7. TROUBLESHOOTING
CHECK BEFORE AND AFTER TROUBLESHOOTING
(A) Check power supply wiring.
* WARNING:
If the following troubleshooting must be done with power being supplied, be careful about any
uninsulated live part that can cause ELECTRIC SHOCK.
(B) Check power supply.
*
Check that voltage is in specified range (+/-10% of the rating)
*
Check that power is being supplied
7-1 Air conditioner does not operate
-
Circuit breaker trips (or fuse blows)
-
When circuit breaker is set to ON, it trips in a few moments (resetting is not possible)
-
Measure insulation resistance there is a possibility of ground fault. If resistance value is 1 Mohm or less,
insulation is defective
-
Circuit breaker trips in several minutes after turning air conditioner ON
-
There is a possibility of short circuit
-
Unit not run
Power is not supplied
Check fuse on PCB assy