Operating and installation instructions
Thrust actuator ARI-PREMIO
®
-Plus 2G
If a position is programmed for a switched Force switch, e.g. in a final position, the corresponding
relay is only switched if this Force switch is actuated, regardless of the position. This can be the
case if a blockage occurs, for instance. A blockage additionally results in a "Failure" signal because
the desired position cannot be reached.
5.7.1.2 Technical data
5.7.1.3 Installation procedure
5.7.1.4 Electrical connection
Fig. 19
Type
Relay
1 Position
2 Position
3 Warning
4 Failure
Switching capacity: U
B
250V~
6A inductive load / 3A ohm resistive load
30V AC/DC~ 2A
Type
Floating changeover contacts
Max. conductor cross-section
2,5mm²
1,5mm²
Contact material
Gold
Gold
Storage temperature
-40°C ... +85°C
Operating temperature
-20°C ... +70°C
Fig. 17
Fig. 18