sonda temperatura mandata ZONE 2 7 Sonda temperatura ritorno ZONE 2 8 Circolato...

Страница 12: ...ia di OFF flussimetro l h Soglia di ON flussimetro l h Flusso nominale l h 40 M 348 390 640 50 M 348 390 800 70 M 70 M T 486 540 1120 90 M 90 M T 630 702 1440 110 M 110 M T 768 852 1755 TABELLA FREQUE...

Страница 13: ...esposizione diretta ai raggi solari Rimuovere il coperchio fig A ed installare la sonda utilizzando il tassello e la vite in dotazione fig B Effettuare il collegamento tramite un cavo da 2x0 5 mm2 Lu...

Страница 14: ...presenza di differenziali e interruttori di sicurezza correttamente dimensionati collegati all unit esterna Verifica che tutti i tappi di sfiato dell aria siano aperti NOTA Le caratteristiche e i codi...

Страница 15: ...uno schermo e verificarne la corretta funzionalit 1 Procedura di apertura dei passaggi per collegamenti Per consentire il passaggio dei cavi rimuovere con l aiuto di un cacciavite le parti pretagliat...

Страница 16: ...l sistema necessario rispettare le distanze minime per l installa zione come illustrato nelle figure sottostanti 150 150 500 MIN 350 1 Rimozione pannello frontale e fissaggio modulo Rimuovere le viti...

Страница 17: ...curarsi che il vaso di espansione abbia una capacit adeguata al quantitativo di acqua presente nell im pianto Prima del riempimento assicurarsi che la pressione di caricamento sia pari ad 1 bar 4 Prep...

Страница 18: ...nto la pressione della rete idrica non superi i 5 bar in caso contrario prevedere un riduttore di pressione all ingresso dell impianto sia previsto un disconnettore dotato di rubinetto tra acqua d imp...

Страница 19: ...n vaso di espansione due circolatori ed una valvola miscelatrice per gestire 2 zone riscaldamento raffrescamento a temperature diverse Legenda 1 Unit Interna 2 Unit esterna 3 Sonda esterna 4 Zona risc...

Страница 20: ...ONE WH L Il circolatore dell unit esterna spinge l acqua verso il sistema di riscaldamento raffrescamento L unit interna provvista di tre resistenze elettriche supplementari da 2kW ed un vaso di espan...

Страница 21: ...i elettriche dovranno essere eseguite con l ausilio di un supporto fisso non utilizzare prese mobili e dotato di un interruttore bipolare dotato di una distanza tra i contatti di almeno 3 mm indispens...

Страница 22: ...trica V ph Hz 230 1 50 400 3 50 230 1 50 400 3 50 230 1 50 400 3 50 Campo tensioni ammissibili V 196 253 340 440 196 253 340 440 196 253 340 440 Potenza nominale assorbita kW 4 4 4 4 6 6 Corrente mass...

Страница 23: ...vi che si trovano sulla staffa C Collegare il cavo di comunicazione alle due unit seguendo le indicazioni presenti sulle morsettiere interna ed esterna In accordo con le istruzioni di installazione tu...

Страница 24: ...Ingresso a 230V Selezionare la modalit operativa tramite il parametro 17 1 0 EDF tariffa elettrica ridotta applicando in segnale a 230V all ingresso della morsettiera il bollitore sanitario riscaldat...

Страница 25: ...interruttore generale NOTA Si raccomanda di verificare la presenza di dispositivi di protezione da sovralimentazioni SPD nella linea MT e la presenza di interruttori di sicurezza differenziali e di in...

Страница 26: ...SS4 1BC2 R S CN1 230V 50hz L CNX2 N N CN11 L 1 Program LINE OPTIONAL P INVERTER 1 PH TDM BOARD EHEHSt1St1 25 mH 13A B T 25 mH 13A L1 L2 L3 N PE 25 mH 13A W Magnetic ring 3 tours R1250RJA N V T S R Ma...

Страница 27: ...23 POWER Compressor 4Way Valve N N CN10 CN11 Electric Line 3P N PE 400VAC 50Hz LE105 1325 LE105 1325 LE105 1325 FLOW METER TR EWT LWT CN7 CN8 CN13 CN9 B A GND CN3 power pump CN4 EH EH St1 St1 PWM FLOW...

Страница 28: ...ZIONE TRIFASE RIMUOVERE SOLO LE PIASTRE METALLICHE INSERITE TRA LE FASI L1 L2 E L3 B T GY BU BU BU BU RD WH BU BN GY GY GY OR BU OR BU LED UI CN1 VALVE 1 VALVE 2 PUMP 1 FUSE 230V SERIAL ANODE PWM2 PWM...

Страница 29: ...1 1 1 1 SYSTEM INTERFACE ENERGY MANAGER PRESSURE SWITCH ELECTRICAL RESISTANCE RD RD BK BN GN GN GY GY RD RD BU BU BU OR BK YE YE BN BU BN BN BN BN BU BU BN BU BU YE GN YE GN RD GN GY YE PI L N BK BK...

Страница 30: ...S INTERNES ZONE MANAGER L N P2 L N 2 2 TA1 TA2 TA3 SE BUS BUS ST2 3 3 ST3 A1 A1 AUX1 230V L N N L P3 PWM 2 PWM 1 P1 B T B T BK BK M1 BK BK R1 BK BK M2 BK BK R2 B T GY BU BU BU BU RD WH BU BN GY GY GY...

Страница 31: ...ve essere effettuato prima del collegamento alla linea BUS prima di collegare i fili alla base dell interfaccia di sis tema far scorrere la linguetta di protezione del connet tore e sollevarla fig 1 c...

Страница 32: ...atura ambiente desiderata deroga Temperatura esterna Funzione AUTO attiva Funzione VACANZA attiva Riscaldamento attivo Sanitario attivo Segnalazione errore Menu completo Prestazioni sistema Opzioni sc...

Страница 33: ...tta a cui associata l inter faccia di sistema ruotare la manopola e selezionare Interfaccia di sistema locale Premere il tasto OK Ruotare la manopola ed impostare la zona corretta Premere il tasto OK...

Страница 34: ...di riscaldamento e acqua cadla sanitaria ed il raffrescamento vengono garantiti con il solo utilizzo della pompa di calore 17 2 1 Termoregolazione Attiva disattiva la funzione di termoregolazione 17...

Страница 35: ...ne manuale dei componenti di sistema circolato ri valvole deviatrici resistenze etc Premere il tasto OK Ruotare la manopola e selezionare 17 7 MODO MANUALE 2 17 7 1 Forza la pompa in riscaldamento Att...

Страница 36: ...RORI Visualizza gli ultimi 10 errori 17 17 RESET MENU Cancella impostazioni di fabbrica 19 CONNETTIVIT Premere il tasto OK Dopo aver verificato la disponibilit del servizio Ariston Net nel proprio pae...

Страница 37: ...a ambiente bisogna verificare il valore della stessa 4 2 3 Spostamento Parallelo Premere il tasto OK Ruotare la manopola ed impostare il valore pi idoneo Premere il tasto OK per confermare IMPORTANTE...

Страница 38: ...temperatura ambiente aumenta questo indica che bi sogna impostare una curva con minore pendenza 2 la temperatura ambiente diminuisce questo indica che bisogna impostare una curva con maggiore pendenz...

Страница 39: ...commutazione estate inverno 0 600 300 min 4 2 Impostaz Zona1 4 2 0 Range Temperatura Bassa Temperatura Alta Temperatura Alta Temperatura 4 2 1 Selezione Tipologia Termoregolazione Temperatura Fissa di...

Страница 40: ...24 C Cool 5 0 1 Temperatura Notte 10 30 C 13 C 5 0 2 Temperatura Zona 2 par 5 2 5 5 2 6 20 LT 40 HT 5 0 3 Temperatura Antigelo zona 2 15 C 5 C 5 1 Funzione estate inverno automatico 5 1 0 Attivazione...

Страница 41: ...Esterna ON OFF 5 5 3 Curva Termoregolazione 18 33 FC 0 30 Pavimento 25 FC 10 Pavimento 5 5 4 Spost Parallelo 2 5 C 2 5 C 0 C 5 5 6 Max T MinT 12 C FC MinT 23 C Pavimento 12 C FC 23 C Pavimento 5 5 7 M...

Страница 42: ...a SG Ready 1 External switch off signal Assente 17 1 1 HV IN 2 Non definito Assente Parzializzazione del carico SG Ready 2 Assente 17 1 2 HV IN 3 Non attivo Integrazione fotovoltaico attiva Non attivo...

Страница 43: ...n attivo Attivo Non attivo 17 4 1 Impostaz Ritardo Accensione Raff 0 10 min 0 min 17 4 2 Comp Temp mandata PC Raffr 10 0 C 0 C 17 5 Sanitario 17 5 0 Temperatura Comfort Sanitario 35 65 C 55 C 17 5 1 T...

Страница 44: ...ronto posa Pronto posa Funzionale Manuale OFF 17 8 2 Tot gg restanti asciugatura massetto solo lettura 17 8 3 gg restanti asciugatura funzionale solo lettura 17 8 4 gg restanti asciugatura pronto posa...

Страница 45: ...0 1200 l min sola lettura 17 11 4 Stato flussostato Aperto Chiuso sola lettura 17 11 5 Spegnimento di protezione del compressore sola lettura 17 11 6 Pressione evaporatore sola lettura 17 11 7 Pressi...

Страница 46: ...ura 17 14 8 Stato Ingresso HV IN 3 sola lettura 17 14 9 Ingresso AUX 1 Aperto Chiuso sola lettura 17 15 Diagnostica scheda 2 Uscite 17 15 0 Cancella impostazioni di fabbrica sola lettura 17 15 1 Stato...

Страница 47: ...uffer 20 0 Configurazione 20 0 0 Attivazione carica buffer OFF ON OFF 20 0 1 Tipologia di carica del buffer Carica parziale 1 sensore Carica completa 2 sensori Carica parziale 1 sensore 20 0 2 Isteres...

Страница 48: ...etti circostanti Informazioni per l utilizzatore Informare l utilizzatore sulle modalit di funzionamento del sistema installato In particolare consegnare all utilizzatore il manuale d istru zioni info...

Страница 49: ...Funzione non selezionata tramite il parametro 17 1 0 9 42 HV IN2 non definito Funzione non selezionata tramite il parametro 17 1 1 9 44 Sovratemperatura in raffrescamento Controllare il flusso nel cir...

Страница 50: ...9 Configurazione d ingresso SG ready non com pletato Solo uno dei parametri 17 1 0 o 17 1 1 impostato come input SG Ready 1 ON OFF 2 microswitch LISTA ERRORI UNIT ESTERNA ERRORE TDM DESCRIZIONE RESET...

Страница 51: ...e interna tra micro controllori della scheda x 53 Errore di comunicazione con la scheda di controllo IDU x 54 sovracorrente uscita inverter x x 55 sovratemperatura dissipatore inverter x x ERRORE INVE...

Страница 52: ...13 Potenza elettrica massima 14 Pressione massima circuito frigorifero 15 Pressione minima circuito frigorifero 16 Luogo di fabbricazione 17 Indice di protezione IP 18 Certificazione 19 Indirizzo di...

Страница 53: ...ont panel 66 Safety valve drain 66 Flling system 67 Expansion vessel 67 Preparing for startup of the heating cooling system 67 Hydraulic connections on indoor module 68 Final installation of the whole...

Страница 54: ...ical cur rent passing through undersized cables Protect all connection pipes and wires in order to prevent them from being damaged Electrocution caused by contact with live wires Flooding caused by wa...

Страница 55: ...and equipment in such a way as to make movement easy and safe avoiding the formation of any piles which could yield or collapse Damage to the appliance or surrounding objects from shocks knocks incisi...

Страница 56: ...o the retailer when a new replacement product is purchased The user is responsible for the disposal of the product at the end of its life at an appropriate waste disposal centre The waste disposal cen...

Страница 57: ...ons mm EXTERNAL UNIT Weight 40 M EXT 79 50 M EXT 79 70 M EXT 104 70 M T EXT 121 90 M EXT 150 90 M T EXT 150 110 M EXT 150 110 M T EXT 150 EXTERNAL UNIT As external unit one of the following models is...

Страница 58: ...ooling 10 Safety thermostat manual switch 11 Safety thermostat automatic switch INTERNAL UNIT WH L M 1Z Weights and dimensions mm Overall view A Hot cold water flow from the external unit G 1 M B Cold...

Страница 59: ...w INTERNAL UNIT WH M 1Z 2Z Weights and dimensions mm Overall view A Hot cold water flow from the external unit G 1 M B Cold hot water return to the external unit G 1 M C Hot cold flow to the installat...

Страница 60: ...13 Hydraulic separator 14 Automatic air purge 15 Expansion vessel 16 Automatic air purge 17 Temperature sensor flow to the installation heating cooling 18 Safety thermostat manual switch 19 Safety th...

Страница 61: ...Safety thermostat automatic switch 16 Heating back up resistance 2kW 2kW 17 Pressure switch WH M 2 ZONE ONLY HEAT A Flow water temperature C B External air temperature C Restrictions of cooling operat...

Страница 62: ...al hoo kup refer to Electrical circuit Warning in case of installation of thermostatic valves on all terminals or zone valves install a bypass to ensure the mini mum operating flow rate System Size Fl...

Страница 63: ...rom the ground and away from direct sunlight Remove the cover and install the sensor using the rawl plug and screw provided Perform connection using a 2x0 5 mm2 wire Maximum connection length 50 m Con...

Страница 64: ...cted to the external unit Choice of placement Avoid a mounting where the ODU is surrounded by wal ls Avoid a mounting in sinks Cold air sinks down and by that air short circuit could occur Avoid posit...

Страница 65: ...een and verify the proper positioning and functioning 1 Opening procedure for lateral passages To allow the passage of cables remove with the help of a screwdriver the precut parts A of the chassis of...

Страница 66: ...tallation as shown in the figures below To position the unit pro perly use the template provided and a spirit level 150 150 500 MIN 350 1 Fitting the tray and removing the front panel Remove the screw...

Страница 67: ...ng systems 8 l Make sure that the expansion vessel has a capacity appropriate to the quantity of water present in the installation Prior to filling make sure that the filling pressure is equal to 1 ba...

Страница 68: ...ter circuit pressure never exceeds 5 bar otherwise install a pressure reducer at the system s intake a disconnector with cock is installed between the system and the domestic water circuit if present...

Страница 69: ...lso has two 2 kW heating elements and an expansion vessel two circulation pumps and a mixer valve to supply two heating cooling zones at different temperature Legend 1 Internal unit 2 External unit 3...

Страница 70: ...ernal unit and the heating cooling system in positioned in the external unit The unit also has three 2 kW heating elements and an expansion vessel Legend 1 Internal unit 2 External unit 3 External sen...

Страница 71: ...to connect the appliance to a correctly grounded electrical circuit as to ensure the safety of the installation It is also forbidden to use for the grounding of the system and the hydraulic connectio...

Страница 72: ...230 1 50 400 3 50 230 1 50 400 3 50 Admitted voltages field V 196 253 340 440 196 253 340 440 196 253 340 440 Rated power input kW 4 4 4 4 6 6 Max current A 19 1 9 6 19 1 9 6 30 9 6 Thermal cutout Cir...

Страница 73: ...respective numbers on the terminal block of indoor and outdoor unit According to the installation instructions all devices for disconnection from the power supply mains must have a contact opening 4 m...

Страница 74: ...he input the tank charge is enabled according to the DHW modes HC HP or HC HP 40 C selectable by the parameter 17 5 2 SG Ready 1 input signal nr 1 for the SG Ready standard see paragraph SMART GRID RE...

Страница 75: ...r and outdoor unit put back both panels of the respective units Electrical connections between internal and external unit Before any work on the system shut off the power at the breaker NOTE It is str...

Страница 76: ...0 SS4 1BC2 R S CN1 230V 50hz L CNX2 N N CN11 L 1 Program LINE OPTIONAL P INVERTER 1 PH TDM BOARD EHEHSt1St1 25 mH 13A B T 25 mH 13A L1 L2 L3 N PE 25 mH 13A W Magnetic ring 3 tours R1250RJA N V T S R M...

Страница 77: ...423 POWER Compressor 4Way Valve N N CN10 CN11 Electric Line 3P N PE 400VAC 50Hz LE105 1325 LE105 1325 LE105 1325 FLOW METER TR EWT LWT CN7 CN8 CN13 CN9 B A GND CN3 power pump CN4 EH EH St1 St1 PWM FLO...

Страница 78: ...BU LED UI CN1 VALVE 1 VALVE 2 PUMP 1 FUSE 230V SERIAL ANODE PWM2 PWM1 CN7 SW1 CN6 CN1 CN4 CN13 CN9 CN5 CN14 CN2 CN8 EBUS EBUS C35 PUMP 2 CN10 CN16 CN12 CN11 F1 1 1 1 1 4 3 1 6 1 1 1 1 1 1 1 SYSTEM IN...

Страница 79: ...N BU BK BU BN BN BN SAFETY THERMOSTAT WH WH BK BK BN BU N N L 3 2 3 1 L L AVVERTENZA PRIMA DI ACCEDERE AI MORSETTI SCOLLEGARE TUTTI I CIRCUITI DI ALIMENTAZIONE COLLEGAMENTO ALIMENTAZIONE MONOFASE NON...

Страница 80: ...2 ST 1 LED UI CN1 VALVE 1 VALVE 2 PUMP 1 FUSE 230V SERIAL ANODE PWM2 PWM1 CN7 SW1 CN6 CN1 CN4 CN13 CN9 CN5 CN14 CN2 CN8 EBUS EBUS C35 PUMP 2 CN10 CN16 CN12 CN11 F1 1 1 1 1 4 3 1 6 1 1 1 1 1 1 1 SYSTE...

Страница 81: ...g the remote control Wall installation The Sensys system interface must be fitted to the wall before the BUS line is connected connect the pair of wires to the connector fig 1 open up the holes requir...

Страница 82: ...OLIDAY function enabled Central heating active Domestic hot water active Error indication Menu System performance Screen setting Floor Heating Circulation pump Valvola deviatrice ST1 Under floor heati...

Страница 83: ...orrect zone Press OK to confirm the setting Turn the knob and select COMPLETE MENU Press the OK button to confirm Turn the knob and select 17 HP SYSTEM PARAMETERS Press the OK button to confirm Turn t...

Страница 84: ...draulic module 17 2 4 Boost Time Enabled only with thermoregulation active and thermore gulation type set as Basic Thermoregulation see para meters 421 521 621 It defines the delay time to increment t...

Страница 85: ...t pump in cooling mode at fixed frequency set by the parameter 17 7 5 17 7 5 Fixed compressor frequency Define the compressor frequency during the working mode of the heat pump selected by the paramet...

Страница 86: ...vailability of the Sensys NET service in your country follow the instructions in the Sensys NET Push OK button Turn the knob and select 20 BUFFER 20 0 CONFIGURATION 20 0 0 Buffer Activation Active Buf...

Страница 87: ...ing that a steeper curve should be set 2 The temperature of the room may rise indicating that a gentler curve should be set 3 The temperature of the room remains constant indicat ing that the set curv...

Страница 88: ...perature of the room may fall indicating that a steeper curve should be set 3 The temperature of the room remains constant indica ting that the set curve is exactly right Once you have found the curve...

Страница 89: ...T Basic Thermoreg 4 2 2 Slope 0 2 1 LT 1 3 5 HT 0 6 LT 1 5 HT 4 2 3 Offset 14 14 HT 7 7 LT 0 C 4 2 4 Room Influence Proportional 0 20 C 2 C LT 10 C HT 4 2 5 Max T 20 C 45 C LT 20 C 70 C HT 45 C LT 60...

Страница 90: ...nly Room Outdoor T Basic Thermoreg 5 2 2 Slope 0 2 C 1 C LT 1 C 3 5 C HT 0 6 C LT 1 5 C HT 5 2 3 Offset 14 14 HT 7 7 LT 0 5 2 4 Room Influence Proportional 0 C 20 C 2 C LT 10 C HT 5 2 5 Max T 20 C 45...

Страница 91: ...Z III MGM II 7 2 1 FlowT Offset 0 7 2 2 Auxiliary output setting Heat request External pump Alarm Heat request 7 2 3 External temperature correction 3 3 C 0 C 7 3 Cooling 7 3 0 Flow_T_offset_Cool 0 6...

Страница 92: ...lowT HP Offset 0 10 C 0 C 17 2 4 Boost Time 0 60 min 16 min 17 2 5 External temperature correction 3 3 C 0 C 17 2 6 Active Resistance Stages 1 Stage 2 Stages 3 Stages 2 Stages 17 2 7 Pro Tech anode ac...

Страница 93: ...ON OFF 17 7 3 Rating heating mode OFF ON OFF 17 7 4 Rating cooling mode OFF ON OFF 17 7 5 Compressor frequency setting 18 120 Hz 120 Hz 17 7 6 Fan 1 rpm setting 0 1000 rpm 0 rpm 17 7 7 Fan 2 rpm setti...

Страница 94: ...ump Down Soft Fail Mode only read 17 11 1 HP Error See inverter error table only read 17 11 2 Safety thermostat ON OFF only read 17 11 3 Flowmeter 0 1200 l min only read l min 17 11 4 Flow Switch Open...

Страница 95: ...AUX Input 1 Open Closed only read 17 15 Energy Manager Diagnostics 2 Output 17 15 0 CH Circulator Status only read 17 15 1 HC Pump 2 only read 17 15 2 PCM Diverter Valve CH DHW only read 17 15 3 PCM D...

Страница 96: ...nfiguration 20 0 0 Buffer Activation OFF ON OFF 20 0 1 Buffer Charge Mode Partial Charge 1 sensor Full Charge 2 sensor Partial Charge 1 sensor 20 0 2 Buffer hysteresis 0 20 C 5 C 20 0 3 Buffer heating...

Страница 97: ...the user on how the installed appliances work In particular provide the user with the instruction manual infor ming him of the need to keep the booklet close to the appliance Also inform the user of...

Страница 98: ...water presence in the tank Check anode status 9 40 Hydraulic scheme not defined Hydraulic scheme not selected by parameter 17 2 0 9 41 HIV IN1 not defined Function not selected by parameter 17 1 0 9 4...

Страница 99: ...tant production of domestic hot water To avoid overloading the BUS power supply set microswitch 1 on one of the P C B s in side the equipment connected to the system except the Tank to OFF as illustra...

Страница 100: ...r x 52 DSP MCU communication error x 53 Abnormal communication with IDU control board x 54 Compressor over current shut off x x 55 Compressor heat sink overheat x x ERRORE INVERTER DESCRIZIONE 1 COMPR...

Страница 101: ...MIN 12 Legend 1 Brand 2 Manufacturer 3 Appliance model Serial number 4 Commercial reference 5 Certification number 9 Electrical data 11 Maximum heating pressure 12 Nominal power of heating elements R...

Страница 102: ...102 GB...

Страница 103: ...103 GB...

Страница 104: ...420010850502 07 2020 Ariston Thermo SpA Viale Aristide Merloni 45 60044 Fabriano AN Italy Telefono 0732 6011 Fax 0732 602331 info it aristonthermo com...

Отзывы: